Advertisement
The SDM630MCT-MV measures and displays the characteristics of single phase two wire (1p2w), three phase three wire (3p3w,) and three phase four wire (3p4w) supplies, including voltage, frequency, current, power, active and reactive energy, imported or exported. Energy is measured in terms of kWh, kVArh. Maximum demand current can be measured over preset periods of up to 60 minutes. In order to measure energy, the unit requires voltage and current inputs in addition to the supply required to power the product. The requisite current input(s) are obtained via current transformers(CT).
SDM630MCT-MV can be configured to work with a wide range of CTs with 0.333V output, giving the unit a wide range of operation. Built-in interfaces provides pulse and RS485 Modbus RTU outputs. Configuration is password protected.
This unit can be powered from a separate auxiliary (AC or DC)supply. Alternatively it can be powered from the monitored supply, where appropriate.
The Unit can measure and display:
The unit has password-protected set-up screens for:
Two pulse output indicates real-time energy measurement. An RS485 output allows remote monitoring from another display or a computer.
The unit can be configured to operate with CT with 0.333V output. The secondary CT is fixed 0.333V, and the primary is optional.
This uses an RS485 serial port with Modbus RTU protocol to provide a means of remotely monitoring and controlling the Unit
Set-up screens are provided for setting up the RS485 port.
This provides two pulse outputs that clock up measured active and reactive energy. The constant for active energy is 3200imp/kWh (Terminals 11&12). The pulse width for pulse 1 (Terminals 9&10) can be set from the set-up menu.
1 | ![]() | The first screen lights up all display segments and can be used as a display check. |
2 | ![]() | The second screen indicates the firmware installed in the unit and its build number. |
3 | ![]() | The interface performs a self-test and indicates the result if the test passes. |
* After a short delay, the screen will display active energy measurements.
The buttons operate as follows:
1 | ![]() | Selects the Voltage and Current display screens In Set-up Mode, this is the "Left" or "Back" button. |
2 | ![]() | Select the Frequency and Power factor display screens In Set-up Mode, this is the "Up" button |
3 | ![]() | Select the Power display screens In Set-up Mode, this is the "Down" button |
4 | ![]() | Select the Energy display screens In Set-up mode, this is the "Enter" or "Right" button |
Each successive pressing of the button selects a new range:
1-1 | ![]() | Phase to neutral voltages (3p4w) |
1-2 | ![]() | Phase to Phase voltages (3p3w) |
2 | ![]() | Current on each phase |
2-1 | ![]() | Neutral current |
3 | ![]() | Phase to neutral voltage THD% (3p4w) |
4 | ![]() | Current THD% for each phase |
Each successive pressing of the button selects a new range:
1 | ![]() | Frequency and Power Factor (total) |
2 | ![]() | Power Factor of each phase |
3 | ![]() | Maximum Current Demand |
4 | ![]() | Maximum Power Demand |
Each successive pressing of the button select a new range:
1 | ![]() | Instantaneous Active Power in kW |
2 | ![]() | Instantaneous Reactive Power in kVAr |
3 | ![]() | Instantaneous Volt-amps in KVA |
4 | ![]() | Total W, VAr, VA |
Each successive pressing of the button selects a new range:
1 | ![]() | Total active energy in kWh |
2 | ![]() | Total reactive energy in kVArh |
3 | ![]() | Imported active energy in kWh |
4 | ![]() | Exported active energy in kWh |
5 | ![]() | Imported reactive energy in kVArh |
6 | ![]() | Exported reactive energy in kVArh |
To enter set-up mode, pressing the button for 3 seconds, until the password screen appears.
Setting up is password-protected so you must enter the correct password (default '1000') before processing.
If an incorrect password is entered, the display will show:
PASS
Err
To exit setting-up mode, press repeatedly until the measurement screen is restored.
Some menu items, such as password and CT, require a four-digit number entry while others, such as supply system, require selection from a number of menu options.
Menu Option Selection
Number Entry Procedure
When setting up the unit, some screens require the entering of a number. In particular, on entry to the setting up section, a password must be entered. Digits are set individually, from left to right. The procedure is as follows:
There is a RS485 port can be used for communication using Modbus RTU protocol. For Modbus RTU, parameters are selected from front panel.
