AT Execute/Cancel

• Selects the limit cycle of MV change width (40% or 100%) for execution. After AT
execution, the "PID" and the "LBA detection time" (LBA: Loop Break Alarm)
parameters are set automatically.
Function
• During heating and cooling control or position-proportional control, only 100%AT
can be executed.
• When this parameter is selected, the setting becomes [
• To execute 40%AT, select [
execution of auto-tuning, the AT LED flashes. However, note that during heating
Example
and cooling control or position-proportional control, [
of use
• When AT execution ends, the parameter setting automatically returns to [
F Related article
3.7 Adjusting Control Operation (page 3-16)
F Related parameters
See
"Run/Stop" (level 0 mode)
"Proportional band" "Integral time" "Derivative time" (level 1 mode)
"LBA detection time" (level 2 mode)

Set point 0

Set point 1

• Switches set points 0 to 3 by event input for use as the set point (local SP).
• Of set points 0 to 3, the number of valid set points is designated by the "multi-SP
function" parameter.
Function
• The following table shows the relationship between event input and the selected
parameter.
Multi-SP Function
Event Input
Set Point 0
Set Point 1

Set Point 2

Set Point 3
• When the set point has been changed, the setting of whichever is selected in event
input, "set point 0" to "set point 3", is linked and changed.
• The decimal point position is dependent on the selected sensor during tempera-
ture input and on the results of scaling during analog input.
Conditions of Use
The controller must be in operation, con-
trol must be advanced PID control, and
ST must be set to OFF.
], and to execute 100%AT, select [
Conditions of Use
The controller must be in the local SP
mode with the multi-SP function enabled.
1
1
1
OFF
OFF
ON
ON
-
OFF
-
ON
Level 1 Mode
].
] is not displayed.
Set point 2
Set point 3
2
2
OFF
OFF
ON
ON
]. During
].