Output Variable Limit Value Write: WL

Command
@
0
Response

4-13 Output Variable Limit Value Write: WL

Function
Setting Data Range
132
1
W
O
0
3
@
0
1
This command is used to write control output variable limit values to a control
point.
1. Output Variable Limit Value Write (WL) cannot be used at a control point
being auto - tuned.
2. Cooling - side output variable limit values can be written to a control point
provided that the E5ZE is a heating and cooling control model.
The output variable limit function will not work at a control point in the follow-
ing cases.
• The E5ZE is in manual operation.
• The E5ZE has an error.
• The E5ZE detects a sensor input error.
• The E5ZE is stopped.
Setting item
Setting unit
Output variable limit value unit
Default
Setting data
1. The output variable lower - limit value set at a control point must not be larg-
er than the upper output variable limit value.
2. If the output variable lower - limit value set at a control point is 1000, the out-
put value will be always 100.0%.
3. If the output variable upper - limit value set at a control point is 1000, the out-
put value will be always 0.0%.
4. If an output variable limit value is set at a control point as both output vari-
able lower - limit value and upper - limit value, the output value will be the out-
put variable limit value.
0
0
0
5
0
50.0%
W
O
0
0
5
Normal end
Lower limit
0.1
%
0000
0000 to 1000
Section 4-13
*