Eastron SDM630-Modbus V2 User Manual

Eastron SDM630-Modbus V2 User Manual

Din rail smart meter for single and three phase electrical systems
Hide thumbs Also See for SDM630-Modbus V2:

Advertisement

Quick Links

EASTRON SDM630-Modbus V2 USER MANUAL V1.5
SDM630-Modbus V2
DIN Rail Smart Meter for Single and Three Phase Electrical Systems
 Measures kWh Kvarh, KW, Kvar, KVA, P,
F, PF, Hz, dmd, V, A, etc.
 Bi-directional measurement IMP & EXP
 Two pulse outputs
 RS485 Modbus
 Din rail mounting 35mm
 100A direct connection
Better than Class 1 / B accuracy
USER MANUAL
2020 V1.5
2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn

Advertisement

loading

Summary of Contents for Eastron SDM630-Modbus V2

  • Page 1  Bi-directional measurement IMP & EXP  Two pulse outputs  RS485 Modbus  Din rail mounting 35mm  100A direct connection Better than Class 1 / B accuracy  USER MANUAL 2020 V1.5 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 2 60 minutes. In order to measure energy, the unit requires voltage and current inputs in addition to the supply required to power the product. SDM630-Modbus V2 supports max. 100A direct connection, saves the cost and avoid the trouble to connect external CTs, giving the unit a cost-effective and easy operation. Built-in interfaces provides pulse and RS485 Modbus RTU outputs.
  • Page 3 In Set-up Mode, this is the “Up” button Select the Power display screens In Set-up Mode, this is the “Down” button Select the Energy display screens In Set-up mode, this is the “Enter” or “Right” button 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 4 Each successive pressing of the button selects a new range: Phase to neutral voltages(3p4w) Phase to neutral voltages(3p3w) Current on each phase Phase to neutral voltage THD%(3p4w) Phase to neutral voltage THD%(3p3w) 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 5 Frequency and Power Factor and Demand Each successive pressing of the button selects a new range: Frequency and Power Factor (total) Power Factor of each phase Maximum Power Demand Maximum Current Demand 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 6 Instantaneous Active Power in kW Instantaneous Reactive Power in kVAr Instantaneous Volt-amps in KVA Total kW, kVArh, kVA Energy Measurements Each successive pressing of the button selects a new range: Imported active energy in kWh 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 7 Imported reactive energy in kVArh Exported reactive energy in kVArh Total active energy in kWh Total reactive energy in kVArh Set-up To enter set-up mode, pressing the button for 3 seconds, until the password screen appears. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 8 The SET indicator will be removed and you will be able to use the buttons for further menu selection. 6) On completion of all set-up, press repeatedly until the measurement screen is restored. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 9 The new password screen will appear with the first digit flashing. to set the first digit and press to confirm your selection. The next digit will flash. Repeat the procedure for the remaining three digits 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 10 The current time interval will flash. buttons to select the time required. Press to confirm the selection. SET indicator will appear. Press to exit the DIT selection routine and return to the menu. Backlit Set-up 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 11 System option. The screen will show the currently selected system type. Press to enter the selection routine. The current selection will flash buttons to select the required system option: 1P2(W),3P3(W) ,3P4(W) 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 12 The unit symbol will flash. buttons to choose the selection . Press to confirm the setting and press to return to the main set up menu.
 Pulse Rate 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 13 Pulse Duration The energy monitored can be active or reactive and the pulse width can be selected as 200, 100(default) or 60ms. (It shows pulse width of 200ms) 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 14 There is a RS485 port can be used for communication using Modbus RTU protocol. For Modbus RTU, parameters are selected from Front panel. RS485 Address (The range is from 001 to 247) From the Set-up menu, use buttons to select the Address ID. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 15 The current setting will flash. buttons to choose Baud rate 2.4k. 4.8k, 9.6k, 19.2k, 38.4k On completion of the entry procedure, press to confirm the setting and press 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 16 On Completion of the entry procedure, press to confirm the setting and press return to the main set-up menu. Stop Bits From the Set-up menu, use buttons to select the Stop Bit option. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 17 Specifications Measured Parameters The unit can monitor and display the following parameters of a single phase two wire(1p2w), three phase three wire(3p3w) or four phase four wire(3p4w) supply. 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 18  Reactive energy (VArh) Class 2 IEC 62053-23  Response time to step input 1s, typical, to >99% of final reading, at 50 Hz. Interfaces for External Monitoring Three interfaces are provided: 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 19 Sinusoidal (distortion factor < 0·005)  Magnetic field of external origin Terrestrial flux Environment  Operating temperature 3K6(-25°C to +55°C*),Default 3K7(-40°C to +70°C*)  Storage temperature -40°C to +70°C*  Relative humidity 0 to 90%, non-condensing 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 20  Vibration 10Hz to 50Hz, IEC 60068-2-6, 2g  Shock 30g in 3 planes * Maximum operating and storage temperatures are in the context of typical daily and seasonal variation. Dimensions Wiring Guide 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 21 EASTRON SDM630-Modbus V2 USER MANUAL V1.5 Wiring diagram  Three Phase Three Wires: 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 22 EASTRON SDM630-Modbus V2 USER MANUAL V1.5  Three Phase Four Wires: 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...
  • Page 23 IF you have any question, please feel free to contact our sales team. No.1369, Chengnan Rd. Jiaxing, Zhejiang, 314001, China Zhejiang Eastron Electronic Co., Ltd. Tel: +86-573-83698881 Fax: +86-573-83698883 Email: sales@eastrongroup.com www.eastrongroup.com 2020 EASTRON ELECTRONIC. ALL RIGHTS RESERVED. Web: www.eastron.com.cn...