Aplisens APR-2200ALW User Manual

Smart pressure/differential pressure transmitters and control instruments, smart level probe, smart level transmitter
Hide thumbs Also See for APR-2200ALW:

Advertisement

Quick Links

DTR.APC.APR.ALW.03
(ENG)
APLISENS
MANUFACTURE OF PRESSURE TRANSMITTERS
AND CONTROL INSTRUMENTS
USER'S MANUAL
SMART PRESSURE TRANSMITTER
type: APC-2000ALW
SMART DIFFERENTIAL PRESSURE TRANSMITTER
type: APR-2000ALW, APR-2200ALW, APR-2000GALW
APR-2000ALW/L, APR-2200ALW/L
SMART LEVEL PROBE
type: APR-2000YALW
SMART LEVEL TRANSMITTER APC-2000ALW/L...
Edition C1
WARSAW AUGUST 2015
Tecnodistribuzione s.r.l. – Via Nataloni, 27 – 47922
Rimini (RN) – ITALY – Tel. +39 0541 790 808 Fax. +39
0541 790 144 Email: td@tecnodistribuzione.it
www. tecnodistribuzione.it

Advertisement

loading
Need help?

Need help?

Do you have a question about the APR-2200ALW and is the answer not in the manual?

Questions and answers

Summary of Contents for Aplisens APR-2200ALW

  • Page 1 APLISENS MANUFACTURE OF PRESSURE TRANSMITTERS AND CONTROL INSTRUMENTS USER’S MANUAL SMART PRESSURE TRANSMITTER type: APC-2000ALW SMART DIFFERENTIAL PRESSURE TRANSMITTER type: APR-2000ALW, APR-2200ALW, APR-2000GALW APR-2000ALW/L, APR-2200ALW/L SMART LEVEL PROBE type: APR-2000YALW SMART LEVEL TRANSMITTER APC-2000ALW/L… Edition C1 WARSAW AUGUST 2015 Tecnodistribuzione s.r.l. – Via Nataloni, 27 – 47922 Rimini (RN) –...
  • Page 2 Changes in the production of transmitters may precede a paper updating for the user. The current user manuals are available at http. www.aplisens.pl Tecnodistribuzione s.r.l. – Via Nataloni, 27 – 47922 Rimini (RN) – ITALY – Tel. +39 0541 790...
  • Page 3 5.1. APC..., APR... C ........................24 OMMON PARAMETERS 5.2. APC-2000ALW M .............. 26 EASUREMENT RANGES AND METROLOGICAL PARAMETERS 5.3. APR-2000ALW, APR-2000ALW/L, APR-2200ALW, APR-2200ALW/L M EASUREMENT RANGES AND METROLOGICAL ..............................27 PARAMETERS 5.4. APR–2000GALW, M .............. 29 EASUREMENT RANGES AND METROLOGICAL PARAMETERS 5.5.
  • Page 4 2” ..... 57 XAMPLE HOW TO INSTALL THE TRANSMITTER WITH A VALVE MANIFOLD TO A PIPE . 15. APR-2200ALW )..58 DIFFERENTIAL PRESSURE TRANSMITTER WITH TWO REMOTE DIAPHRAGM SEALS EXAMPLES . 16. APR-2200ALW ). 58 DIFFERENTIAL PRESSURE TRANSMITTER WITH DIRECT AND REMOTE DIAPHRAGM SEAL EXAMPLES .
  • Page 5 1. Introduction 1.1. This “Appendix Exd.ATEX” applies to transmitters of types APC-2000ALW/XX, APR-2000ALW/XX, APR-2200ALW/XX and APR-2000YALW/XX in Exd versions only, marked on the rating plate as shown in p.3 and denoted Exd in the Product Certificate. 1.2. The appendix contains supplementary information relating to the Exd (flame-proof) versions compatible with ATEX directive of mentioned transmitters.
