Eastron SDM630MCT-MV Manual
Also See for SDM630MCT-MV:

Advertisement

Eastron SDM630MCT-MV Manual

Introduction

The SDM630MCT-MV measures and displays the characteristics of single phase two wire (1p2w), three phase three wire (3p3w,) and three phase four wire (3p4w) supplies, including voltage, frequency, current, power, active and reactive energy, imported or exported. Energy is measured in terms of kWh, kVArh. Maximum demand current can be measured over preset periods of up to 60 minutes. In order to measure energy, the unit requires voltage and current inputs in addition to the supply required to power the product. The requisite current input(s) are obtained via current transformers(CT).
SDM630MCT-MV can be configured to work with a wide range of CTs with 0.333V output, giving the unit a wide range of operation. Built-in interfaces provides pulse and RS485 Modbus RTU outputs. Configuration is password protected.
This unit can be powered from a separate auxiliary (AC or DC)supply. Alternatively it can be powered from the monitored supply, where appropriate.

Unit Characteristics

The Unit can measure and display:

  • Line voltage and THD% (total harmonic distortion) of all phases
  • Line Frequency
  • Currents, Current demands and current THD% of all phases
  • Power, maximum power demand and power factor
  • Active energy imported and exported
  • Reactive energy imported and exported

The unit has password-protected set-up screens for:

  • Changing password
  • Supply system selection 1p2w, 3p3w, 3p4w
  • Demand Interval time
  • Reset for demand measurements
  • Pulse output duration

Two pulse output indicates real-time energy measurement. An RS485 output allows remote monitoring from another display or a computer.

Current Transformer Primary Current

The unit can be configured to operate with CT with 0.333V output. The secondary CT is fixed 0.333V, and the primary is optional.

RS485 Serial – Modbus RTU

This uses an RS485 serial port with Modbus RTU protocol to provide a means of remotely monitoring and controlling the Unit
Set-up screens are provided for setting up the RS485 port.

Pulse output

This provides two pulse outputs that clock up measured active and reactive energy. The constant for active energy is 3200imp/kWh (Terminals 11&12). The pulse width for pulse 1 (Terminals 9&10) can be set from the set-up menu.

Start Up Screens

1 The first screen lights up all display segments and can be used as a display check.
2 The second screen indicates the firmware installed in the unit and its build number.
3 The interface performs a self-test and indicates the result if the test passes.

* After a short delay, the screen will display active energy measurements.

Measurements

The buttons operate as follows:

1 Selects the Voltage and Current display screens
In Set-up Mode, this is the "Left" or "Back" button.
2 Select the Frequency and Power factor display screens
In Set-up Mode, this is the "Up" button
3 Select the Power display screens
In Set-up Mode, this is the "Down" button
4 Select the Energy display screens
In Set-up mode, this is the "Enter" or "Right" button

Voltage and Current

Each successive pressing of the button selects a new range:

1-1 Phase to neutral voltages (3p4w)
1-2 Phase to Phase voltages (3p3w)
2 Current on each phase
2-1 Neutral current
3 Phase to neutral voltage THD% (3p4w)
4 Current THD% for each phase

Frequency and Power factor and Demand

Each successive pressing of the button selects a new range:

1 Frequency and Power Factor (total)
2 Power Factor of each phase
3 Maximum Current Demand
4 Maximum Power Demand

Power

Each successive pressing of the button select a new range:

1 Instantaneous Active Power in kW
2 Instantaneous Reactive Power in kVAr
3 Instantaneous Volt-amps in KVA
4 Total W, VAr, VA

Energy Measurements

Each successive pressing of the button selects a new range:

1 Total active energy in kWh
2 Total reactive energy in kVArh
3 Imported active energy in kWh
4 Exported active energy in kWh
5 Imported reactive energy in kVArh
6 Exported reactive energy in kVArh

Setting Up

To enter set-up mode, pressing the button for 3 seconds, until the password screen appears.

Setting up is password-protected so you must enter the correct password (default '1000') before processing.
If an incorrect password is entered, the display will show:
PASS
Err

To exit setting-up mode, press repeatedly until the measurement screen is restored.

