BPS Alarms
This chapter provides information about the external alarm conditions of the
Dell backup power supply (BPS). The Dell backup power supply (BPS) LED
is solid amber with an audible alarm.
Table A-1. External Alarm Conditions
Alarm
Description
Battery
Battery voltage is lower
disconnected
than the batteries
disconnected level
defined for this UPS.
This may be due to a
blown fuse,
intermittent battery
connection or battery
cable being
disconnected.
If EBMs are attached
this alarm will not
trigger unless the EBMs
are also disconnected
since they are paralleled
with the battery bus.
Service
A faulted battery string
battery
has been detected and
as a result the battery
charger has been
disabled until it is
replaced.
Input AC over
Utility RMS voltage
voltage
greater than maximum
valid utility threshold.
Audible
Corrective Action
Beeping
Reconnect the battery by
following the steps in the
Getting Started Guide.
Beeping
Battery needs to be replaced.
Contact Dell.
Beeping
Check the utility power.
A
BPS Alarms