Download Print this page
Wilo DrainLift SANI CUT-L Installation And Operating Instructions Manual

Wilo DrainLift SANI CUT-L Installation And Operating Instructions Manual

Advertisement

Quick Links

Pioneering for You
Wilo-DrainLift SANI CUT-L
en Installation and operating instructions
·
6097572 • Ed.01/2024-08

Advertisement

loading
Need help?

Need help?

Do you have a question about the DrainLift SANI CUT-L and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Wilo DrainLift SANI CUT-L

  • Page 1 Pioneering for You Wilo-DrainLift SANI CUT-L en Installation and operating instructions · 6097572 • Ed.01/2024-08...
  • Page 2 DrainLift SANI CUT-L https://qr.wilo.com/10498...
  • Page 3 Staff qualifications ............. 14 Installation types .............. 14 Operator responsibilities ........... 14 Installation ................ 15 Electrical connection............ 21 7 Commissioning.................  23 Staff qualifications ............. 23 Operator responsibilities ........... 23 Operation ................ 23 Test run ................ 23 Follow-up time.............. 24 8 Operation..................  24 Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 4 All rights reserved. Subject to change Wilo reserves the right to change the listed data without prior notice and is not liable for technical inaccuracies and/or omissions. The illustrations vary from the original and are in- tended as a sample representation of the product.
  • Page 5 Wear safety helmet. Wear safety shoes. Wear safety gloves. Wear respiratory mask. Wear safety glasses. Obey the instructions. Useful information Staff qualifications • The staff knows the local accident prevention regulations. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 6 WILO SE assumes no liability for the articles mentioned regarding their conformity to the applicable standards. Electrical work • Do electrical work only by a qualified electrician. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 7 Obey local regulations for these connections. • Route the ventilation pipe. For floor-mounted or concealed-wall installation in buildings, – route the ventilation pipe over the roof of the building. Obey Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 8 The maximum inflow must be less than the maximum output of the system. • Do not open the inspection opening. • Make sure that the operating space is sufficiently ventilated. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 9 Supply protective equipment. Make sure that staff wears pro- tective equipment. • Make sure that attached safety and warning signs are clearly readable. • Tell staff how the system operates. • Mark and close the working area. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 10 Cleaning agents, disinfectants, dishwashing or laundry detergents in too much quantit- ies, which have a disproportionately high degree of foam formation • Drinking water To use the product correctly, follow these installation and operating instructions. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 11 The high water LED or display shows an alarm signal. Also, the internal buzzer can emit a sound alarm signal. Furthermore, the output for the collective fault signal (SSM) activates. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 12 29 l/7 US.liq.gal. (180 mm*)/39 l/10 US.liq.gal. (250 depending on the inlet height* mm*)/48 l/12 US.liq.gal. (315 mm*) Diagonal dimension 782/802 mm (31/31.5 in) Weight 77.5 ... 86.7 kg (170 ... 191 lb) Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 13 The lifting unit collects and pumps sewage. There can be bacteria and hazardous germs in the tank. Follow these points: • After removal, disinfect the lifting unit. Especially the inner side of the tank. • Obey the factory regulations. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 14 • Obey the consulting documents to lay and prepare the pipes. • To prevent the mains connection from flooding, mount the mains connection at a suffi- cient height. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 15 Be conscious of the diagonal dimension of the lifting unit. • Install lifting accessory on flat, clean and hard surface. Make sure to get access to the storage area and installation location easily. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 16 Ventilation of the lifting unit over the roof – Sufficient space for maintenance and repair: safe and easy access to tank opening, non-return valve, motor, and switchgear • For concealed-floor installation, follow these points: Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 17 To prevent frost, install the discharge line sufficiently deep. • Install a shut-off valve. ✓ The lifting unit is installed correctly. ✓ The discharge pipe is installed correctly as shown in the consulting documents. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 18 - If the distance is too small, decrease the length of the discharge pipe. - If the distance is too large, extend or replace the discharge pipe. ▶ Discharge pipe is connected. Next step: Connecting the inlet. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 19 Be conscious of the minimum inlet height (from floor to the centre of the inlet pipe): 180 mm (7 in). • Make sure that all connections are fully tight. • Install a shut-off valve in the inlet pipe. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 20 For floor-mounted or concealed-wall installation in buildings, route the ventilation pipe over the roof of the building. • For concealed-floor installation (underground installation) outside of buildings, route the ventilation pipe over the surface. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 21 Fuse on mains side Circuit breaker • Make sure the type and switching characteristics of the circuit breakers are compatible with the rated current of the connected product. • Obey local regulations. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 22 NOTICE! If the inlet is below the permitted inlet height, there is a risk of a permanent backflow into the inlet pipe. Wilo-Control MS-L switchgear For the Wilo-Control MS-L switchgear, set the switching points through fixed switch posi- tions of DIP switch 3: Switching points Inlet height: 180 mm (7 in) or higher...
  • Page 23 Unscrew the inspection cover on the collection tank. Slowly fill the collection tank with water through the inspection opening with a hose. NOTICE! Risk of malfunction! Do not hold water jet directly above the float switch. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 24 • Max. short-time fluid temperature: 65 °C (149 °F), 5 min • Ambient temperature: 3 ... 40 °C (37 ... 104 °F) • Maximum switching frequency: 120/h • Operating mode: S3 10% Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 25 • Disinfect the lifting unit and operating space. • Dispose of rinsing water to the sewer • Obey local regulations to dispose of protective clothing and cleaning material. • Obey the factory regulations. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 26 • Disinfect the lifting unit and operating space. • Dispose of rinsing water to the sewer • Obey local regulations to dispose of protective clothing and cleaning material. • Obey the factory regulations. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 27 Loosen the floor anchoring. Pull the lifting unit carefully out of the pipework. ▶ Lifting unit is dismantled. Next step: Cleaning and disinfecting the lifting unit and the operating space. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 28 Order spare parts through customer service. To prevent return queries and incorrect orders, always supply the serial or article number. Subject to change without prior notice. Disposal 12.1 Protective clothing Obey local regulations to dispose of worn protective clothing. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 29 Only return the product to a designated and permitted collection point. • Obey local regulations. Consult your local municipality, the nearest waste disposal site, or your retailer for a correct disposal. See www.wilo‑recycling.com for more information about recycling. Installation and operating instructions • Wilo-DrainLift SANI CUT-L • Ed.01/2024-08...
  • Page 32 Local contact at www.wilo.com/contact WILO SE Wilopark 1 44263 Dortmund Germany T +49 (0)231 4102-0 T +49 (0)231 4102-7363 wilo@wilo.com Pioneering for You www.wilo.com...