Connecting the device in safety applications ............ 21 Connecting the device to Ethernet ................ 22 6.3.1 Applications with QuickConnect (QC) and Fast Start Up (FSU) ........ 22 V02.00 | 2024/08 | 2 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 3
Adding the devices from the Catalog files to the new project........ 93 7.8.2 Configuring the device in Logix Designer................ 95 V02.00 | 2024/08 | 3 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 4
Technical data – TBEN-LL-16DOP ................ 151 14.5 Technical data – TBEN-LL-8DIP-8DOP.............. 152 15 Turck branches — contact data .................... 153 V02.00 | 2024/08 | 4 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
If you have any suggestions for improving the design or if some information is missing in the document, please send your suggestions to techdoc@turck.com. V02.00 | 2024/08 | 5 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Screw caps or blind caps for network and I/O connectors Labeling clips Turck service Turck supports you in your projects – from the initial analysis right through to the commission- ing of your application. The Turck product database at www.turck.com...
The product is designed according to state of the art technology. Residual hazards, however, still exist. Observe the following safety instructions and warnings in order to prevent danger to persons and property. Turck accepts no liability for damage caused by failure to observe these safety instructions.
Provide unused male connectors with suitable sealing or blanking caps in order to ensure degree of protection IP65, IP67 or IP69K The tightening torque for the M4 screws is 0.5 Nm. V02.00 | 2024/08 | 8 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
4.1.2 Indication elements The device is provided with the following LEDs: Power supply voltage Group and bus error Status Diagnostics V02.00 | 2024/08 | 9 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
– Network load class 3 EtherNet/IP: – Support of the IO-Link Parameter Object for asynchronous services (IO-Link CALL) – Predefined in- and oputput assemblies V02.00 | 2024/08 | 11 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
BEEP (Backplane Ethernet Extension Protocol) is a technology that is available in many digital Turck multi protocol block I/O modules. BEEP allows a network, of up to 33 participants (one controller and 32 devices) or 480 bytes of data, to appear to the PLC as a single device on a single connection using a single IP address.
Fit the housing cover and screw on as shown in the following figure. The tightening torque for the Torx T8 screw is 0.5 Nm. Fig. 7: Installing the device in the TB-SG-L protective housing V02.00 | 2024/08 | 17 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
The mechanical and electrical properties of the device are not impaired. To prevent material wear and color changes: Protect the device from direct sunlight with protective panels. V02.00 | 2024/08 | 18 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
RC element, the grounding clip must be removed. In the delivery state, the grounding clip is mounted. V02.00 | 2024/08 | 19 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
With mounted grounding clip: The shielding of the fieldbus and the module grounding are connected to the reference potential of the installation. V02.00 | 2024/08 | 20 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Provide unused male connectors with suitable sealing or blanking caps. The tightening torque for the M4 screws is 0.5 Nm. V02.00 | 2024/08 | 21 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Do not use crossover cables in applications with QuickConnect (QC) and and Fast Start Up (FSU) applications. Connect incoming Ethernet cables to XF1. Connect outgoing Ethernet cables to XF2. V02.00 | 2024/08 | 22 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
If V2 is undershot, the PWR LED changes from green to green flashing or red (depending on the configuration). If V1 is undershot, the PWR LED extinguishes. V02.00 | 2024/08 | 23 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
V2 supply. Fig. 16: Power supply of TBEN-LL-16DIP Fig. 17: Power supply of TBEN-LL-16DXP and TBEN-LL-8DIP-8DOP Fig. 18: Power supply of TBEN-LL-16DOP V02.00 | 2024/08 | 24 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
ISO 13849-1:201, Annex C.5: "MTTF data of electrical components" and D.1: "Parts count method". V02.00 | 2024/08 | 28 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
If the galvanic isolation is used, ensure on the application side that no external feed can occur. DXP channels that operate with safe disconnectable potential must be supplied by the corresponding conenctor. V02.00 | 2024/08 | 29 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Damage to the device due to foreign material or liquids penetrating the device is possible. Tightly close the service window. V02.00 | 2024/08 | 31 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
The devices are addressed via the prefix ”TBEN” and the address set on the rotary coding switches as follows: Switch position 701: TBEN_701 … Switch position 899: TBEN_899 V02.00 | 2024/08 | 32 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 33
