Solution 4000 control panel
This output operates when a user activates a Codepad Medical Alarm by pressing [7] and
[9] at the same time on the remote codepad. This output is reset when a valid User Code is
entered at the remote codepad.
1,9 Codepad Fire Alarm
This output operates when a user activates a Codepad Medical Alarm by pressing [4] and
[6] at the same time on the remote codepad. This output is reset when a valid User Code is
entered at the remote codepad.
1,10 Codepad Panic Alarm
This output operates when a user activates a Codepad Panic Alarm by pressing either [1]
and [3] or [STAY] and [AWAY] at the same time on the remote codepad , or when a keyfob
Panic Alarm is activated by pressing ARM button and DISARM button together on the
learned keyfob. This output is reset when a valid User Code is entered at the remote
codepad, or ARM or DISARM button on the keyfob is pressed to reset alarm.
1,11 Codepad Duress Alarm
This output operates when a user activates a Duress Alarm by adding a 9 to the end of the
User Code used to disarm the system. This output is reset the next time the system is
armed.
1,12 Codepad PIN Error - Access Denied
This output operates when the wrong code is entered more times than allowed. The number
of incorrect attempts allowed is programmed in Location 424 or TEXT codepad option
"Access Retry" (Menu 2-3). This output is reset when a valid User Code is entered after the
codepad is unlocked.
1,14 Horn Speaker (Output 1 Only)
This output operates only on Output 1. Use this output for one or two 8 Ω horn speakers.
To enable monitoring of the horn speaker, select Option 2 in Location 492.
1,15 Sirens Running
This output operates for the duration of the Siren Run Time programmed in Location 479.
When the sirens are activated, this output is reset when the Siren Run Time expires. The
relay output (Output 4) is set by default for this operation.
2,0 Strobe Operating
This output operates when an alarm occurs and is reset when a valid User Code is entered.
The strobe output (Output 3) is set by default for strobe operation and is programmed to
reset automatically after 8 hours.
2,1 Silent Alarm
This output operates when any zone programmed to be silent activates. The output is reset
when the Siren Run Time expires, an audible alarm is activated, or a valid User Code is
entered.
2,2 Alarm When in STAY Mode
This output operates when an audible alarm zone is activated when the system is armed in
STAY Mode 1 or STAY Mode 2. The output is reset when the system is disarmed. Silent
alarm will not trigger this event.
2,3 Alarm When in AWAY Mode
This output operates when an audible zone alarm is activated when the system is armed in
AWAY Mode. The output is reset when the system is disarmed. Silent alarm will not trigger
this event.
2,4 Mimic System Fault
This output operates when any system fault occurs. The output is reset when all system
faults are restored.
2,5 Fire Alarm Resetting
Bosch Security Systems B.V.
Installation manual
Programmable Outputs | en 151
2024-07 | V01 | F.01U.418.606