  • Page 6 Appendix Exd.ATEX. (ENG) Items b), c), d) are available on www.aplisens.pl 5. Power supply and exploitation of transmitters. 5.1. The transmitter connecting should be made after introduction with present instruction content. Electrically transmitter should be connected according to scheme at p.6 Appendix Exd.ATEX.
  • Page 7 DTR.APC.APR.ALW.03 (ENG) Appendix Exd.ATEX 6. The electrical connection way of transmitter’s series: APC-2000ALW/XX, APR-2000ALW/XX, APR-2200ALW/XX and APR-2000YALW/XX in Exd version Hazardous area Safe area short-circuit( jumper)  Ex power supply TEST TEST SIGNAL see p.5.  Communicator @%& Fuse: In = 0,05A, Un = 250V according to EN 60127 Fig.
  • Page 8 DTR.APC.APR.ALW.03 (ENG) Appendix Exd.ATEX Table 1. Permitted cable glands Type Producer Screw Feature Other marking No of certificate 501/423 HAWKE M20x1.5 Exd IIC dimension OS, O, A Baseefa 06 ATEX 0056X 501/421 HAWKE M20x1.5 Exd IIC dimension OS, O, A Baseefa 06 ATEX 0056X ICG 623 HAWKE...
  • Page 9 APC-2000ALW/XX, APR-2000ALW/XX, APR-2200ALW/XX and APR-2000YALW/XX in Exd versions only, marked on the rating plate as shown in p.3 and denoted Exd in the Product Certificate. 1.2. The appendix contains supplementary information relating to the Exd (flame-proof) versions compatible with IECEx certificate of mentioned transmitters.
  • Page 10 Appendix Exd.IECEx. (ENG) Items b), c), d) are available on www.aplisens.pl 5. Power supply and exploitation of transmitters 5.1. The transmitter connecting should be made after introduction with present instruction content. Electrically transmitter should be connected according to scheme at p.6 Appendix Exd.IECEx.
  • Page 11 In danger zone don’t unscrew transmitter covers and don’t change the display position or its back lighting. 6. The electrical connection way of transmitter’s series: APC-2000ALW/XX, APR-2000ALW/XX, APR-2200ALW/XX and APR-2000YALW/XX in Exd version  According to the p.6 DTR.APC.APR.ALW.03(ENG) Appendix Exd.ATEX.
  • Page 12 DTR.APC.APR.ALW.03 (ENG) III. APPENDIX Exi.ATEX APC–2000ALW PRESSURE TRANSMITTER, 1453 APR–2000ALW, APR–2200ALW, APR–2000GALW, APR-2000ALW/L, APR-2200ALW/L DIFFERENTIAL PRESSURE TRANSMITTERS, APR–2000YALW LEVEL PROBE, APC–2000ALW/L LEVEL TANSMITTER Ex VERSION in accordance with ATEX directive 1. Introduction 1.1. This “Appendix Exi.ATEX” applies to transmitters of types APC–2000ALW, APR–2000ALW, APR–2200ALW,...
  • Page 13 Appendix Exi.ATEX. (ENG) Items b), c), d) are available on www.aplisens.pl 5. Permitted input parameters (based on data from the FTZÚ 08 ATEX 0020X certificate, and certification documentation) The transmitters should be powered via the associated power feeding and measurement devices provided with the relevant intrinsic-safe certificates.
  • Page 14 DTR.APC.APR.ALW.03 (ENG) Appendix Exi.ATEX If Uo < then parameters Uq, Io, Po are interrelated as follows: Uo(Uq – Uo) Uq = Rw = Po = for Uo ≤ 1/2Uq 5.5. For power supply with a rectangular output characteristic in „Version SC" or “Version SC, SA” -40ºC ...
