Advertisement
This document provides operating, maintenance and installation instructions. This unit measures and displays the characteristics of Single Phase Two Wire (1P2W), Three Phase Three Wire (3P3W) and Three Phase Four Wire (3P4W) networks. The measuring parameters include Voltage (V), Current (A), Frequency (Hz), Power (kW/KVA/KVAr), Power Factor (PF), Imported, Exported and Total Energy (kWh/kVArh). The unit also measures Maximum Demand Current and Power, this is measured over preset periods of up to 60 minutes.
This particular model accommodates 1A or 5A Current Transformers and can be configured to work with a wide range of CTs. It also comes with a complete comms capability with built in Pulse and RS485 Modbus RTU outputs, configuration is password protected.
This unit can be powered from a separate auxiliary supply (AC or DC). Alternatively, it can be powered from the monitored supply by linking the voltage reference and neutral reference in to terminals 5 & 6 (Please refer to wiring diagram).
The SMARTRAIL X835 can measure and display:
The unit has a Password-Protected set up menu for:
This unit requires configuring to operate with the appropriate curren transformer(s), the optional secondary currents are 1A or 5A. It is programmed by inputting the ratio (CT Primary divided by the CT Secondary). It can be used on primary currents up to 6000A.
On the MID Version, you can only program the CT Rate ONCE.
This unit is compatible with remote monitoring through RS485 Modbus RTU. Set-up screens are provided for configuring the RS485 port.
The SMARTRAIL X835 has Two Pulsed Outputs that can be set for active (kWh) or reactive (kVArh) energy. Terminals 9 & 10 (Pulse 1) are configurable within the setup menu.
Terminals 11 & 10 (Pulse 2) have a fixed output of 3200imp/kWh.
The first screen lights up all display segments and can be used as a display check.
The second screen indicates the firmware installed in the unit and its build number.
The interface performs a self-test and indicates the result if the test passes.
*After a short delay, the screen will display active energy measurements.
The buttons operate as follows:
![]() | Selects the Voltage and Current display screens. In Set-up Mode, this is the "Left" (press) or "Escape" (hold 3sec) button. |
![]() | Select the Frequency and Power factor display screens. In Set-up Mode, this is the "Up" (press) button. |
![]() | Select the Power display screens. In Set-up Mode, this is the "Down" (press) button. |
![]() | Select the Energy display screens. In Set-up mode, this is the "Right" (press) or "Enter" (hold 3sec) button. |
Each successive press of the button selects a new parameter:
![]() | Phase to neutral voltages. |
![]() | Current on each phase. |
![]() | Phase to neutral voltage THD%. |
![]() | Current THD% for each phase. |
Each successive press of the button selects a new range:
![]() | Frequency and Power Factor (total). |
![]() | Power Factor of each phase. |
![]() | Maximum Power Demand. |
![]() | Maximum Current Demand. |
Each successive press of the button select a new range:
![]() | Instantaneous Active Power in kW. |
![]() | Instantaneous Reactive Power in kVAr. |
![]() | Instantaneous Volt-Amps in KVA. |
![]() | Total kW, kVArh, kVA. |
Each successive press of the button selects a new range:
![]() | Imported active energy in kWh. |
![]() | Exported active energy in kWh. |
![]() | Imported reactive energy in kVArh. |
![]() | Exported reactive energy in kVArh. |
![]() | Total active energy in kWh. |
![]() | Total reactive energy in kVArh. |
Please note the register is 9999999.9 display over two lines.
To enter set up mode, hold the button for 3 seconds, until the password screen appears.
![]() | The set up is passwordprotected so you must enter the correct password (default '1000') before processing. |
![]() | If an incorrect password is entered, the display will show: PASS Err (Error) |
To exit the set up menu, hold the for 3 seconds, the measurement screen will display.
Some menu items, such as Password and CT, require a fourdigit number entry while others, such as supply system, require selection from a number of menu options.
When setting up the unit, some screens require the entering of a number. In particular, on entry to the setting up section, a password must be entered. Digits are set individually, from left to right. The procedure is as follows:
![]() | Use the ![]() ![]() |
![]() | Hold the ![]() |
![]() | Use ![]() ![]() |
![]() | Repeat the procedure for the remaining three digits. |
![]() | After setting the last digit, Hold the ![]() |
Hold the button for 3 seconds to exit the set up menu.