The factory reset resets all settings to the default values: Network setting (IP address, subnet mask, gateway) PROFINET device name Device parameters V02.00 | 2024/08 | 33 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
TAS or on the device website. Change the device name, the IP address and the network mask if necessary. V02.00 | 2024/08 | 34 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 35
Adjusting network settings and operation mode Save changes by clicking on APPLY . Fig. 35: Changing network settings in TAS V02.00 | 2024/08 | 35 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Adjust the network settings. Write the changes into the device via SET NETWORK CONFIGURATION. Fig. 36: Web server – adjusting network settings V02.00 | 2024/08 | 36 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
For the correct cabling in FSU applications please observe the note in the chapter "Connecting the Device to Ethernet” [} 22]. V02.00 | 2024/08 | 37 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 38
Set "Transmission rate/duplex" to a fix value. Deactivate auto-negotiation Fig. 37: TIA-Portal – port-settings for FSU V02.00 | 2024/08 | 38 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
For PROFINET, the response monitoring time must be selected accordingly > 200 ms. It is not possible to use Fast Start-Up in an MRP network. V02.00 | 2024/08 | 39 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
The device is added to the Hardware catalog of the programming software. Fig. 39: Installing the GSDML file in TIA Portal V02.00 | 2024/08 | 42 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Connect the devices to the PLC in the Devices & networks editor. Fig. 40: Connecting the device to the PLC V02.00 | 2024/08 | 43 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Functions Ò Assign PROFINET device name. Assign the desired PROFINET device name with Assign name. Fig. 41: TIA-Portal: Assigning the PROFINET device name V02.00 | 2024/08 | 44 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Select Device view Ò register Properties Ò Ethernet addresses. Assign the desired IP address. Fig. 42: TIA-Portal: Assigning the IP address V02.00 | 2024/08 | 45 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Start the online mode (Go online). The device has been successfully connected to the PLC. Fig. 44: TIA-Portal: Online mode V02.00 | 2024/08 | 47 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
LED behavior (PWR) at V2 undervoltage Bit 0: 0 = red 1 = green flashing 0x2400 read only V1 in mV: 0 at undervoltage V02.00 | 2024/08 | 48 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
0x113D. Both registers can also be written with one single request using the function codes FC16 and FC23. The parameters are reset tot default values. Save changes via a subsequent Save service. V02.00 | 2024/08 | 50 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
16 bit Bit by bit TBEN-LL-16DXP 16 bit 16 bit Bit by bit TBEN-LL-8DIP-8DOP 8 bit 8 bit Bit by bit V02.00 | 2024/08 | 51 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
"0" after the watchdog time has expired, unless another protocol (PROFINET, EtherNet/IP) has been activated in the meantime. V02.00 | 2024/08 | 57 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
The programming software has been started. A new project has been created. The PLC has been added to the project. V02.00 | 2024/08 | 58 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Click Insert device. The Ethernet Adapter is added to the project tree as Ethernet (Ethernet). Fig. 45: Adding the Ethernet Adapter V02.00 | 2024/08 | 59 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 60
Select Add Device. Double-click Modbus TCP Master. The Modbus_TCP_Master is added to the project tree. Fig. 46: Adding the Modbus TCP Master V02.00 | 2024/08 | 60 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 61
Select Add Device. Double-click Modbus TCP Slave. The Modbus_TCP_Slave is added to the project tree. Fig. 47: Adding the Modbus TCP Slave V02.00 | 2024/08 | 61 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Click Device Ò Scan network. Select Modbus TCP Master (here: TX715-P3CV01) and confirm with OK. Fig. 48: Configuring the network interface V02.00 | 2024/08 | 62 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 63
Open the dialog box Network Adapter by clicking the Browse... button in the register tab General. Select the interface TX715-P3CV01 (here: 192.168.145.72) Fig. 49: Selecting the interface V02.00 | 2024/08 | 63 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Enter the slave IP address in the General register tab (here: 192.168.145.200). Fig. 50: Modbus TCP Slave: Setting the IP address V02.00 | 2024/08 | 64 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Channel name Access type: Read Input Registers Offset: 0x0000 Length: 1 register Confirm with OK. Fig. 51: Defining the input register V02.00 | 2024/08 | 65 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 66