  • Page 15 Ex power supply TEST TEST SIGNAL see p.5.  Aplisens KAP-03Ex Communicator @%& To measure the current in the transmitter without disconnecting the signalling circuit, connect a milliammeter to transmitter terminals TEST+, TEST-. In hazardous areas, connections to the control terminals must be made using only instruments which are permitted to be used in such areas.
  • Page 16 DTR.APC.APR.ALW.03 (ENG) IV. APPENDIX Exi.IECEx APC–2000ALW PRESSURE TRANSMITTER, APR–2000ALW, APR–2200ALW, APR–2000GALW, APR-2000ALW/L, APR-2200ALW/L DIFFERENTIAL PRESSURE TRANSMITTERS, APR–2000YALW LEVEL PROBE, APC–2000ALW/L LEVEL TANSMITTER Ex VERSION in accordance with IECEx certificate 1. Introduction 1.1. This “Appendix Exi.IECEx” applies to transmitters of types APC–2000ALW, APR–2000ALW, APR–2200ALW,...
  • Page 17 Appendix Exi.IECEx. (ENG) Items b), c), d) are available on www.aplisens.pl 5. Permitted input parameters (based on data from the IECEx FTZÚ 14.0026X certificate, and certification documentation) The transmitters should be powered via the associated power feeding and measurement devices provided with the relevant intrinsic-safe certificates.
  • Page 18 DTR.APC.APR.ALW.03 (ENG) Appendix Exi.IECEx 5.7. Load resistance: - from 28V linear supply 28V – 10.5V – (300Ω* 0.0225A) · Ro max [Ω] = 0.0225A - from a source with trapezial or rectangular characteristic supply Usup. – 10.5V Ro max [Ω] = 0.0225A *) barrier resistance.
  • Page 19 022 814 07 78 T. +48 22 814 07 77 www.aplisens.pl www.aplisens.pl F. +48 22 814 07 78 APLISENS SA - Produkcja Przemysłowej POLAND Aparatury Pomiarowej i Elementów Automatyki smart pressure transmitter INTELIGENTNY PRZETWORNIK CIŚNIENIA TYP: APC-2000ALW / XX...
  • Page 20 Declaration of Conformity - on request; User's Manual; Copies of certificates - on request; Calibration certificate - on request. Items: b, c, d can be found at: www.aplisens.pl APC-2000ALW for MID applications. Technical parameters Transmitter supply (Usup) 13.5* ÷ 28V DC for Exi versions 13.5* ÷45V DC...
  • Page 21 Transmitters in the MID version are equipped with one of the following types of Aplisens pressure ports: M, P, G1/2 G1/4, GP, R1/2, 1/2NPT (see p.5.2.4 DTR.APC.APR.ALW.03(ENG)). Pressure connection type, which designation given is the type of transmitter, the purchaser should agree with the manufacturer.
  • Page 22 DTR.APC.APR.ALW.03 (ENG) Appendix MID For electrical connection should be use twisted pair cable; shielded or not shielded, flexible, with diameter 5mm ≤  ≤ 9mm, complies to ATEX standards. Example of the type of cable is shown below. Producer Technokabel LAPPKABEL ®...
  • Page 23 DTR.APC.APR.ALW.03 (ENG) Appendix MID 7. APC-2000ALW in MID application. Electronic display Electronic indicating device (display), built-in the APC-2000ALW transmitters, are not controlled metrologically and as such cannot be used for clearing in accordance with EN12405-1:2005+A2:2010. 8. APC-2000ALW in MID application. Protection against unauthorized manipulation 8.1.
  • Page 24 PC with Windows XP or higher, with at least 512 MB of RAM;  Report 2 APLISENS software. A computer with a converter must be connected to the transmitter as shown in Figure 2a or 2c for the load resistance Ro <240 , see User's Manual DTR.APC.APR.ALW.03(ENG) p.16. Drawings. After starting Report 2 program read data from the transmitter.