Set-up Entry Methods

Some menu items, such as password and CT, require a four-digit number entry while others, such as supply system, require selection from a number of menu options.

Menu Option Selection

  1. Use the and buttons to select the required item from the menu. Selection does not roll over between bottom and top of list
  2. Press to confirm your selection
  3. If an item flashes, then it can be adjusted by the and buttons. If not, there maybe a further layer.
  4. Having selected an option from the current layer, press to confirm your selection.
  5. Having completed a parameter setting, press to return to a higher menu level. You will be able to use the and buttons for further menu selection.
  6. On completion of all setting-up, press repeatedly until the measurement screen is restored.

Number Entry Procedure
When setting up the unit, some screens require the entering of a number. In particular, on entry to the setting up section, a password must be entered. Digits are set individually, from left to right. The procedure is as follows:

  1. The current digit to be set flashes and is set using the and buttons
  2. Press to confirm each digit setting.
  3. After setting the last digit, press to exit the number setting routine.

Communication

There is a RS485 port can be used for communication using Modbus RTU protocol. For Modbus RTU, parameters are selected from front panel.

RS485 Address
(The range is from 001 to 247)

1 From the Set-up menu, use and buttons to select the Address ID
2-1 Press button to enter the selection routine. The current setting will be flashing.
2-2 Use and buttons to choose Modbus Address (001 to 247)
On completion of the entry procedure, press button to confirm the setting and press button to return the main set-up menu.

Baud Rate

1 From the Set-up menu, use and buttons to select the Baud Rate option.
2-1 Press to enter the selection routine. The current setting will flash.
2-2 Use and buttons to choose Baud rate 2.4k. 4.8k, 9.6k, 19.2k, 38.4k
On completion of the entry procedure, press to confirm the setting and press to return to the main set up menu.

Parity

1 From the Set-up menu, use and buttons to select the Parity option.
2-1 Press to enter the selection routine. The current setting will flash.
2-2 Use and buttons to choose Parity (EVEN / ODD/ NONE) Default is NONE.
On completion of the entry procedure, press to confirm the setting and press to return to the main set up menu.

Stop bits

1 From the Set-up menu, use and buttons to select the Stop Bit option.
2-1 Press to enter the selection routine. The current setting will flash.
2-2 Use and buttons to choose Stop Bit (2 or 1)
On completion of the entry procedure, press to confirm the setting and press to return to the main set up menu.

Note: Default is 1, and only when the parity is NONE that the stop bit can be changed to 2.

CT

The CT option sets the primary current of the current transformer (CT) that wires to the meter. CT2 is fixed with 0.333V

1 From the Set-up menu, use and buttons to select the CT primary(CT1).
Its' default 5A,and ranged from 0005 to 9999.
2 Secondary CT(CT2)
It's fixed 0.333V, and can not be set.

PT

The PT option sets the secondary voltage (PT2 100 to 500V) of the Voltage transformer (PT) that wires to the meter.

1 From the Set-up menu, use and buttons to select the PT option. The screen will show the voltage PT secondary voltage value. The default value is 400V
2 Secondary PT setting
Press to enter the PT secondary voltage selection routine. The range is from 100 to 500V.
3 Set PT ratios value
Press to enter the PT ratio screen.
The range is from 0001 to 2000.
For example, if set the ratio to be 100, it means the primary voltage equals secondary voltage x 100

Pulse output

This option allows you to configure the pulse output. The output can be set to provide a pulse for a defined amount of energy active or reactive.
Use this section to set up the pulse output 1 — Units: Total kWh (default), Total kVArh

1 From the Set-up menu, use and buttons to select the Pulse output option.
2 Press to enter the selection routine. The unit symbol will flash.
3 Use and buttons to choose kWh or kVArh.
On completion of the entry procedure, press to confirm the setting and press to return to the main set up menu.

Pulse rate
Use this to set the energy represented by each pulse. Rate can be set to 1 pulse per 0.01kWh/0.1kWh/1kWh/10kWh/100kWh/1000kWh.

