Eastron SDM630 Series, SDM630-MB, SDM630-MB-2T Manual

Eastron SDM630 Series, SDM630-MB, SDM630-MB-2T Manual

Also See for SDM630 Series:

Advertisement

Eastron SDM630 Series, SDM630-MB, SDM630-MB-2T Manual

Introduction

Product Introduction

SDM630 Mbus series including models: SDM630-MB & SDM630-MB-2T.
The meter measures and displays the characteristics of single phase two wire (1p2w), three phase three wire (3p3w) and three phase four wire (3p4w) supplies, including voltage, frequency, current, power, active and reactive energy, imported or exported. Energy is measured in terms of kWh, kVArh. Maximum demand current can be measured over preset periods of up to 60 minutes.
These units are Max. 100A direct connected and do not need to connect with external current transformers(CT). An M-Bus communication port is available on the meters for remote data transmission. SDM630-MB-2T also offers a 2 tariff port for dual power source measurement.

Product Characteristics

  • Bi-directional measurement IMP & EXP
  • M-Bus EN13757-3
  • Multi-parameters measurement
  • LCD with white backlit, adjustable backlit time

Measurements:

  • Phase voltage: V1, V2, V3
  • Line voltage: V1-2, V2-3, V3-1
  • Current: I1, I2, I3, IN
  • Active power: P1, P2, P3, P_total (total active power)
  • Reactive power: Q1, Q2, Q3, Q_total (total reactive power)
  • Apparent power: S1, S2, S3, S_Total (total apparent power)
  • Frequency: Hz
  • Power factor: PF
  • Active energy: Ep_imp (import active energy), Ep_exp (export active energy), Ep_total (total active energy)
  • Reactive energy: Eq_imp (import reactive energy), Eq_exp (export reactive energy), Eq_total (total reactive energy)
  • THD-I and THD-U
  • Maximum demand: MD

Setup:

  • M-Bus parameters
  • Demand interval time
  • Backlit time
  • Supply system 1p2w, 3p3w, 3p4w
  • Clear re-settable energy & demand info.
  • Password modification

Technical Parameters

Technical Parameters

Voltage AC (Un) 3*230/400VAC
Voltage range 100 - 277V AC( L-N )
Voltage between phase 100 to 480V AC ( L-L)
Current input 0.3-10(100)A
Over current withstand 30Imax for 0.01S
Frequency rating value 50/60Hz
AC voltage withstand 4KV/1min
Impulse voltage withstand 6kV – 1.2/50µS waveform
Power consumption ≤ 2W/10VA
Display LCD with white backlit
Max. reading 999999.99 kWh/kVArh

Mechanical Characteristics

Weight ≈325g
IP Degree of Protection (IEC 60529) IP51 front display IP20 whole meter
Dimensions (DxHxW) 66*100*72mm
Mounting DIN Rail 35mm
Material of Meter Case Self-extinguishing UL 94 V-0
Mechanical Environment M1

Performance Criteria

Operation humidity ≤90% Non-condensing
Storage humidity ≤95% Non-condensing
Operating temperature -40℃~+70℃
Storage temperature -40℃~+80℃
Pollution Degree 2
Altitude ≤2000m
Vibration 10Hz to 50Hz, IEC 60068-2-6

Electromagnetic Compatibility

Electrostatic Discharge IEC 61000-4-2
Immunity to Radiated Fields IEC 61000-4-3
Immunity to Fast Transients IEC 61000-4-4
Immunity to Impulse Waves IEC 61000-4-5
Conducted Immunity IEC 61000-4-6
Immunity to Magnetic Fields IEC 61000-4-8
Immunity to Voltage Dips IEC 61000-4-11
Radiated Emissions EN55032 Class B
Conducted Emissions EN55032 Class B

Safety

Over-voltage Category CAT III
Installation Category CAT III
Insulating Encased Meter of Protective Class II

Accuracy

Parameters Accuracy Resolution
Voltage ±0.5% 0.1V
Current ±0.5% 0.001A
Frequency ±0.2% 0.01Hz
Power Factor ±0.01 0.001
Active Power ±1% 0.001kW
Reactive Power ±1% 0.001kVAr
Apparent Power ±1% 0.001kVA
Active Energy Class 1 or 0.5 IEC62053-21 Class B or C EN50470-3:2022 0.01kWh
Reactive Energy Class 2 IEC 62053-23 0.01kVArh

Outputs

M-bus Communication
The meter provides an M-Bus port for remote communication. The protocol fully comply with EN13757-3. The following communication parameters can be configured via M-bus communication:

Baud rate 0.6k, 1.2k, 2.4k(default), 4.8k, 9.6k bps
Parity NONE/ ODD / EVEN(default)
Stop bits 1 or 2
M-Bus network primary address 001 to 250
M-Bus network secondary address 00 00 00 00 to 99 99 99 99
(default: the last 8 digits of SN)

Dual Source Measurement - 2 Tariffs
SDM630-MB-2T can measure energy from two different power supplies upon detection of a 230V voltage signal. For example, when public grid is power off and electric generator is on, the meter switches to tariff 2 measurement automatically.
The meter can also be used as a tariff meter. The tariff is controlled by an external time relay.