  • Page 25 It includes essential recommendations concerning installation and use, as well as emergency procedures. The parameters and information specified for transmitters identified here as APC..., APR... also apply to transmitters: APC-2000ALW, APR-2000ALW, APR-2200ALW, APR-2000ALW/L, APR-2200ALW/L, APR-2000GALW, APR-2000YALW, APC-2000ALW/L and their explosion-proof versions, as well as all the variations differing by the type of the process terminals.
  • Page 26 (current loop). The use of smart electronics enables regulation of the zero point, the measurement range, damping, radical conversion characteristic and other functions using an Aplisens KAP communicator or from a PC using a HART/RS232 or HART/USB/Bluetooth Converter and Aplisens “Raport 2” configuration software.
  • Page 27 DTR.APC.APR.ALW.03 (ENG) Safe working area for normal transmitter (grid) upper colour area. Output updating time 500ms Additional electronic damping 0...60s 5.1.2. APC..., APR... Construction materials Diaphragm seal for APC... Stainless steel 1.4404/1.4435(316L)(PED version) or Hastelloy C276 Diaphragm seal for APR... Stainless steel 1.4404/1.4435(316L)(PED version) or Hastelloy C276 Sensing module Stainless steel 1.4404 (316L)
  • Page 28 DTR.APC.APR.ALW.03 (ENG) 5.2. APC-2000ALW Measurement ranges and metrological parameters 5.2.1. APC..., Measurement ranges Nominal measuring range Overpressure limit Minimum set range Rangeability  (FSO) (without hysteresis) 0...1000bar (0...100MPa) 10bar (1MPa) 100:1 1200bar (120MPa) 0...300bar (0...30MPa) 3bar (300kPa) 100:1 450bar (45MPa) 0...160bar (0...16MPa) 1.6bar...
  • Page 29 R1/2-type connector with R1/2 tread, available for PED version; CG1/2-type connector with G1/2 tread and flush diaphragm, available for PED version; other connection types by arrangement. 5.3. APR-2000ALW, APR-2000ALW/L, APR-2200ALW, APR-2200ALW/L Measurement ranges and metrological parameters 5.3.1. APR-2000ALW, APR-2000ALW/L, Measurement ranges...
  • Page 30 PED version. APR-2000ALW, APR-2000ALW/L with single direct diaphragm seal – as in the example (Fig.11) or with other diaphragm seals in accordance with “DIAPHRAGM SEALS” catalogue cards. 5.3.7. APR-2200ALW, APR-2200ALW/L, Pressure Connectors - diaphragm seals see “DIAPHRAGM SEALS” catalogue cards.
  • Page 31 0.1 % / 10bar * zeroing in static pressure conditions with zero differential pressure eliminates this error; Medium density range – up to 1.1 g/cm 3 – (standard version) – over 1.1 g/cm 3 – (special version by arrangement with Aplisens...
  • Page 32 DTR.APC.APR.ALW.03 (ENG) 5.6. APC–2000ALW/L…. Measurement ranges and metrological parameters 5.6.1. APC–2000ALW/L…level transmitter. Measurement ranges. N Nominal range (FSO) 0...20m H 0...10m H 0...2.5m H Minimum set range 2m H 1m H 0.5m H Possibility of zero shift 0...18m H 0...9m H 0...2m H Overpressure limit 0...200m H...
  • Page 33 DTR.APC.APR.ALW.03 (ENG) 5.7. APC … APR … Environmental parameters 5.7.1. Electromagnetic Compatibility (EMC), 5.7.3. Climatic Immunity Immunity Criterion according to EN 61326-1,2 Temperature: EN 60068-2-1, EN 60068-2-2 Electrostatic Discharge (ESD): hot: T = 55ºC, RH = max 55% EN 61000-4-2 cold: T = -25ºC, level 3, contact ±6kV...
  • Page 34 DTR.APC.APR.ALW.03 (ENG) 6. CONSTRUCTION 6.1. Principle of measurement. Electronic system construction The electrical signal from the sensor which is proportional to the pressure is sent to a digital analog input and converted to a digital signal. The digital signal is transmitted through optoelectronic galvanic barrier to conditioning module.
