5.20 Specifying the Hysteresis
hys1
hys2
TIPS
A hysteresis setting of "0" is
assumed to be a hysteresis
setting of "1".
These parameters allow you to specify the hysteresis for each of comparative
outputs 1 and 2.
Parameter
Set value
0 ~ 9999
hys
The setting of the decimal point position parameter at the initial setting level is
reflected on the decimal point position of the hysteresis.
For details, refer to Section 6.9 Hysteresis.
Procedure
A.
When the product is at the operation level,
press the L key and hold it down for at least
three seconds to enter the initial setting level.
"s" will appear on the level indicator, indicating
the product has entered the initial setting level.
B.
Press the M key several times until parameter
"amov" is displayed, and then enter password
"–0169".
"f" will appear on the level indicator, indicating
the product has entered the advanced-function
setting level.
For details on how to move to the
advanced-function setting level, refer to Section
5.2 Moving among Levels.
C.
Press the M key several times until parameter
"hys1" appears on the main indicator.
D.
Press the S key to display the set value of
parameter "hys1" on the main indicator.
The current set value will appear on the main
indicator.
E.
Press the S key again.
The set value will start blinking, indicating the
product is in the change state.
F.
Use the S and
/
ZERO
value.
G.
Press the M key to go to parameter "hys2".
The change is saved.
H.
Repeat steps D to G for parameter "hys2".
The next parameter will appear on the main
indicator when you finish setting of parameter
"hys2".
5.20 Specifying the Hysteresis
Advanced-function setting level
Description
0 to 9999: Hysteresis
S
keys to change the set
L
0in-t
T
s
3 sec.
" s " appears.
0init
T
f
"f" appears.
M ...
ehys1
T
f
S
1
T
ahol
f
"SV" is illuminated.
S
a0001
T
f
/
0005
T
ZERO
4
f
M
ehys2
T
f
color
T
f
69