Access type Write Single Register Offset: 0x0800 Length: 1 register Confirm with OK. Fig. 52: Defining the output data register V02.00 | 2024/08 | 66 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Download the application to the PLC and start it via Debug Ò Start. The Modbus TCP communication is setup. Fig. 54: Modbus TCP communication V02.00 | 2024/08 | 67 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Click onto register tab Modbus TCP Slave I/O Mapping. Set the function Always update variables to Enabled 1 (…). The process data are displayed. Fig. 55: Process data V02.00 | 2024/08 | 68 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Deactivated For information on the correct connection of Ethernet cables in QuickConnect applications, please refer to the chapter Connecting [} 22]. V02.00 | 2024/08 | 69 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 70
Activate Quick Connect via Class Instance Attribute as follows: Class Instance Attribute Value 0xF5 0x01 0x0C 0: deactivated (default) 1: activated V02.00 | 2024/08 | 70 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Ethernet traffic, so that a line topology is created for normal Ethernet telegrams. DLR messages can continue to use the ring in both directions and thus continuously check the function of the ring. V02.00 | 2024/08 | 71 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Contains the last 3 bytes of the MAC number 0x07 Product STRUCT OF: i. e.: TBEN-LL-16DXP name USINT STRING [13] V02.00 | 2024/08 | 72 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 73
Starts the reset service for the device. 0x0E Get_Attribute_Single Returns the content of a specified attribute. 0x10 Set_Attribute_Single Modifies a single attribute. V02.00 | 2024/08 | 73 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Dec. Hex. 0x01 Get_Attribute_All Returns a predefined list of object attributes. 0x0E Get_Attribute_Single Returns the content of a specified attribute. V02.00 | 2024/08 | 74 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 75
0x18 Inv. DI14 0x19 Inv. DI15 0x1A IST DI0 0x1B IST DI1 … … 0x28 IST DI14 0x29 IST DI15 V02.00 | 2024/08 | 75 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 76
EN DO1 … … 0x38 EN DO14 0x39 EN DO15 0x3A SRO0 0x3B SRO1 … … 0x48 SRO14 0x49 SRO15 V02.00 | 2024/08 | 76 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 77
Eth1 port Quick 0x09 setup setup Connect Parameter data [} 124] 0x0A SRO8 0x0B SRO9 … … 0x18 SRO14 0x19 SRO15 V02.00 | 2024/08 | 77 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
V1 X0 Ch14 Ch12 Ch10 Ch15 Ch13 Ch11 Output data – TBEN-LL-16DIP control word Word Bit no. Control 0x0000 Reserved V02.00 | 2024/08 | 79 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Physical STRUCT link object Path size UINT Number of 16 bit words: 0x02 Path Padded 0x20, 0xF6, 0x24, 0x01 EPATH V02.00 | 2024/08 | 82 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 83
The device is capable of resolving host names by querying a DNS server. DHCP client The device is capable of obtaining its network configuration via DHCP. V02.00 | 2024/08 | 83 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 84
0x02 Max. object instance UINT 0x03 Number of instances UINT 0x06 Max. class identifier UINT 0x07 Max. instance attribute UINT V02.00 | 2024/08 | 84 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 85
1 = local hardware error detected Common services Service code Class Instance Meaning Dec. Hex. 0x01 Get_Attribute_All 0x0E Get_Attribute_Single 0x4C Enetlink_Get_and_Clear V02.00 | 2024/08 | 85 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
USINT 0: No curr. 1: Yes 0x12 DO 9 – manual reset after over- USINT 0: No curr. 1: Yes V02.00 | 2024/08 | 86 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 87
Bit 0: output value Ch0 Bit 1: output value Ch1 … Bit 6: output value Ch6 Bit 7: output value Ch7 V02.00 | 2024/08 | 87 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 88
Bit 0: input value Ch0 Bit 1: input value Ch1 … Bit 14: input value Ch14 Bit 15: input value Ch15 V02.00 | 2024/08 | 88 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 89
Bit 0: output value Ch0 Bit 1: output value Ch1 … Bit 14: output value Ch14 Bit 15: output value Ch15 V02.00 | 2024/08 | 89 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 90
DXP 0 – Overcurrent output USINT 0: - 1: active 0x42 DXP 1 – Overcurrent output USINT 0: - 1: active … … … V02.00 | 2024/08 | 90 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 91
Bit 0: output value Ch0 Bit 1: output value Ch1 … Bit 14: output value Ch14 Bit 15: output value Ch15 V02.00 | 2024/08 | 91 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
A new project has been created in a second instance of RSLogix. The PLC and the Scanner mentioned above have been added to the project in the second instance of Studio5000. V02.00 | 2024/08 | 92 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Adding the devices from the Catalog files to the new project Right-click the device entry and use Copy. Fig. 58: RSLogix – copying the device entry from catalog file V02.00 | 2024/08 | 93 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 94
