SIGMATEK TO 161 Operating Manual

SIGMATEK TO 161 Operating Manual

S-dias digital output module

Advertisement

Quick Links

TO 161
S-DIAS Digital Output Module
Operating Manual
Date of creation: 30.07.2013
Version date: 26.07.2023
Article number: 20-007-161-E

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TO 161 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for SIGMATEK TO 161

  • Page 1 TO 161 S-DIAS Digital Output Module Operating Manual Date of creation: 30.07.2013 Version date: 26.07.2023 Article number: 20-007-161-E...
  • Page 2 (print, photocopy, microfilm or in any other process) without the express permission. We reserve the right to make changes in the content without notice. The SIGMATEK GmbH & Co KG is not responsible for technical or printing errors in the handbook and assumes no responsibility for damages that occur...
  • Page 3 TO 161 with 16 short-circuit proof digital outputs The S-DIAS TO 161 digital output module has 16 short-circuit proof digital outputs in two groups (+24 V/0.5 A, short-circuit proof). The supply voltage for each group is monitored for low voltage.
  • Page 4: Table Of Contents

    TO 161 S-DIAS DIGITAL OUTPUT MODULE Contents Introduction ................5 Target Group/Purpose of this Operating Manual ...... 5 Important Reference Documentation ......... 5 Contents of Delivery ..............5 Basic Safety Directives ............6 Symbols Used ................6 Disclaimer ..................8 General Safety Directives ............
  • Page 5 S-DIAS DIGITAL OUTPUT MODULE TO 161 Connector Layout ..............18 Status LEDs ................. 19 Applicable Connectors ............... 19 Label Field ................... 20 Wiring ..................21 General Information on the Digital Outputs ......21 Wiring Example ................22 Note ....................23 Assembly/Installation ............
  • Page 6 TO 161 S-DIAS DIGITAL OUTPUT MODULE 15.2 Cycle Times equal to or higher than 1 ms (in ms)....30 16 Hardware Class TO161 ............31 16.1 Interfaces ..................32 16.1.1 Clients ....................32 16.1.2 Servers ....................32 16.1.3 Communication Interfaces ..............32 16.2...
  • Page 7: Introduction

    General knowledge of automation technology is required. Further help and training information, as well as the appropriate accessories can be found on our website www.sigmatek-automation.com. Our support team is happily available to answer your questions. Please see our website for our hotline number and business hours.
  • Page 8: Basic Safety Directives

    TO 161 S-DIAS DIGITAL OUTPUT MODULE Basic Safety Directives Symbols Used The following symbols are used in the operator documentation for warning and danger messages, as well as informational notes: DANGER Danger indicates that death or serious injury will occur, if the specified measures are not taken.
  • Page 9 S-DIAS DIGITAL OUTPUT MODULE TO 161 INFORMATION Information  Provides important information on the product, handling or relevant sections of the documentation, which require attention. 26.07.2023 Page 7...
  • Page 10: Disclaimer

    It does not guarantee properties under the warranty. Please thoroughly read the corresponding documents and this operating manual before handling a product. SIGMATEK GmbH & Co KG is not liable for damages caused through, non-compliance with these instructions or applicable regulations.
  • Page 11: General Safety Directives

    S-DIAS DIGITAL OUTPUT MODULE TO 161 General Safety Directives The Safety Directives in the other sections of this operating manual must be observed. These instructions are visually emphasized by symbols. INFORMATION According to EU Directives, the operating manual is a component of a product.
  • Page 12: Software/Training

    TO 161 S-DIAS DIGITAL OUTPUT MODULE CAUTION Handle the device with care and do not drop or let fall. Prevent foreign bodies and fluids from entering the device. The device must not be opened! Manipulez l’appareil avec précaution et ne le laissez pas tomber.
  • Page 13: Standards And Directives

    The product was constructed in compliance with the following European Union directives and tested for conformity. 3.1.1 EU Conformity Declaration EU Declaration of Conformity The product TO 161 conforms to the following European directives: • 2014/35/EU Low-voltage Directive • 2014/30/EU Electromagnetic Compatibility (EMC Directive) •...
  • Page 14: Type Plate

    TO 161 S-DIAS DIGITAL OUTPUT MODULE Type Plate HW: Hardware version SW: Software version Page 12 26.07.2023...
  • Page 15: Technical Data

    S-DIAS DIGITAL OUTPUT MODULE TO 161 Technical Data Digital Output Specifications Number Short-circuit proof Maximum continuous current load 0.5 A allowed per channel Maximum total current 4 A (100% of on-time) (per 8-channel group) Maximum total current (entire 8 A (100 % of on time)
  • Page 16: Electrical Requirements

    TO 161 S-DIAS DIGITAL OUTPUT MODULE Electrical Requirements Supply voltage +24 V /1-2 18-30 V DC Current consumption of voltage corresponds to the load on the digital outputs supply +24 V /1-2 Voltage supply from S-DIAS bus +5 V Current consumption on the...
  • Page 17 S-DIAS DIGITAL OUTPUT MODULE TO 161 26.07.2023 Page 15...
  • Page 18: Voltage Monitor

    TO 161 S-DIAS DIGITAL OUTPUT MODULE Voltage Monitor Supply voltage +24 V /1-2 supply voltage > 18 V (corresponding DC OK-LED lights green) Miscellaneous Article number 20-007-161 20-007-161-X (polymer coated printed circuit board) Standard UL 508 (E247993) Approbations UL, cUL, CE, UKCA...
  • Page 19: Mechanical Dimensions

    S-DIAS DIGITAL OUTPUT MODULE TO 161 Mechanical Dimensions 26.07.2023 Page 17...
  • Page 20: Connector Layout