  • Page 35 DTR.APC.APR.ALW.03 (ENG) 7. PLACE OF INSTALLATION 7.1. General recommendations 7.1.1. The smart pressure transmitter and differential pressure transmitter can be installed both indoors and outdoors. It is recommended that transmitters intended for outdoor use be placed in a box or under cover. 7.1.2.
  • Page 36 (for example) straight connecting elements with C type nuts. If elastic impulse lines are used, the transmitter should be additionally fastened to a pipe, panel or supporting construction. 8.2.2. The APR-2000ALW, APR-2000ALW/L and APR-2200ALW, APR-2200ALW/L can be installed using the ø25 Fastener (Fig.12) on an ø25 pipe or on a flat surface using an angle bracket.
  • Page 37 The transmitter sensor is immersed in measured medium. The sensor can be hung on the power cable by using a Aplisens SG handle , but especially in the case of long cables, or if are opportunities of hooking protruding elements when the cable is pulling up, it is recommended that the sensor suspended on a steel rope using the sensor lug.
  • Page 38 (see the table, column 3). Also external protective devices may be used, e.g. the UZ-2 Aplisens system, or others. When the transmission lines are long, it is advantageous to use one protective device near the transmitter (or inside it), and another near entry points to other devices used in conjunction with it.
  • Page 39 The transmitter may also be calibrated, by taking readings with the input pressure controlled using a standard device. These process and zero-point adjustments are called “Calibration”. 10.2.4. Configuration and Calibration of the transmitter are carried out using an Aplisens KAP communicator, certain HART communicators or a PC with HART/RS232 converter and Aplisens “Raport 2” software.
  • Page 40 DTR.APC.APR.ALW.03 (ENG)
  • Page 41 DTR.APC.APR.ALW.03 (ENG) The selected unit should be confirmed by pressing [◙]. After approval the parameter transmitter will confirm the party of command by the "DONE" or report the error number. The "← BACK" cause goes up one level. Descriptions: Local Menu Submenu Notice Return from the local Menu to the normal operation of the transmitter...
  • Page 42 DTR.APC.APR.ALW.03 (ENG) Set the decimal point position on LCD2. In a situation where the value provided to display on the display LCD2 cannot be displayed properly LCD2DP due to the position of the decimal point, this is indicated by displaying the four flashing dots •...
  • Page 43 DTR.APC.APR.ALW.03 (ENG) 10.2.6. View local LCD display Changes of the display options in local MENU are possible using buttons, or remote way using communicator, or the PC software. If it is necessary the display switching off is also possible. The display switching of function is possible with using communicator or PC software only.
  • Page 44 DTR.APC.APR.ALW.03 (ENG) 10.2.8. Configuration of the APR-2200ALW transmitters to measure the level, density of liquid and phase boundary Configuration of the APR-2200ALW transmitters to measure the level of liquid in a tank. KAP-03 Configuration of the APR-2200ALW transmitters to measure density of liquids.
  • Page 45 DTR.APC.APR.ALW.03 (ENG) KAP-03...
  • Page 46 Set the square root output transmitter signal and the cutoff point [in % FS]; remotely using computer and Aplisens Raport 2 software according with p. 10.2.4 or locally with transmitter buttons (up to 1% only) according to p. 10.2.5 of the Manual.
  • Page 47 DTR.APC.APR.ALW.03 (ENG) APR-2000ALW transmitter analog output signal with setting cutoff point in n%. The device configuration example: Transmitter configuration parameters  Basic range 0…100 kPa  Set range 0…50 kPa  Cutoff 5% of the set range Assemble the measuring system in accordance with Figure 2 and run Raport2 according to IO.RAPORT2: ...
