06: Bypass enable/disable when UPS is off
Interface
06
BYPASS
07: Bypass voltage range setting
Interface
07
HLS
I N P U T
BYPASS
08: Autonomy limitation setting
Interface
08
M
14
EnA
260
Vac
999
Setting
Parameter 3: Enable or disable Bypass function.
You may choose the following two options:
ENA: Bypass enable
DIS: Bypass disable (Default)
Setting
Parameter 2 & 3: S Parameter 2 & 3: Set the acceptable high
voltage point and acceptable low voltage point for Bypass
mode by pressing the Down key or Up key.
HLS: Bypass high voltage point
For 200/208/220/230/240 VAC models:
230-264: setting the high voltage point in parameter 3 from
230Vac to 264Vac. (Default: 264Vac)
LLS: Bypass low voltage point
For 200/208/220/230/240 VAC models:
170-220: setting the low voltage point in parameter 3 from
170Vac to 220Vac. (Default: 170Vac)
Setting
Parameter 3: Set up backup time on battery mode for
general outlets.
0-999: setting the backup time in minutes from 0-999 for
general outlets on battery mode.
0: When setting as "0", the backup time will be only
10 seconds.
999: When setting as "999", the backup time setting will be
disabled. (Default)