Right-click the EtherNet/IP Scanner in the 2nd instance of Logix Designer and add the device to the project via Paste. Fig. 59: RS Logix - adding the device to the project V02.00 | 2024/08 | 94 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Set the IP address of the device (example: 192.168.145.181). Fig. 60: Setting module name and IP address Optional: Set the connection parameters. Fig. 61: Setting the connection parameters V02.00 | 2024/08 | 95 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Open the Controller Tags of the device. Parameterize the device via the Controller Tags TBEN-LL-16DXP:C. Fig. 62: Parameterizing the device V02.00 | 2024/08 | 96 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Select the PLC. Set the communication path via Set Project Path. The communication path is set Fig. 63: Setting the communication path V02.00 | 2024/08 | 97 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 98
Click Download in the following dialog (Connect To Go Online) Confirm all following messages. The program is downloaded to the PLC. The online connection is established. V02.00 | 2024/08 | 98 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
The access to the input data (TBEN-LL-16DXP:I) and output data (TBEN-LL-16DXP:O) is possible. Fig. 65: Controller Tags in the project tree V02.00 | 2024/08 | 99 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
61451 (port number of server station for NodeSearch and IPAddressSet) 7.9.2 CSP+ files The CSP+ files can be downloaded free of charge at www.turck.com. V02.00 | 2024/08 | 100 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
X0…X7 = connector at the device, P… = pin 7.9.6 Word area The word area does not contain any data for the digital TBEN-L... devices. V02.00 | 2024/08 | 108 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
(0xAD00… 0xADFF) closes this connection. If the value -1 (0xFFFF) is written, all acyclic connections opened for CC-Link are closed. V02.00 | 2024/08 | 109 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 110
1…n Accesses the input data of one (sub)module. Data is … structured in the native order of that (sub)module. 0x00… V02.00 | 2024/08 | 110 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 111
Accesses the diagnostic data data of one (sub)module. … Data is structured in the native order of that (sub)mod- 0x00… ule. V02.00 | 2024/08 | 111 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Connecting devices to a CC-Link IE Field Basic client with GX Works3 Naming convention Turck uses the terms ”client” and ”server”. The following description uses the terms “Master Sta- tion” (client) and “Slave Station” (server) only because of the naming in Melsoft GX Works.
Under CC-Link IEF Baisc Settings, set the option To Use or Not to Use CC-Link IEF Basic Setting to Use in order to activate Fig. 67: GX Works3: Activate CC-Link IEF Basic on CPU V02.00 | 2024/08 | 113 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Under Module Parameters Ò CC-Link IEF Basic Settings open the function Network Configuration Settings. Fig. 68: GX Works3: Network Configuration Settings V02.00 | 2024/08 | 114 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 115
Scan the CC-Link IEF Basic network under CC-Link IEF Basic Configuration via Detect Now. Fig. 69: GX Works3: scanning the CC-Link IEF Basic network V02.00 | 2024/08 | 115 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 116
For devices that can be integrated with different process data variables (profiles) (here: TBEN-S2-4IOL): select the requested profile under Station Type. V02.00 | 2024/08 | 116 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 117
All parameters for one slot (in the example below: Slot 1) must be set. It is not pos- sible to set individual parameters for a slot. V02.00 | 2024/08 | 117 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 118
Connecting devices to a CC-Link IE Field Basic client with GX Works3 Set the parameters and store the settings via Execute. Fig. 72: GX Works3: Parameterizing the device V02.00 | 2024/08 | 118 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 119
Accept the changes in the network structure under Module Parameters with Apply. Fig. 74: GX Works3: Module Parameters, accept changes V02.00 | 2024/08 | 119 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Fig. 75: GX Works3: Process data mapping in Refresh Settings NOTE Adjusting the mapping may require a voltage reset of the control unit. V02.00 | 2024/08 | 120 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Write the configuration to the PLC via Online Ò Write to PLC. Fig. 76: GX Works3: Writing the configuration to the PLC V02.00 | 2024/08 | 121 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 122
If necessary, define which data have to be written and press Execute. Fig. 77: GX Works3: Selecting data to be written V02.00 | 2024/08 | 122 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
The mapping shows a signal at the 2nd Digital input of the 1st CC-Link device (station address 2, TBEN-LL-8DIP-8DOP) [} 114]. V02.00 | 2024/08 | 123 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
0x02 The 24 VDC sensor/actuator supply at pin1 of the connector is switched off. V02.00 | 2024/08 | 124 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Deactivate EtherNet/IP Explicit disabling of the Ethernet pro- tocols or the web server Deactivate Modbus TCP Deactivate web server V02.00 | 2024/08 | 125 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 128