  • Page 48 DTR.APC.APR.ALW.03 (ENG) 11. INSPECTIONS AND SPARE PARTS 11.1. Periodic service Periodic inspections should be made in accordance with the regulations to which the user is subject. During inspection, the pressure connectors should be checked for loose connections and leaks, the electrical connectors should be checked with regard to tightness and the state of the gaskets, cable glands, and the diaphragm seals should be checked for tarnishing and corrosion.
  • Page 49 DTR.APC.APR.ALW.03 (ENG) 14. SCRAPPING, DISPOSAL Waste or damaged transmitters should be dismantled and disposed of in accordance with Directive (2002/96/EC) on waste electrical and electronic equipment (WEEE) or returned to the manufacturer. 15. ADDITIONAL INFORMATION The manufacturer reserves the right to make constructional and technological changes which do not lower the quality of the transmitters.
  • Page 50 DTR.APC.APR.ALW.03 (ENG) Connection of the APC…, APR… transmitter Connect as shown in Fig. 2a. If it is necessary to enable communication with the transmitter, a communicator or converter can also be connected. Optional connection configurations to communication devices are shown below. Communicator or converter connection near to a switch box In order to enable communication with a transmitter at a distant location via connection near to a switch box, make sure that the resistance Ro from the point of connection of the communicator to the power supply source...
  • Page 51 DTR.APC.APR.ALW.03 (ENG) Communicator or converter connection to the transmitter’s terminals In order to enable local communication by connecting a communicator or converter to the transmitter’s terminals, make sure that the resistance Ro from the transmitter’s terminals to the power supply source lies within the range of 240÷1100 ...
  • Page 52 DTR.APC.APR.ALW.03 (ENG) HART/USB/Bluetooth Converter Raport 2 JUMPER Converter HART/RS232 Current loop 4÷20 mA  SIGNAL @%& Fig.2d. The link of transmitter and communicator or converter to <SIGNAL+> <SIGNAL-> transmitter terminals in case of the resistance in current loop is smaller than 240Ω. If Ro in current loop is lower than 240Ω...
  • Page 53 DTR.APC.APR.ALW.03 (ENG) Fig. 4. APC..., APR..display rotation possibility, configuration buttons.
  • Page 54 DTR.APC.APR.ALW.03 (ENG) ±180 with 90 pitch unscrew the Configuration display cover buttons and casing display screws Move the electronic unit from transmitter casing, take up the upper part of the casing with display from the catch and revolve its to left or to right to the display setting at needed position.
  • Page 55 DTR.APC.APR.ALW.03 (ENG) Fig.6a. M-type connector Fig.6b. Socket for M-type connector with M20x1.5 thread min.15 diaphragm seal Fig.7a. P-type connector Fig.7b. Socket for P-type connector with M20x1.5 thread min.15 diaphragm seal Fig.8a. CM30x2-type connector Fig.8c. Socket for Fig.8b. Socket for with flush diaphragm CM30x2-type CM30x2-type connector with M30x2 thread,...
  • Page 56 DTR.APC.APR.ALW.03 (ENG) 24,5 -0.5 14,5 min. Fig.9b. Socket for G1/2-type connector. Fig.9a. G1/2 -type connector with G1/2" thread, 21,5 -0,2 min.10,5 Sealing: teflon 21,2 x 24,4 x 1,7 O-ring 15x2 20,5 -0,1 27-6kt. Fig.9c. CG1/2 -type connector Fig.9d. Socket for with flush diaphragm CG1/2 - type connector with G1/2"...
  • Page 57 DTR.APC.APR.ALW.03 (ENG) 2 x M6 4 x M10 PD electrical connector, IP65 DIN 43650 connector Lock preventing Earthing terminal  Cable  Cable rotation of the casing Fig. 10. APR-2000ALW differential pressure transmitter with C type vented covers. S-T type tube flanged diaphragm seal S-P type...