This sets the period (in minutes) in which the Current and Power readings are integrated for maximum demand measurement. The options are off; 5; 10; 15; 30 or 60 minutes.
![]() | Use the ![]() ![]() |
![]() | Hold the ![]() |
![]() | Use the ![]() ![]() |
![]() | Hold the ![]() |
Hold the button for 3 seconds to exit the set up menu.
The unit has a default setting of 3 Phase 4 Wire (3P4W).
Use this section to set the type of electrical system.
![]() | Use the ![]() ![]() |
![]() | Hold the ![]() |
![]() | Use the ![]() ![]() |
Hold the button to confirm your adjustment. Hold the
button for 3 seconds to exit the set up menu.
The CT options set the Secondary Current (CT2 5A or 1A) of the Current Transformer (CT) that are used with the meter.
![]() | Use the ![]() ![]() |
![]() | Secondary CT Setting: Hold the ![]() |
![]() | Set the CT Ratio Value: Hold the ![]() |
The CT Rate is the CT Primary divided by the CT Secondary. For Example: 200/5A Current Transformers - 200÷5=40, so the CT Rate would be 0040 and the CT2 would be 5.
On the MID Version, you can only program the CT Rate ONCE.
If the CT connections are incorrectly wired, they can be reversed through the "Set System Continued" menu:
![]() | Use the ![]() ![]() ![]() |
![]() | This screen will display, you can change "Forward" to "Reverse" on each individual CT connection. |
![]() | Hold the ![]() ![]() ![]() |
Hold the button for 3 seconds to exit the set up menu.
The PT option sets the Secondary Voltage (PT2 100-500V) of the Voltage Transformer (PT) that may be connected to the meter.
![]() | Use the ![]() ![]() |
![]() | Secondary PT Setting: Hold the ![]() |
![]() | Set the PT Ratio Value: Hold the ![]() |
The PT Rate is the PT Primary divided by the PT Secondary. For Example: Voltage Transformer - 11000÷110=100, so the PT Rate would be 0100 and the PT2 would be 110.
Use this section to configure the Pulsed Output Type. Units: kVArh (default); kWh.
![]() | Use the ![]() ![]() |
![]() | Hold the ![]() |
![]() | Use the ![]() ![]() ![]() |
Hold the button for 3 seconds to exit the set up menu.
You can configure the number of pulses to relate to a defined amount of Total Energy.
Please note there are limitations that need to be factored in when setting the pulsed output. This is based upon the relay output only being able to pulse 2 times per second.
For example, If the CT is set to 500/5A on a Single Phase network this would generate (500Ax230V=115,000 / 1000) 115kWh which is 31W per second. A setting of 10IMP/kWh (10 pulses per kWH) would generate 3 pulses per second. This will exceed the 2 pulse per second limitation.
Pulse settings: 1 Pulse per: 10W (0.01) / 100W (0.1) / 1000W/1kWh (1) / 10kWh (10) / 100kWh (100) /1000kWh
![]() | Use the ![]() ![]() |
![]() | Hold the ![]() |
Use the and
buttons to choose the desired pulse rate. To save the new setting, hold the
button for 3 seconds until the selection stops flashing.
The energy monitored can be active or reactive and the pulse width can be selected as 200, 100 or 60mS.
![]() | Use the ![]() ![]() |
![]() | Hold the ![]() |
Use the and
buttons to choose the desired pulse rate. To save the new setting, hold the
button for 3 seconds until the selection stops flashing.
The RS485 port can be used for communication using Modbus RTU Protocol. To configure the Modbus settings, such as Address and Baud Rate, this is also done within the Password-protected set up menu.
![]() | Use the![]() ![]() |
![]() | Hold the ![]() |
![]() | Hold the ![]() |
Use the and
buttons to choose the necessary number, then press the
button to move along to the next number. To save the new setting, hold the
button for 3 seconds until the selection stops flashing.
![]() | Use the ![]() ![]() |
![]() | Hold the ![]() |
![]() | Use the ![]() ![]() |
On completion of the entry procedure, hold the button to confirm the setting.
![]() | Use the ![]() ![]() |
![]() | Hold the ![]() |
![]() | Use the![]() ![]() |
On completion of the entry procedure, hold the button for 3 seconds until the selection stops flashing.
