Remote Condenser Location - Scotsman C2648 - SERVICE MANUAL 11-2010 Service Manual

Hide thumbs Also See for C2648 - SERVICE MANUAL 11-2010:
Table of Contents

Advertisement

C2648 Service Manual - Installation

Remote Condenser Location

Use the following for planning the placement of the
condenser relative to the ice machine
Location Limits - condenser location must not
exceed ANY of the following limits:
Maximum rise from the ice machine to the
condenser is 35 physical feet
Maximum drop from the ice machine to the
condenser is 15 physical feet
Physical line set maximum length is 100 feet.
Calculated line set length maximum is 150.
Calculation Formula:
Drop = dd x 6.6 (dd = distance in feet)
Rise = rd x 1.7 (rd = distance in feet)
Horizontal Run = hd x 1 (hd = distance in feet)
Calculation: Drop(s) + Rise(s) + Horizontal
Run = dd+rd+hd = Calculated Line Length
Max 35'
hd
Max
15'
rd
Configurations that do NOT meet these
requirements must receive prior written
authorization from Scotsman.
Do NOT:
Route a line set that rises, then falls, then
rises.
Route a line set that falls, then rises, then falls.
Calculation Example 1:
The condenser is to be located 5 feet below the ice
machine and then 20 feet away horizontally.
5 feet x 6.6 = 33. 33 + 20 = 53. This location would
be acceptable
Calculation Example 2:
The condenser is to be located 35 feet above and
then 100 feet away horizontally. 35 x 1.7 = 59.5.
59.5 +100 = 159.5. 159.5 is greater than the 150
maximum and is NOT acceptable.
40.35"
dd
Remote Condenser
Located ABOVE Ice
Machine
Remote Condenser Located
BELOW Ice Machine
November 2010
Page 8
Condenser Distance &
Location Schematic

Advertisement

Table of Contents
loading

This manual is also suitable for:

C2648sr-3C2848mr-3

Table of Contents