10. INSPECTION
The inspection should be conducted once every 6 months to a year.
Any inspected items which do not satisfy the criteria shown below should be repaired
Inspection
item
Measure the voltage fluctuation at the power
Power supply
supply terminal block of the converter to
determine if it is within the prescribed range.
Check the ambient temperature.
Ambient
Conditions
There should be no accumulation of dust.
Verify that the sensor is securely mounted.
Verify that the sensor
to the machine shaft.
Mount
Check for severed cables.
Conditions
Verify that the sensor cable connector is
plugged in all the way.
Verify that the LAN cable connector is plugged
in all the way.
*1: For CYLNUC Cylinder and CYLNUC MarkⅡ Cylinder, contact your NSD representative.
Inspection Description
rod
is securely coupled
Criteria
Within 21.6V to 26.4VDC range
ABSOCODER sensor
VLS-12.8PRA28: -20 to +120°C
VLS-12.8MHP28: -20 to +120°C
IRS-51.2P: -20 to +120°C
Converter: 0 to +55°C
None
There should be no looseness.
There should be no looseness.
Cable should appear normal.
There should be no looseness.
There should be no looseness.
52
Remark
Tester
Thermometer
*1
Visual
Inspection