  • Page 58 34,5 Assembly Kit ("Mounting bracket  25" made by APLISENS) for fitting differential pressure transmitters with P-type connector on a  25 pipe see catalogue cards "Fitting accessories". Fig. 12. Example: how to install the APR-2200ALW transmitters with remote diaphragm.
  • Page 59 DTR.APC.APR.ALW.03 (ENG) 161,5 Fastener C2 for fitting differential pressure transmitters with C-type connection to a 2” pipe or to a wall. see catalogue cards „Fitting accessories” Fig. 13. Example: how to install the APR-2000ALW transmitter on a vertical or horizontal pipe. Fastener C2 for fitting differential pressure transmitters with a valve manifold to a 2”...
  • Page 60 S-CompK GP-type or  S-CompK -type remote diaphragm seal S-DINK type remote diaphragm seal  Fig. 15. APR-2200ALW differential pressure transmitter with two remote diaphragm seals (examples). Fig. 16. APR-2200ALW differential pressure transmitter with direct and remote diaphragm seal (examples).
  • Page 61 DTR.APC.APR.ALW.03 (ENG) Fastening on a pipe Fastening to a wall Fig. 17. Example: how to install the APC..., APR... transmitter.
  • Page 62 DTR.APC.APR.ALW.03 (ENG) FIg. b. Fig. a. Fig. c.   Adapter for valve manifold or steel impulse lines  SW27 1/4" NPT 2otw. M8x10  (G1/2")   Adapter M20x1.5/  Weidable impulse Valve manifold line connector Fig. 18. APR-2000GALW smart differential pressure transmitter for low ranges. a) APR-2000GALW transmitter –...
  • Page 63 DTR.APC.APR.ALW.03 (ENG)     Stanless steel or aluminium tube up to 6m long (by order)  Fig. 19. APR–2000YALW smart level probe for pressure tanks. Rys.19. Sonda poziomu APR-2000YALW.
  • Page 64 DTR.APC.APR.ALW.03 (ENG) scale:2:1 MINIMUM WIDTH OF JOINT AND MAXIMUM GAP FOR GROUP IIC ENCLOSURES width of joint diameter minimum quantity (min. real) N° according to of joint PN-EN 60079-1:2004(U) +0,027 -0,040   13,2 0,097 width of joint min.12,5 -0,070 min.5 threads M72x1,5 M72x1,5...
  • Page 65 DTR.APC.APR.ALW.03 (ENG) Mounting bracket PC  4 holes (spacing of holes 38x38mm)    APC-2000ALW/LSG-25.S APC-2000ALW/LSG-25  Submersible sensor Submersible sensor (sensor specification according to (sensor specification according to APC-2000ALW/LSG-25S-Titan data sheet for SGE-25S) data sheet for SGE-25) Submersible sensor (sensor specification according to data sheet for SGE-25S-Titan) Fig.
  • Page 66 DTR.APC.APR.ALW.03 (ENG) Mounting bracket PC  4 holes (spacing of holes 38x38mm)   APC-2000ALW/LM APC-2000ALW/LSP Transmtter with M type sensor Transmtter with SP type diaphragm seal Fig. 23. APC–2000ALW/LM & APC–2000ALW/LSP smart pressure or level transmitters.
  • Page 67 DTR.APC.APR.ALW.03 (ENG) Mounting bracket PC  4 holes  4 holes (spacing of holes 38x38mm) L (do 25m) 34,5 Transmitter Sensor working temperature -40...+80°C working temperature -40...+100°C IP66/67 IP68 Fig. 24. An example of the differential pressure transmitter APR-2200ALW/L.
  • Page 68 DTR.APC.APR.ALW.03 (ENG) M20x1,5 or G1/2" Moving M20x1,5 or G1/2" Moving Impulse line 10 MPa max. Marerials: P235T1 (PN R35) (SO) 1.4301 (304) Ordering code: Impulse line - (S) or (SO) /M20x1,5 or G1/2" M20x1,5 G1/2" Siphon tube  25 MPa max.