Omron CXONE-ALC-V4 - 10-2010 Operation Manual page 68

Hide thumbs Also See for CXONE-ALC-V4 - 10-2010:
Table of Contents

Advertisement

Three-position ON/OFF (Block Model 002)
52
3
4
1
2
1: MV Status Display
The status is displayed according to the contact information of tag ITEM MVH
(ITEM 093) and MVL (ITEM 095), as shown in the following table.
Lamp
Red: MVH (ITEM 093) is OFF and MVL (ITEM 095) is ON.
Green: Other combinations
Red: MVH (ITEM 093) is OFF and MVL (ITEM 095) is OFF.
Green: Other combinations
Red: MVH (ITEM 093) is ON and MVL (ITEM 095) is OFF.
Green: Other combinations
These lamps are built as ON/OFF Buttons using Simple Rectangles (Type 3).
A Control Flag is set to disable input.
2: Switch to MV Buttons
These buttons switch the contact information of tag ITEM MV (ITEM 093).
Button
Turns OFF MVH (ITEM 093) and turns
ON MVL (ITEM 095).
Turns OFF MVH (ITEM 093) and turns
OFF MVL (ITEM 095).
Turns ON MVH (ITEM 093) and turns
OFF MVL (ITEM 095).
These buttons are created as momentary ON/OFF Buttons using a Select
Shape of type 1, and with no write address set. (Macros are used to write
data.)
The button is displayed as a Select Shape graphic.
When the buttons are touched, tag ITEM A/M_SW (ITEM 086) is referenced,
and when the value is 1, a message is displayed indicating that the value can-
not be set, and setting is disabled.
In the graphic display, 2 is
displayed as follows:
Color
Operation
Section 6-4