    TO 161 S-DIAS DIGITAL OUTPUT MODULE Connector Layout INFORMATION The GND supply (X5: Pin 3 and Pin 4) is internally bridged. Only one GND pin (pin 3 or pin 4) is required to power the module. The bridged connections may be used for further looping of the +24 V supply and the GND supply.
  • Page 21: Status Leds

    S-DIAS DIGITAL OUTPUT MODULE TO 161 Status LEDs Module Status green module active no supply available BLINKING (5 Hz) no communication User yellow can be set from the application (e.g. the module LED can be set to blinking through the...
  • Page 22: Label Field

    TO 161 S-DIAS DIGITAL OUTPUT MODULE Label Field Manufacturer Weidmüller Type MF 10/5 CABUR MC NE WS Weidmüller article number 1854510000 Compatible printer Weidmüller Type Printjet Advanced 230V Weidmüller article number 1324380000 Page 20 26.07.2023...
  • Page 23: Wiring

    S-DIAS DIGITAL OUTPUT MODULE TO 161 Wiring General Information on the Digital Outputs The cross sectional area of the +24 V supply must be designed for the maximum output current drawn by a group. The outputs can be turned off by disconnecting the +24 V supply voltage.
  • Page 24: Wiring Example

    TO 161 S-DIAS DIGITAL OUTPUT MODULE Wiring Example Page 22 26.07.2023...
  • Page 25: Note

    S-DIAS DIGITAL OUTPUT MODULE TO 161 Note The following guidelines should be observed: • Avoid parallel wiring between input lines and load-bearing circuits. • Protective circuits for all relays (RC networks or free-wheeling diodes) • Correct wiring to mass Connecting Inductive Loads:...
  • Page 26: Assembly/Installation

    TO 161 S-DIAS DIGITAL OUTPUT MODULE Assembly/Installation Check Contents of Delivery Ensure that the contents of the delivery are complete and intact. See chapter 1.3 Contents of Delivery. INFORMATION On receipt and before initial use, check the device for damage. If the device is damaged, contact our customer service and do not install the device in your system.
  • Page 27: Mounting

    S-DIAS DIGITAL OUTPUT MODULE TO 161 Mounting The S-DIAS modules are designed for installation into the control cabinet. To mount the modules a DIN-rail is required. The DIN rail must establish a conductive connection with the back wall of the control cabinet. The individual S-DIAS modules are mounted on the DIN rail as a block and secured with latches.
  • Page 28 TO 161 S-DIAS DIGITAL OUTPUT MODULE Recommended minimum distances of the S-DIAS modules to the surrounding components or control cabinet wall: a, b, c … distances in mm (inches) Page 26 26.07.2023...
  • Page 29: Transport/Storage

    S-DIAS DIGITAL OUTPUT MODULE TO 161 10 Transport/Storage INFORMATION This device contains sensitive electronics. During transport and storage, high mechanical stress must therefore be avoided. For storage and transport, the same values for humidity and vibration as for operation must be maintained! Temperature and humidity fluctuations may occur during transport.
  • Page 30: Maintenance

    TO 161 S-DIAS DIGITAL OUTPUT MODULE 12 Maintenance INFORMATION During maintenance as well as servicing, observe the safety instructions from chapter 2 Basic Safety Directives. 12.1 Service This product was constructed for low-maintenance operation. 12.2 Repair INFORMATION In the event of a defect/repair, send the device with a detailed error description to the address listed at the beginning of this document.
  • Page 31: Addressing

    S-DIAS DIGITAL OUTPUT MODULE TO 161 14 Addressing Address Size Access Type Description Reset value (hex) (bytes) Memory Output Register Bit 0 Output 1 0000 0000 Bit 1 Output 2 … Bit 15 Output 16 24 V status Bit 0...
  • Page 32: Supported Cycle Times

    TO 161 S-DIAS DIGITAL OUTPUT MODULE 15 Supported Cycle Times 15.1 Cycle Times below 1 ms (in µs) x= supported 15.2 Cycle Times equal to or higher than 1 ms (in ms) x= supported x= supported Page 30 26.07.2023...
  • Page 33: Hardware Class To161

    16 Hardware Class TO161 Hardware Class TO161 for the S-DIAS TO161 digital module This hardware class is used to control the TO 161 hardware module with 16 digital outputs. More information on the hardware can be found in the module documentation.
  • Page 34: Interfaces

    TO 161 S-DIAS DIGITAL OUTPUT MODULE 16.1 Interfaces 16.1.1 Clients The client must be connected to an S-DIAS port, an "SdiasOut"_[x]” server. SdiasIn Place The physical location of the hardware module is entered in this client. Up to 64 modules, 0 to 63, can be assigned.
  • Page 35: Example

    S-DIAS DIGITAL OUTPUT MODULE TO 161 16.2 Example 26.07.2023 Page 33...
  • Page 36 TO 161 S-DIAS DIGITAL OUTPUT MODULE Documentation Changes Change date Affected Chapter Note page(s) 24.10.2013 Added Vibration resistance 23.12.2013 3 Connector Layout Changed image 4.2 Wiring Example Added wiring example 11.02.2014 3 Connector Layout Changed image 3.2 Applicable Connectors Connection capacity added French notes added 01.04.2014...
  • Page 37 S-DIAS DIGITAL OUTPUT MODULE TO 161 22.12.2021 1.1 Digital Output Delay values changed Specifications 4.1 General Information on Outputs adjusted the Digital Outputs 20.05.2022 1.2 Electrical Requirements HW-Version added 06.12.2022 1.3 Miscellaneous UKCA conformity 26.07.2023 Document General chapters added, design 26.07.2023...

Table of Contents