Alarm Temperature Write: W - Omron E5ZE-8 Communications Manual

Multipoint temperature controller
Table of Contents

Advertisement

Alarm Temperature Write: W%

3-17 Alarm Temperature Write: W%

Function
Setting Data Range
Parameters
Alarm OFF
Upper- and lower-limit alarm
Upper-limit alarm
Lower-limit alarm
Upper- and lower-limit range alarm
Upper- and lower-limit alarm with standby sequence
Upper-limit alarm with standby sequence
Lower-limit alarm with standby sequence
Absolute-value upper-limit alarm
Absolute-value lower-limit alarm
Absolute-value upper-limit alarm with standby
sequence
Absolute-value lower-limit alarm with standby
sequence
HB and HS alarm
Command
When Setting Unit is 1
Unit
@
1
0
x16
x16
Header code
When Setting Unit is 0.1
Unit
@
W
1
0
x16
x16
Header code
106
This command is used to set the alarm temperatures for alarm 1 or 2 of a con-
trol point.
Setting unit
C or F
Default
1. Setting Unit Write (Wt) must be used to set the temperature setting unit of
a control point to 1 or 0.1.
2. It is unnecessary to set an alarm temperature if HB and HS alarm data is
used as the parameters for Alarm Temperature Write (W%).
Control
W
%
Bank
point
Control
%
Bank
point
Setting data
Data code
Alarm set value
3
x10
Or minus sign (-)
00: Alarm 1
01: Alarm 2
Setting data
Data code
Alarm set value
3
2
x10
x10
Or minus sign (-)
00: Alarm 1
01: Alarm 2
1
C
F
0000
-999 to 9999
0000 to 9999
-999 to 9999
-999 to 9999
0000 to 9999
0000 to 9999
-999 to 9999
-999 to 9999
-999 to 9999
-999 to 9999
-999 to 9999
-999 to 9999
---
FCS
2
1
0
x10
x10
x10
Decimal point
FCS
-1
x10
1
x10
0
x10
Decimal point
Section 3-17
0.1
C
F
00000
-9999 to 99999
00000 to 99999
-9999 to 99999
-9999 to 99999
00000 to 99999
00000 to 99999
-9999 to 99999
-9999 to 99999
-9999 to 99999
-9999 to 99999
-9999 to 99999
-9999 to 99999
---
*
s
Terminator
*
s
Terminator