CHAPTER 5 PARAMETERS
Setup Mode
Input type
• Sets the sensor type by the code.
Function
• Set the code according to the following table. Default is "2: K1 thermocouple".
Comment
F Related article
3.2 Setting Input Specifications (page 3-4)
F Related parameters
See
When input type is set to temperature input:
"_C/_F selection" (setup mode)
When input type is set to voltage input or current input:
"Scaling upper limit" "Scaling lower limit" "Decimal point" (setup mode)
5--26
Set value
0
JPt
-199.9 to 650.0 (_C)
1
Pt
-199.9 to 650.0 (_C)
2
K1
-200 to 1300 (_C)
3
K2
0.0 to 500.0 (_C)
4
J1
-100 to 850 (_C)
5
J2
0.0 to 400.0 (_C)
6
T
-199.9 to 400.0 (_C)
7
E
0 to 600 (_C)
8
L1
-100 to 850 (_C)
9
L2
0.0 to 400.0 (_C)
10
U
-199.9 to 400.0 (_C)
11
N
-200 to 1300 (_C)
12
R
0 to 1700 (_C)
13
S
0 to 1700 (_C)
14
B
100 to 1800 (_C)
15
W
0 to 2300 (_C)
16
PLII
0 to 1300 (_C)
17
4 to 20mA
18
0 to 20mA
19
1 to 5V
20
0 to 5V
21
0 to 10V
Input Type
/-199.9 to 999.9 (_F)
Platinum resistance thermometer
Platinum resistance thermometer
/-199.9 to 999.9 (_F)
/-300 to 2300 (_F)
/0.0 to 900.0 (_F)
/-100 to 1500 (_F)
/0.0 to 750.0 (_F)
/-199.9 to 700.0 (_F)
/0 to 1100 (_F)
/-100 to 1500 (_F)
/0.0 to 750.0 (_F)
/-199.9 to 700.0 (_F)
/-300 to 2300 (_F)
/0 to 3000 (_F)
/0 to 3000 (_F)
/300 to 3200 (_F)
/0 to 4100 (_F)
/0 to 2300 (_F)
Thermocouple
Thermocouple
Current input
Current input
Voltage input
Voltage input