CHAPTER 5 PARAMETERS
Level 1 Mode

Control period (heat)

Control period (cool)

• Sets the pulse output period. Set the control period taking the control characteris-
tics and life expectancy of the controller into consideration.
• In standard control, use the "control period (heat)" parameter. The "control
Function
period (cool)" parameter cannot be used.
• In heating and cooling control, the control period can be set independently for
heating and cooling. Use the "control period (heat)" parameter to set the heating
side control period, and use the "control period (cool)" parameter to set the cool-
ing side control period.
Comment
F Related article
3.3 Setting Output Specifications (page 3-6)
F Related parameters
See
"Control output 1 assignment" "Control output 2 assignment" (setup mode)
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
Model
5--16
Parameter
Setting Range
Control period (heat)
Control period (cool)
Conditions of Use
Relay or voltage output must be set as
the outputs, and the control must be set
to advanced PID control, standard con-
trol or heating and cooling control.
Unit
1 to 99
Second
1 to 99
Second
Default
20
20