(It shows 1 impulse = 10kWh/kVArh)

1 From the Set-up menu, use and buttons to select the Pulse Rate option.
2 Press to enter the selection routine. The current setting will flash.
0.01/0.1/1/10/100/1000kWh/kVArh per pulse
Use and buttons to choose pulse rate. On Completion of the entry procedure, press to confirm the setting and press to return to the main set up menu.

Pulse Duration
The energy monitored can be active or reactive and the pulse width can be 200, 100 or 60ms.

(It shows pulse width of 200ms)

1-1 From the Set-up menu, use and buttons to select the Pulse width option.
1-2 Press to enter the selection routine. The current setting will flash.
Use and buttons to choose pulse width.
On completion of the entry procedure, press to confirm the setting and press to return to the main set up menu.

DIT Demand Integration Time

This sets the period in minutes over which the current and power readings are integrated for maximum demand measurement. The options are: off (0), 5, 8, 10, 15,20, 30, 60 minutes

1 From the set-up menu, use and buttons to select the DIT option. The screen will show the currently selected integration time.
2-1 Press to enter the selection routine. The current time interval will flash
2-2 Use and buttons to select the time required.
2-3 Press to confirm the selection. SET indicator will appear.
Press to exit the DIT selection routine and return to the menu.

Backlit set-up

The meter provides a function to set the blue backlit lasting time.

1 The backlit lasting time is settable
Default lasting time is 60 minutes
For example, if it's set as 5, the backlit will be off in 5minutes from the last time operation on the meter.
Notes: If it's set as 0, the backlit will always be on.
2 Press to enter the selection routine. The current time interval will flash
The options can be: 0/5/10/30/60/120 minutes
Use and buttons to select the time required. Then press to confirm the set-up.

Supply System

Use this section to set the type of power supply being monitored.

1 From the Set-up menu, use and buttons to select the System option. The screen will show the currently selected power supply.
2 Press to enter the selection routine. The current selection will flash
3-1 Use and buttons to select the required system option: 1P2(W),3P3(W),3P4(W)
3-2 Press to confirm the selection. SET indicator will appear.
Press to exit the system selection routine and return to the menu. SET will disappear and you will be returned to the main Set-up Menu

Change password

1 Use the and to choose the change password option
2-1 Press the to enter the change password routine. The new password screen will appear with the first digit flashing
2-2 Use and to set the first digit and press to confirm your selection. The next digit will flash.
2-3 Repeat the procedure for the remaining three digits
2-4 After setting the last digit, SET will show.
Press to exit the number setting routine and return to the Set-up menu. SET will be removed

CLR

The meter provides a function to reset the maximum demand value of current and power.

1 From the Set-up menu, use and buttons to select the reset option.
2 Press to enter the selection routine. The MD will flash.
Press to confirm the setting and press to return to the main set up menu.

Reverse connected current inputs correction set-up

1 Use and buttons to select page "SET sys cont"
2-1 Press to enter Phase A, the default is Frd (forward)
2-2 Use and buttons to Phase B or C setting pages

How to operate if phase A is reversely connected

1 Go to phase A setting page
2 Press to enter the selection routine. The Frd will flash.
Use button to change Frd to Rev.
Press to confirm the setting and press to return to the main set up menu.

Specifications

Measured Parameters
The unit can monitor and display the following parameters of a single phase two wire (1p2w), three phase three wire (3p3w) or four phase four wire (3p4w) supply.

Voltage and Current
Phase to neutral voltages 100 to 289V a.c. (not for 3p3w supplies)
Voltages between phases 173 to 480V a.c. (3p supplies only)
Percentage total voltage harmonic distortion (THD%) for each phase to N ( not for 3p3w supplies)
Percentage voltage THD% between phases (three phase supplies only)
Current THD% for each phase

Power factor and Frequency and Max. Demand
Frequency in Hz
Instantaneous power:

  • Power 0 to 3600 MW
  • Reactive Power 0 to 3600 MVAr
  • Volt-amps 0 to 3600 MVA

Maximum demanded power since last Demand reset Power factor
Maximum neutral demand current, since the last Demand reset (for three phase supplies only)

Energy Measurements

  • Imported/Exported active energy
0 to 9999999.9 kWh
  • Imported/Exported reactive energy
0 to 9999999.9 kVArh
  • Total active energy
0 to 9999999.9 kWh
  • Total reactive energy
0 to 9999999.9 kVArh

Measured Inputs
Voltage inputs through 4-way fixed connector with 2.5mm² stranded wire capacity. single phase two wire (1p2w), three phase three wire(3p3w) or four phase four wire (3p4w) unbalanced. Line frequency measured from L1 voltage or L3 voltage.
Three current inputs (six physical terminals) with 2.5mm² stranded wire capacity for connection of external CTs. Nominal rated input current 333mV a.c. Rms.
Maximum torque is 0.4Nm.

