Wiring DeviceNet Communications Cables
48
2. Peel back the mesh shield carefully to expose the signal lines, power lines,
and the shielding wire. The shielding wire will be loose on the outside of
the other lines, but it is harder than the mesh shield and should be easily
identified.
3. Remove the exposed mesh shield, remove the aluminum tape from the sig-
nal and power lines, and strip the covering from the signal and power lines
to the proper length for the crimp terminal connectors. Twist together the
wires of each of the signal and power lines.
Strip to match
the crimp
terminals.
4. Attach the crimp terminals to the lines and then cover any exposed areas
of the cable and lines with electrician's tape or heat-shrinking tubes.
Orient the connector properly, loosen the line set screws, and then insert
the lines in order: Red, white, shield, blue, and then black.
The DeviceNet Communications Unit is equipped with screwless clamping
terminals. It is not necessary to secure the lines with screws as with previ-
ous connectors. Push up the orange tab and then insert each line into the
back of each hole.
Release the orange lever after inserting the lines, and gently pull each line
to check that it is securely connected to the connector.
Red (+V)
Blue
(CAN L)
Black (−V)
There are colored stickers provided on the Master Unit and Slaves that
match the colors of the lines to be inserted. Check that the colors of the
lines and stickers match when wiring the connectors.
The colors used are as follows:
Color
Red
White
-
Blue
Black
Shield wire
White
(CAN H)
Shield
Signal
Power line, positive voltage (+V)
Communications line, high (CAN H)
Shield
Communications line, low (CAN L)
Power line, negative voltage (−V)
Section 3-3