RS485 Address
(The range is from 001 to 247)
1 | ![]() | From the Set-up menu, use ![]() ![]() |
2-1 | ![]() | Press ![]() |
2-2 | ![]() | Use ![]() ![]() |
On completion of the entry procedure, press ![]() ![]() |
Baud Rate
1 | ![]() | From the Set-up menu, use ![]() ![]() |
2-1 | ![]() | Press ![]() |
2-2 | ![]() | Use ![]() ![]() |
On completion of the entry procedure, press ![]() ![]() |
Parity
1 | ![]() | From the Set-up menu, use ![]() ![]() |
2-1 | ![]() | Press ![]() |
2-2 | ![]() | Use ![]() ![]() |
On completion of the entry procedure, press ![]() ![]() |
Stop bits
1 | ![]() | From the Set-up menu, use ![]() ![]() |
2-1 | ![]() | Press ![]() |
2-2 | ![]() | Use ![]() ![]() |
On completion of the entry procedure, press ![]() ![]() |
Note: Default is 1, and only when the parity is NONE that the stop bit can be changed to 2.
The CT option sets the primary current of the current transformer (CT) that wires to the meter. CT2 is fixed with 0.333V
1 | ![]() | From the Set-up menu, use ![]() ![]() Its' default 5A,and ranged from 0005 to 9999. |
2 | ![]() | Secondary CT(CT2) It's fixed 0.333V, and can not be set. |
The PT option sets the secondary voltage (PT2 100 to 500V) of the Voltage transformer (PT) that wires to the meter.
1 | ![]() | From the Set-up menu, use ![]() ![]() |
2 | ![]() | Secondary PT setting Press ![]() |
3 | ![]() | Set PT ratios value Press ![]() The range is from 0001 to 2000. |
For example, if set the ratio to be 100, it means the primary voltage equals secondary voltage x 100 |
This option allows you to configure the pulse output. The output can be set to provide a pulse for a defined amount of energy active or reactive.
Use this section to set up the pulse output 1 — Units: Total kWh (default), Total kVArh
1 | ![]() | From the Set-up menu, use ![]() ![]() |
2 | ![]() | Press ![]() |
3 | ![]() | Use ![]() ![]() |
On completion of the entry procedure, press ![]() ![]() |
Pulse rate
Use this to set the energy represented by each pulse. Rate can be set to 1 pulse per 0.01kWh/0.1kWh/1kWh/10kWh/100kWh/1000kWh.
(It shows 1 impulse = 10kWh/kVArh)
1 | ![]() | From the Set-up menu, use ![]() ![]() |
2 | ![]() | Press ![]() 0.01/0.1/1/10/100/1000kWh/kVArh per pulse |
Use ![]() ![]() ![]() ![]() |
Pulse Duration
The energy monitored can be active or reactive and the pulse width can be 200, 100 or 60ms.
(It shows pulse width of 200ms)
1-1 | ![]() | From the Set-up menu, use ![]() ![]() |
1-2 | ![]() | Press ![]() Use ![]() ![]() |
On completion of the entry procedure, press ![]() ![]() |
This sets the period in minutes over which the current and power readings are integrated for maximum demand measurement. The options are: off (0), 5, 8, 10, 15,20, 30, 60 minutes
1 | ![]() | From the set-up menu, use ![]() ![]() |
2-1 | ![]() | Press ![]() |
2-2 | ![]() | Use ![]() ![]() |
2-3 | ![]() | Press ![]() |
Press ![]() |
The meter provides a function to set the blue backlit lasting time.
1 | ![]() | The backlit lasting time is settable Default lasting time is 60 minutes For example, if it's set as 5, the backlit will be off in 5minutes from the last time operation on the meter. Notes: If it's set as 0, the backlit will always be on. |
2 | ![]() | Press ![]() The options can be: 0/5/10/30/60/120 minutes |
Use ![]() ![]() ![]() |
Use this section to set the type of power supply being monitored.
1 | ![]() | From the Set-up menu, use ![]() ![]() |
2 | ![]() | Press ![]() |
3-1 | ![]() | Use ![]() ![]() |
3-2 | ![]() | Press ![]() |
Press ![]() |
1 | ![]() | Use the ![]() ![]() |
2-1 | ![]() | Press the ![]() |
2-2 | ![]() | Use ![]() ![]() ![]() |
2-3 | ![]() | Repeat the procedure for the remaining three digits |
2-4 | ![]() | After setting the last digit, SET will show. |
Press ![]() |
The meter provides a function to reset the maximum demand value of current and power.
