Tower (Inbuilt battery UPS)
PARAMETERS
Topology
Output power capacity
INPUT
Phase
Low line transfer
Voltage
Low line comeback
range
High line transfer
High line comeback
Frequency range
Power factor
OUTPUT
Output voltage
AC voltage regulation
Frequency range
Frequency range (Battery mode)
Overload
Current crest ratio
Harmonic distortion
AC mode to battery mode
Transfer
Time
Inverter to bypass
Waveform (Battery mode)
BATTERY
Battery Type
Number of batteries
Standard
Battery voltage
In-built
battery
Recharge time
model
Charging current
Charging voltage
PHYSICAL
Dimension D X W X H (in mm)
Standard
Model
Net Weight (kgs)
ENVIRONMENT
Operation humidity
Noise level
MANAGEMENT
Smart RS-232 or USB
Optional SNMP
Note :
Derate capacity to 80% of capacity in Frequency converter mode or when the output voltage is adjusted to 200/208VAC.
Product specifications are subject to change without further notice.
20
1KVA
True online double conversion UPS
800 W
160VAC/ 140VAC/ 120VAC/ 110VAC ±5% (Ambient temperature <35*C)
(based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
175VAC/ 155VAC/ 135VAC/ 125VAC ± 5 % (Ambient temperature <35*C)
(based on load percentage 100%-80 %/ 80%-70% /70-60%/ 60%-0)
≧ 0.9 @ nominal voltage (input voltage)
200/208/220/230/240 VAC
±1% (Battery mode)
47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized range)
50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
Ambient temperature <35*C
105%~110%: UPS shuts down after 10 minutes in battery mode or transfers to bypass
when the utility is normal
110%~130%: UPS shuts down after 1minute in battery mode or transfers to bypass
when the utility is normal
>130%: UPS shuts down after 3 seconds in battery mode or transfers to bypass
when the utility is normal
≦ 3 % THD (linear load); ≦ 6 % THD (non-linear load)
2
24VDC
4 hours to recharge upto 90% capacity (Typical)
27.4 VDC ± 1%
282 X 145 X 220
9.8
20-90 % RH @ 0- 40°C (non-condensing)
less than 50dBA @ 1 Meter
Supports Windows® 2000/2003/XP/Vista/2008/7/8, Linux, Unix and MAC
Power management from SNMP manager and web browser
2KVA
1600 W
Single phase
300 VAC ± 5 %
290 VAC ± 5 %
40Hz ~ 70 Hz
3:1
Zero
4 ms (Typical)
Pure sinewave
12V-7AH/9AH
4
48VDC
1.0 A (max.)
54.7 VDC ±1%
397 X 145 X 220
421 X 190 X 318
17
3 KVA
2400 W
6
72VDC
82.1 VDC ±1%
26.2