Accuracy

Voltage 0·5% of range maximum
Current 0·5% of nominal
Frequency 0·2% of mid-frequency
Power factor 1% of unity (0.01)
Active power (W) ±1% of range maximum
Reactive power (VAr) ±1% of range maximum
Apparent power (VA) ±1% of range maximum
Active energy (Wh) Class 1 IEC 62053-21
Reactive energy (VARh) Class 2 IEC62053-23
Total harmonic distortion 1% up to 31st harmonic
Response time to step input 1s, typical, to >99% of final reading, at 50 Hz.

*Auxiliary Supply
Two-way fixed connector with 2·5mm2 stranded wire capacity.
85 to 275V a.c. 50/60Hz ±10% or 120V to 380V d.c. ±20%. Consumption < 10W.

Interfaces for External Monitoring
Three interfaces are provided: An RS485 communication channel that can be programmed for Modbus RTU protocol

  • pulse output indicating real-time measured energy.(configurable)
  • pulse output 3200imp/kWh (not configurable)
  • The Modbus configuration (Baud rate etc.) and the pulse output assignments (kWh/kVArh) are configured through the Set-up screens.

Pulse Output
The unit provides two pulse outputs. Both pulse outputs are passive type.
Pulse output 1 is configurable. The pulse output can be set to generate pulses to represent total kWh or kVArh.
The pulse constant can be set to generate 1 pulse per:
0.01 = 10 Wh/VArh
0.1 = 100 Wh/VArh
1 = 1 kWh/kVArh
10 = 10 kWh/kVArh
100 = 100 kWh/kVArh
1000=1000 kWh/kVArh
Pulse width: 200/100(default)/60ms
Pulse output 2 is non-configurable. It is fixed up with total kWh. The constant is 3200imp/kWh.

RS485 Output for Modbus RTU
For Modbus RTU, the following RS485 communication parameters can be configured from the Set-up menu:

  • Baud rate 2400, 4800, 9600, 19200, 38400
  • Parity none (default)/odd/even
  • Stop bits 1 or 2
  • RS485 network address nnn – 3-digit number, 001 to 247
  • Modbus™ Word order Hi/Lo byte order is set automatically to normal or reverse. It cannot be configured from the set-up menu.

Reference Conditions of Influence Quantities

Influence Quantities are variables that affect measurement errors to a minor degree. Accuracy is verified under nominal value (within the specified tolerance) of these conditions.

Ambient temperature 23°C ±1°C
Input frequency 50 or 60Hz ±2%
Input waveform Sinusoidal (distortion factor < 0·005)
Auxiliary supply voltage Nominal ±1%
Auxiliary supply frequency Nominal ±1%
Auxiliary supply waveform (if AC) Sinusoidal (distortion factor < 0·05)
Magnetic field of external origin Terrestrial flux

Dimensions

Dimensions

Wiring Diagram

Three phase four wire
Wiring Diagram - Part 1 - Three phase four wire

Three phase three wire
Wiring Diagram - Part 2 - Three phase three wire

Single phase two wire
Wiring Diagram - Part 3 - Single phase two wire

If you have any question, please feel free to contact our sales team.
Zhejiang Eastron Electronic Co., Ltd.
No.52 Dongjin Rd. Nanhu, Jiaxing, Zhejiang, 314001, China
Tel: +86-573-83698881
Email: sales@eastrongroup.com
www.eastrongroup.com

Documents / Resources

References

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Eastron SDM630MCT-MV Manual

Advertisement

Need help?

Need help?

Do you have a question about the SDM630MCT-MV and is the answer not in the manual?

Questions and answers

Table of Contents