1 | ![]() | From the Set-up menu, use ![]() ![]() |
2 | ![]() | Press ![]() |
Press ![]() ![]() |
1 | ![]() | Use ![]() ![]() |
2-1 | ![]() | Press to ![]() |
2-2 | ![]() | Use ![]() ![]() |
How to operate if phase A is reversely connected
1 | ![]() | Go to phase A setting page |
2 | ![]() | Press ![]() Use ![]() |
Press ![]() ![]() |
Measured Parameters
The unit can monitor and display the following parameters of a single phase two wire (1p2w), three phase three wire (3p3w) or four phase four wire (3p4w) supply.
Voltage and Current
Phase to neutral voltages 100 to 289V a.c. (not for 3p3w supplies)
Voltages between phases 173 to 480V a.c. (3p supplies only)
Percentage total voltage harmonic distortion (THD%) for each phase to N ( not for 3p3w supplies)
Percentage voltage THD% between phases (three phase supplies only)
Current THD% for each phase
Power factor and Frequency and Max. Demand
Frequency in Hz
Instantaneous power:
Maximum demanded power since last Demand reset Power factor
Maximum neutral demand current, since the last Demand reset (for three phase supplies only)
Energy Measurements
| 0 to 9999999.9 kWh |
| 0 to 9999999.9 kVArh |
| 0 to 9999999.9 kWh |
| 0 to 9999999.9 kVArh |
Measured Inputs
Voltage inputs through 4-way fixed connector with 2.5mm² stranded wire capacity. single phase two wire (1p2w), three phase three wire(3p3w) or four phase four wire (3p4w) unbalanced. Line frequency measured from L1 voltage or L3 voltage.
Three current inputs (six physical terminals) with 2.5mm² stranded wire capacity for connection of external CTs. Nominal rated input current 333mV a.c. Rms.
Maximum torque is 0.4Nm.
Accuracy
Voltage | 0·5% of range maximum |
Current | 0·5% of nominal |
Frequency | 0·2% of mid-frequency |
Power factor | 1% of unity (0.01) |
Active power (W) | ±1% of range maximum |
Reactive power (VAr) | ±1% of range maximum |
Apparent power (VA) | ±1% of range maximum |
Active energy (Wh) | Class 1 IEC 62053-21 |
Reactive energy (VARh) | Class 2 IEC62053-23 |
Total harmonic distortion | 1% up to 31st harmonic |
Response time to step input | 1s, typical, to >99% of final reading, at 50 Hz. |
*Auxiliary Supply
Two-way fixed connector with 2·5mm2 stranded wire capacity.
85 to 275V a.c. 50/60Hz ±10% or 120V to 380V d.c. ±20%. Consumption < 10W.
Interfaces for External Monitoring
Three interfaces are provided: An RS485 communication channel that can be programmed for Modbus RTU protocol
Pulse Output
The unit provides two pulse outputs. Both pulse outputs are passive type.
Pulse output 1 is configurable. The pulse output can be set to generate pulses to represent total kWh or kVArh.
The pulse constant can be set to generate 1 pulse per:
0.01 = 10 Wh/VArh
0.1 = 100 Wh/VArh
1 = 1 kWh/kVArh
10 = 10 kWh/kVArh
100 = 100 kWh/kVArh
1000=1000 kWh/kVArh
Pulse width: 200/100(default)/60ms
Pulse output 2 is non-configurable. It is fixed up with total kWh. The constant is 3200imp/kWh.
RS485 Output for Modbus RTU
For Modbus RTU, the following RS485 communication parameters can be configured from the Set-up menu:
Reference Conditions of Influence Quantities
Influence Quantities are variables that affect measurement errors to a minor degree. Accuracy is verified under nominal value (within the specified tolerance) of these conditions.
Ambient temperature | 23°C ±1°C |
Input frequency | 50 or 60Hz ±2% |
Input waveform | Sinusoidal (distortion factor < 0·005) |
Auxiliary supply voltage | Nominal ±1% |
Auxiliary supply frequency | Nominal ±1% |
Auxiliary supply waveform (if AC) | Sinusoidal (distortion factor < 0·05) |
Magnetic field of external origin | Terrestrial flux |
Three phase four wire
Three phase three wire
Single phase two wire
If you have any question, please feel free to contact our sales team.
Zhejiang Eastron Electronic Co., Ltd.
No.52 Dongjin Rd. Nanhu, Jiaxing, Zhejiang, 314001, China
Tel: +86-573-83698881
Email: sales@eastrongroup.com
www.eastrongroup.com
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Advertisement
Need help?
Do you have a question about the SDM630MCT-MV and is the answer not in the manual?
Questions and answers