![]() | Use the ![]() ![]() |
![]() | Hold the ![]() |
![]() | Use the ![]() ![]() Range: 1 (default) or 2. |
On completion of the entry procedure, hold the button for 3 seconds until the selection stops flashing.
The meter provides a function to reset the maximum demand value of current and power.
![]() | Use the ![]() ![]() |
![]() | Hold the ![]() |
Hold the button to confirm the setting and press
to return to the main set up menu.
The unit can monitor and display the following parameters of a Single Phase Two Wire (1P2W), Three Phase Three Wire (3P3W) or Three Phase Four Wire (3P4W) system.
| 0 to 9999999.9 kWh |
| 0 to 9999999.9 kVArh |
| 0 to 9999999.9 kWh |
| 0 to 9999999.9 kVArh |
Voltage inputs through 4-way fixed connector with 2.5mm² stranded wire capacity. Single Phase Two Wire (1P2W), Three Phase Three Wire (3P3W) or Three Phase Four Wire (3P4W) unbalanced. Line frequency measured from L1 Voltage or L3 Voltage. Three current inputs (six physical terminals) with 2.5mm² stranded wire capacity for connection of external CTs.
Nominal rated input current 5A or 1A AC RMS.
| 0·5% of range maximum |
| 0·5% of nominal |
| 0·2% of mid-frequency |
| 1% of unity (0.01) |
| ±1% of range maximum |
| ±1% of range maximum |
| ±1% of range maximum |
| Class 1 IEC 62053-21 |
| ±1% of range maximum |
| 1% up to 31st harmonic |
| 1s, typical, to >99% of final reading, at 50 Hz. |
Two-way fixed connector with 2.5mm² stranded wire capacity. 85-275V AC 50/60Hz ±10% or 120-380V DC ±20%.
Consumption <2W 10VA.
Three interfaces are provided:
The Modbus configuration (baud rate etc.) and the pulse relay output assignments (kW/kVArh) are configured through the set-up screens.
Opto-coupler with potential free SPST-NO Contact (Contact rating 5-27V DC / Max current input: Imin 2mA and Imax 27mA DC). The pulse output can be set to generate pulses to represent kWh or kVArh.
Rate can be set to generate 1 pulse per:
0.01 = 10 Wh/VArh
0.1 = 100 Wh/VArh
1 = 1 kWh/kVArh
10 = 10 kWh/kVArh
100 = 100 kWh/kVArh
Pulse width 200/100/60 mS.
For Modbus RTU, the following RS485 communication parameters can be configured from the set-up menu:
Baud rate: 2400, 4800, 9600, 19200, 38400
Parity: none (default) / odd / even
Stop bits: 1 or 2
RS485 Network Address: 3 digit number - 001-247
Modbus™ Word order Hi/Lo byte order is set automatically to normal or reverse. It cannot be configured from the set-up menu.
Influence Quantities are variables that affect measurement errors to a minor degree. Accuracy is verified under nominal value (within the specified tolerance) of these conditions.
| 23°C ±1°C |
| 50 or 60Hz ±2% |
| Sinusoidal (distortion factor < 0·005) |
| Nominal ±1% |
| Nominal ±1% |
| Sinusoidal (distortion factor < 0·05) |
| Terrestrial flux |
| -25°C to +55°C* |
| -40°C to +70°C* |
| 0 to 95%, non-condensing |
| Up to 3000m |
| 1 minute |
| 10Hz to 50Hz, IEC 60068-2-6, 2g |
| 30g in 3 planes |
*Maximum operating and storage temperatures are in the context of typical daily and seasonal variation.
| 72 x 94.5 mm (WxH) per DIN 43880 |
| DIN rail (DIN 43880) |
| IP51 indoor |
| Self-extinguishing UL 94 V-0 |
We, Eastron (Metering) Europe Limited, declare under our sole responsibility as the manufacturer that the poly phase multifunction electrical energy meter "SDM630MCT-MOD-MID" correspond to the production model described in the EC-type examination certificate and to the requirements of the Directive 2004/22/EC EC type examination certificate number 0120/SGS0142.
Identifcation number of the NB 0120.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download Eastron SDM630MCT-MOD-MID - DIN Rail Smart Energy Meter Manual
Advertisement
Need help?
Do you have a question about the SDM630MCT-MOD-MID and is the answer not in the manual?
Questions and answers