Page 1
XDM 161 X-DIAS Digital Mixed Module Instruction Manual Date of creation: 11.07.2024 Version date: 06.02.2025 Article number: 21-008-161-E...
Page 2
(print, photocopy, microfilm or in any other process) without express permission. We reserve the right to make changes in the content without notice. SIGMATEK GmbH & Co KG is not responsible for technical or printing errors in this handbook and assumes no responsibility for damages that occur through...
Page 3
X-DIAS Digital Mixed Module XDM 161 8 digital inputs 8 short-circuit proof digital outputs The X-DIAS Digital Mixed Module XDM 161 has eight digital inputs (+24 V/3.7 mA/5 ms) and 8 short-circuit proof digital outputs (+24 V/0.5 A). The supply voltage is monitored for under voltage. 06.02.2025...
Page 5
X-DIAS DIGITAL MIXED MODULE XDM 161 9.2 Coding Hole Positions on Wiring Board (TOP View) 10 Wiring 10.1 ESD Protection 10.2 Wiring Example 10.3 Note 10.3.1 Connecting Inductive Loads 11 Assembly/Installation 11.1 Mounting 12 Supported Cycle Times 12.1 Cycle Times below 1 ms (in µs) 12.2 Cycle Times equal to or higher than 1 ms (in ms)
Please see our website for our hotline number and business hours. 1.2 Important Reference Documentation X-DIAS Designguide This and additional documents can be downloaded from our website or obtained through support. 1.3 Contents of Delivery 1x XDM 161 Page 4 06.02.2025...
X-DIAS DIGITAL MIXED MODULE XDM 161 2 Basic Safety Directives 2.1 Symbols Used The following symbols are used in the operator documentation for warning and danger messages, as well as informational notes. DANGER Danger indicates that death or serious injury will occur, if the specified measures are not taken.
Page 8
XDM 161 X-DIAS DIGITAL MIXED MODULE CAUTION Caution indicates that moderate to slight injury can occur, if the specified measures are not taken. To avoid moderate to slight injuries, observe all guidelines. Attention indique une situation dangereuse qui, faute de prendre les mesures adéquates, peut entraîner des blessures assez graves ou...
Please thoroughly read the corresponding documents and this operating manual before handling a product. SIGMATEK GmbH & Co KG is not liable for damages caused through, non-compliance with these instructions or applicable regulations.
Regarding the requirements for Safety and health connected to the use of machines, the manufacturer must perform a risk assessment in accordance with machine directives 2006/42/EG before introducing a machine to the market. Operate the unit with devices and accessories approved by SIGMATEK only. Page 8 06.02.2025...
Page 11
X-DIAS DIGITAL MIXED MODULE XDM 161 CAUTION Handle the device with care and do not drop or let fall. Prevent foreign bodies and fluids from entering the device. The device must not be opened! Manipulez l’appareil avec précaution et ne le laissez pas tomber.
The product was constructed in compliance with the following European Union directives and tested for conformity. 3.1.1 EU Conformity Declaration EU Declaration of Conformity The product XDM 161 conforms to the following European directives: 2014/35/EU Low-voltage Directive 2014/30/EU Electromagnetic Compatibility (EMC Directive) 2011/65/EU “Restricted use of certain hazardous substances in electrical and electronic equipment”...
X-DIAS DIGITAL MIXED MODULE XDM 161 4 Type Plate HW: Hardware version SW: Software version FW: Firmware version LD: Logic Device version 06.02.2025 Page 11...
XDM 161 X-DIAS DIGITAL MIXED MODULE 5 Technical Data 5.1 Digital Input Specifications Number Input voltage typically +24 V maximum +30 V Signal level low: < +5 V high: > +15 V Input current 3,7 mA at +24 V Input delay typically 5 ms 5.2 Digital Output Specifications...
