Setting and Wiring Hardware
56
Connect the Master and DeviceNet Communications
Unit with the communications cable.
Connect the Slice I/O Units to the DeviceNet
Communications Unit.
Set the DeviceNet node address with the rotary
switches or the Configurator. After setting the node
address, turn the power ON again or reset the Unit
from the Configurator.
Turn ON (OFF to ON) pin 1 of the DIP switch on the
front of the DeviceNet Communications Unit. The
Unit will create a table recording the Slice I/O Unit
configuration at that time. The Unit compares the
configuration in the table with the actual configuration
when the power is turned ON. A new table can be
created by turning pin 1 ON again with power ON.
Set functions in the
DeviceNet Communications Unit?
Yes
Set each desired function with explicit message
commands or from the DeviceNet Communications
Unit's Edit Device Parameters Window in the
Configurator.
Select and allocate
particular data for the connected
Slice I/O Units and set functions?
Yes
Select allocation data for the connected Slice I/O
Units. Set each desired function with explicit message
commands or from the DeviceNet Communications
Unit's Edit Device Parameters Window in the
Configurator. Download all of the parameters together
to the Units. (Refer to the GRT1 Series Slice I/O Units
Operation Manual for details on each function.
Section 4-3
No
Settings not needed.
No
Settings not needed.