Pulse output
The meter is equipped with pulse output, which is fully isolated from the inside circuit. That generates pulses in proportion to the measured energy. The pulse output is polarity dependent, passive transistor output requiring an external voltage source for correct operation. For this external voltage source, the voltage shall be 5-27V DC, and the maximum input current shall be 27mA DC.
warningATTENTION: Pulse output must be fed as shown in the wiring diagram on the left.
Scrupulously respect polarities and the connection mode.
Opto-coupler with potential-free SPST-NO Contact.
Contact range: 5~27VDC
Max. current Input: 27mA DC

Pulse outputs type Two independent channels of optocoupler passive pulse outputs
Pulse output 1 ( configurable ) Type kWh/kVArh ( total, imported, exported) Default: export kWh
Constant dFt, 0.01, 0.1, 1, 10, 100, 1000 kWh/kVArh per imp Default: dFt = 0.0025 kWh/imp
Width 200, 100, 60mS
Default: 200mS
Pulse output 2 ( fixed ) Type Total kWh
Constant 400imp/kWh
Width 100mS

Dimensions

Dimensions

Wiring Diagram

3P4W 3P3W
1P2W(L+N)

*230V/2T terminal for SDM630-MB-2T only

Terminal
Measurement Connection Screw Connection
Strip Length 12-13mm
Screw M5
Rigid/Supple 4-25mm²
Tightening Torque 3.5Nm
Model PH2
Terminal
Measurement Connection Screw Connection
Strip Length 6-7mm
Screw M2.5
Rigid/Supple 0.5-1.5mm² (22 ~ 14AWG)
Tightening Torque 0.4Nm
Model PH0

Operation

Installation Display

The first screen lights up all display segments and can be used as a display check.
The second screen and the third screen indicates the firmware installed in the unit.
Note:the actual display might be different with the left on here.
The interface performs a self-test and indicates the result if the test passes.

Button Functions

Button Short click Long press (3s)
Display mode Setup mode Display mode Setup mode
V1 V2 V3 V1-2 V2-3 V3-1 I1 I2 I3 IN V %THD I %THD Return to previous menu
Hz PF PF1 PF2 PF3 MD of I1 I2 I3 MD of Power Previous page or increase value Primary address Second address Baud rate Parity bit Stop bit CRC All display segments
P1 P2 P3 Q1 Q2 Q3 S1 S2 S3 P-t Q-t S-t Next page or decrease value
Active E-t Reactive E-t Imp Active E Exp Active E Imp Reactive E Exp Reactive E Move to right side Enter setup mode Confirm setting
Note: For tariff meters, the display is different. Please refer to the following content for detailed information.

Measurements

Voltage and current
Each successive pressing of the button selects a new range:

Phase to neutral voltage
(Not available under 3P3W)
Phase to phase voltage
(Not available under 1P2W)
Current of each phase
Neutral current
(Not available under 3P3W &1P2W)
Phase to neutral voltage THD%
(Phase to phase voltage THD% under 3P3W)
Phase current THD%

Frequency, Power factor and Demand
Each successive pressing of the button selects a new range:

Frequency and Power Factor (total)
Power Factor of each phase
(Not available under 3P3W &1P2W)
Maximum current demand of each phase
Maximum total power demand

Power
Each successive pressing of the button select a new range:

Instantaneous Active Power in kW (Not available under 3P3W &1P2W)
Instantaneous Reactive Power in kVAr (Not available under 3P3W &1P2W)
Instantaneous Volt-amps in kVA
(Not available under 3P3W &1P2W)
Total kW, kVAr, kVA

Energy
Each successive pressing of the button shows following measurements:

For SDM630-MB:

Total active energy in kWh
Total reactive energy in kVArh
Imported active energy in kWh
Exported active energy in kWh
Imported reactive energy in kVArh
Exported reactive energy in kVArh

For SDM630-Mbus-2T:

Total active energy in kWh
Total reactive energy in kVArh
T1 active energy in kWh
(T1 run means under T1 calculation )
T2 active energy in kWh
T1 active energy in kWh (T1 run means under T1 calculation )
T2 reactive energy in kVArh

SDM630-MB-2T shows tariff kWh/kVArh instead of imported and exported kWh/kVArh.