X-DIAS DIGITAL MIXED MODULE XDM 161 5.3 Electrical Requirements Voltage supply from S-DIAS bus +24 V DC ±20 % (SELV/PELV) UL: NEC Class 2 Protection class Current consumption on the typically 13 mA maximum 17 mA S-DIAS bus (+24 V supply) Supply for I/Os +24 V ±20 %...
XDM 161 X-DIAS DIGITAL MIXED MODULE 5.5 Environmental Conditions Storage temperature -40 ... +85 °C Environmental temperature -25 ... +60 °C Humidity 0-95 %, non condensing Installation altitude above sea 0-2000 m without derating level > 2000 m up to a maximum of 5000 m with derating of the maximum environmental temperature by 0.5 °C per 100 m...
XDM 161 X-DIAS DIGITAL MIXED MODULE 7 Connector Layout Signal Description +24 V bus +24 V bus S-DIAS bus The +24 V voltage supply is provided by the S-DIAS CPU or RxD- OUT RxD- IN the S-DIAS interface module. RxD+ OUT...
XDM 161 X-DIAS DIGITAL MIXED MODULE Module status green module active no supply available BLINKING (5 Hz) no communication User yellow adjustable by application (e.g. the module LED can be set to blinking through the visualization so that the module is easily found in...
9 Module Coding X-DIAS modules have module coding by means of coding pins on the module housing. In combination with coding holes on the wiring board, a mismating protection can be realized. 9.1 Module Coding XDM 161 Position 1 Position 2...
X-DIAS DIGITAL MIXED MODULE XDM 161 10 Wiring 10.1 ESD Protection CAUTION The operator must ensure that no ESD interference affects the product. L'opérateur doit s'assurer qu'aucune interférence due à des décharges électrostatiques n'affecte le produit. 06.02.2025 Page 21...
X-DIAS DIGITAL MIXED MODULE XDM 161 10.3 Note The functional grounding of the X-DIAS modules is carried out via their GND connection on the wiring board. The wiring board must be connected to the grounded switch cabinet mounting plate with low resistance via the mounting screws.
XDM 161 X-DIAS DIGITAL MIXED MODULE 11 Assembly/Installation 11.1 Mounting The S-DIAS modules are designed for installation into the control cabinet. To mount the modules, a DIN-rail is required. The DIN rail must establish a conductive connection with the back wall of the control cabinet. The individual S-DIAS modules are mounted on the DIN rail as a block and secured with latches.
Page 27
X-DIAS DIGITAL MIXED MODULE XDM 161 Recommended minimum distances between the S-DIAS modules and the surrounding components or control cabinet wall: a, b, c … distances in mm (inches) 06.02.2025 Page 25...
XDM 161 X-DIAS DIGITAL MIXED MODULE 12 Supported Cycle Times 12.1 Cycle Times below 1 ms (in µs) x = supported 12.2 Cycle Times equal to or higher than 1 ms (in ms) x = supported x = supported Page 26...
X-DIAS DIGITAL MIXED MODULE XDM 161 13 Transport/Storage INFORMATION This device contains sensitive electronics. During transport and storage, high mechanical stress must therefore be avoided. For storage and transport, the same values for humidity and vibration as for operation must be maintained! Temperature and humidity fluctuations may occur during transport.
XDM 161 X-DIAS DIGITAL MIXED MODULE 14 Storage INFORMATION When not in use, store the operating panel according to the storage conditions. See chapter 13 Transport/Storage. During storage, ensure that all protective covers (if available) are placed correctly, so that no contamination, foreign bodies or fluids enter the device.
X-DIAS DIGITAL MIXED MODULE XDM 161 15 Maintenance INFORMATION During maintenance as well as servicing, observe the safety instructions from chapter 2 Basic Safety Directives. Lors de l'entretien et de la maintenance, respectez les consignes de sécurité du chapitre 2 Basic Safety Directives.
Need help?
Do you have a question about the XDM 161 and is the answer not in the manual?
Questions and answers