Specifying The Scaling Factor For Input Pulse Frequency; Specifying The Scaling Factor For Input Pulse Frequency (Inp, Dsp) - Omron K3GN - V1.04 User Manual

1/32 din digital panel meter
Table of Contents

Advertisement

5.12 Specifying the Scaling Factor for Input Pulse Frequency

inp
dsp
TIPS
The decimal point position of
parameter " inp " is automati-
cally set depending on
setting of the input-pulse
frequency range as follows.
30 Hz:
,,,.,,
5 kHz:
,,,,,
5.12 Specifying the Scaling Factor for Input Pulse Frequency
These parameters allow you to specify the scaling factor.
Before specifying the scaling factor, you must set the input type parameter to
"pulse".
Parameter
Set value
:9999 ~ 99999
inp
:9999 ~ 99999
dsp
Readout
dsp
The input value can be set by teaching.
To allow a readout of 10.000 when the input value is 4.2 kHz (= 4200 Hz), for
example, set the parameters as follows.
- inp = 4200
- dsp = 10000
Specify the decimal point position of the display value with parameter dp.
For details, refer to Section 6.2 Scaling.
Procedure
A.
When the product is at the operation level,
press the L key and hold it down for at least
three seconds to enter the initial setting level.
"s" will appear on the level indicator, indicating
the product has entered the initial setting level.
B.
Press the M key several times until parameter
"inp" appears on the main indicator.
"T" will be illuminated, indicating teaching of
this parameter is possible.
For the procedure of teaching, refer to the next
page.
C.
Press the S key to display the set value of the
parameter on the main indicator.
The current set value of parameter "inp" will
appear on the indicator.
D.
Press the S key again.
The set value will start blinking, indicating the
product is in the change state.
E.
Use the S and
/
ZERO
value.
Description
Any input value
Output value (readout) corresponding to inp
Input value
inp
S
keys to change the set
Initial setting level
L
0in-t
T
s
3 sec.
"s" appears.
"T" is illuminated.
M ...
ii n p
T
p
s
S
5 0 0 0
T
5
s
"SV" is illuminated.
S
55000
T
s
/
4200
T
ZERO
4
s
55