Auxiliary Mode

Each successive Long pressing of the button enter the auxiliary and each successive pressing of the button select a new range:

Primary Address
Second Address
Baud Rate
Parity Bit
Stop Bit
CRC
All display segments

Setup Mode

The meter's settable parameters are password protected. Each successive Long pressing on the button to enter setup mode. Some menu items, such as password and CT, require a four-digit number entry while others, such as supply system, require selection from a number of menu options.

Menu Option Selection

  1. Use the and buttons to scroll through the different options of the set up menu.
  2. Long press to confirm your selection.
  3. If an item flashes, then it can be adjusted by the and buttons.
  4. Having selected an option from the current layer, long press to confirm your selection.
  5. Having completed a parameter setting, press to return to a higher menu level.
    You will be able to use the and buttons for further menu selection.
  6. On completion of all setting-up, press repeatedly until the measurement screen is restored.

Number Entry Procedure
When setting up the unit, some screens require the entering of a number. In particular, on entry to the setting up section, a password must be entered. Digits are set individually, from left to right.
The procedure is as follows:

  1. The current digit to be set flashes and is set using the buttons.
  2. Short press to confirm the digit setting and remove to the next.
  3. After setting the last digit, long press to confirm the setting.
  4. Press to return to a higher menu level.
Settings interface Set status Optional configuration
Password
Default: 1000
Primary address setting
Range: 001~250 Default: 001
Secondary address
setting Range:
00000000 to 99999999 Default: the last 8 digits
of SN
Baud rate setting
Option: 0.6k, 1.2k, 2.4k,
4.8k, 9.6k bps
Default: 2.4k bps
Parity bit setting
Option: EVEN, ODD,
NONE
Default: EVEN
Stop bit setting
Option: 1, 2
Default: 1
Pulse output setting
Option: kWh or kVArh
(import, export, total)
Default: export kWh
Pulse rate setting
Option: dFt, 0.01, 0.1, 1, 10, 100, 1000 kWh/kVArh per imp
Default: dFt = 0.0025 kWh/kVArh per imp
Pulse duration setting
Option: 200, 100, 60mS
Default: 100mS
Demand interval time setting
Option: 0, 5, 8, 10, 15, 20,
30, 60min
Default: 60min
Backlit time setting
Option: on, off, 5, 10, 30,
60, 120 min
Default: 60 min
System type setting
Option: 3P4W, 3P3W,
1P2W
Default: 3P4W
Clear
Option: demand, energy
Password setting
Range: 0000~9999
Default: 1000

Risk Information

Information for Your Own Safety
This manual does not contain all of the safety measures operating the equipment (module, device) for different conditions and requirements. However, it does contain information which you must know for your own safety and to avoid damages. These information are highlighted by a warning triangle indicating the degree of potential danger.

This means that failure to observe the instruction can result in death, serious injury or considerable material damage.

This means hazard of electric shock and failure to take the necessary safety precautions will result in death, serious injury or considerable material damage.

Qualified personnel
Operation of the equipment (module, device) described in this manual may only be performed by qualified personnel. Qualified personnel in this manual means person who are authorized to commission, start up, ground and label devices, systems and circuits according to safety and Regulatory standards.

Proper handling
The prerequisites for perfect, reliable operation of the product are proper transport, proper storage, installation and proper operation and maintenance. When operating electrical equipment, parts of this equipment automatically carry dangerous voltages. Improper handling can therefore result in serious injuries or material damage.

  • Use only insulating tools.
  • Do not connect while circuit is live (hot).
  • Place the meter only in dry surroundings.
  • Do not mount the meter in an explosive area or expose the meter to dust, mildew and insects.
  • Make sure the wires are suitable for the maximum current of this meter.
  • Make sure the AC wires are connected correctly before activating the current/voltage to the meter.
  • Do not touch the meter connecting clamps directly with metal, blank wire and your bare hands as you may get electrical shock.
  • Make sure the protection cover is placed after installation.
  • Installation, maintenance and reparation should only be done by qualified personnel.
  • Never break the seals and open the front cover as this might influence the function of the meter, and will cause no warranty.
  • Do not drop, or allow strong physical impact on the meter as the high precisely components inside may be damaged.
  • Designed to be mounted inside of switchboards or cabinet on DIN rail.
  • This device must have a suitable sized Circuit Breaker feeding the Multi Function Energy Meter so it does not exceed the maximum rated current.
  • The supply wiring of this device shall be suitable sized cable to match the installed circuit breaker.
  • A Disconnection Device (Circuit Breaker) should be installed close to the Multi Function Energy Meter.
  • The Disconnection Device shall be marked as the Disconnection Device for the Multi Function Energy Meter.

Documents / Resources

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Eastron SDM630 Series, SDM630-MB, SDM630-MB-2T Manual

Advertisement

Need help?

Need help?

Do you have a question about the SDM630 Series and is the answer not in the manual?

Questions and answers

Table of Contents