ARGEE program running in the device DIAG Diagnostic messages at the device Force Mode activated V1 too low V2 too low V02.00 | 2024/08 | 128 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
DO8 X4 0x01 Reserved Meaning of the process data bits Name Meaning DO… Digital output DX… DXP channel P… X… Connector V02.00 | 2024/08 | 129 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Overload of the sensor and actuator supply In devices with group diagnostics, all connector LEDs of the supply group flash simultaneously in case of an error. V02.00 | 2024/08 | 130 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Activating or deactivating the status and control word modifies the process data mapping. Control Word The control word has no function. V02.00 | 2024/08 | 131 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
If there are no faults, there is a device malfunction. In this case, decommission the device and replace it with a new device of the same type. V02.00 | 2024/08 | 136 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
TCP network. This enables a firmware update to be performed for multiple devices at once. V02.00 | 2024/08 | 137 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 138
Click LOG IN. Click SELECT FILE. Open the directory of the firmware file. Fig. 82: Selecting a firmware file V02.00 | 2024/08 | 138 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 139
Click START to start the firmware update. Fig. 83: Firmware update progress The progress of the firmware update is displayed. V02.00 | 2024/08 | 139 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Click Firmware Ò SELECT FIRMWARE FILE Select the new firmware file and load it via Open. Fig. 84: Webserver – Selecting the firmware file V02.00 | 2024/08 | 140 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 141
The progress of the firmware update is displayed. Fig. 86: Webserver – Firmware update running Restart the device after the update process has been completed. V02.00 | 2024/08 | 141 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Example: Update the Firmware with the PACTware FDT Frame Application Launch PACTware. Right-click HOST PC Ò Add device. Fig. 87: Adding a device in PACTware V02.00 | 2024/08 | 142 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 143
Fig. 88: Selecting the Ethernet interface Double-click the connected device. PACTware opens the bus address management. Fig. 89: Opening the busaddress management V02.00 | 2024/08 | 143 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 144
PACTware shows the progress of the firmware update with a green bar at the bottom of the screen. Fig. 92: Firmware update running V02.00 | 2024/08 | 144 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Disposal The devices must be disposed of properly and do not belong in the domestic waste. V02.00 | 2024/08 | 145 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Number of TCP connections Input register, start address 0 (0x0000) Output register, start address 2048 (0x0800) Local port Port 502, fix setting V02.00 | 2024/08 | 146 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 147
Housing color Black Material screw 303 stainless steel Material label Polycarbonate Halogen free Mounting 2 mounting holes, Ø 6.3 mm V02.00 | 2024/08 | 147 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 148
Part 15 of the FCC regulations. Operation of this device in a residential area may cause harmful interference. In this case users must rectify the interference at their own cost. V02.00 | 2024/08 | 148 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Galvanic isolation to XF1/XF2, voltage proof up to 500 VAC General information MTTF 193 years acc. to SN 29500 (Ed. 99) 20 °C V02.00 | 2024/08 | 149 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Galvanic isolation to XF1/XF2, voltage proof up to 500 VAC General information MTTF 134 years acc. to SN 29500 (Ed. 99) 20 °C V02.00 | 2024/08 | 150 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Galvanic isolation to XF1/XF2, voltage proof up to 500 VAC General information MTTF 165 years acc. to SN 29500 (Ed. 99) 20 °C V02.00 | 2024/08 | 151 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Galvanic isolation to XF1/XF2, voltage proof up to 500 VAC General information MTTF 157 years acc. to SN 29500 (Ed. 99) 20 °C V02.00 | 2024/08 | 152 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Via San Domenico 5, IT-20008 Bareggio (MI) www.turckbanner.it Japan TURCK Japan Corporation ISM Akihabara 1F, 1-24-2, Taito, Taito-ku, 110-0016 Tokyo www.turck.jp V02.00 | 2024/08 | 153 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 154
United Kingdom TURCK BANNER LIMITED Blenheim House, Hurricane Way, GB-SS11 8YT Wickford, Essex www.turckbanner.co.uk Turck Inc. 3000 Campus Drive, USA-MN 55441 Minneapolis www.turck.us V02.00 | 2024/08 | 154 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 155
Over 30 subsidiaries and 60 representations worldwide! 100030991 | 2024/08 100030991 www.turck.com...