An inductive motor driven with an inverter is different from a servomotor in that
the torque at low speeds is so low that it may not be possible to turn the motor
shaft at the minimum frequency. The CP1L provide a minimum output setting
the ensure a minimum output to enable positioning at low speeds even when
there are extremely few pulses in the error counter.
The amount of movement (i.e., amount of rotation) is input to the high-speed
counter as feedback pulses. During inverter positioning, the present value of
the high-speed counter can be used as an absolute position.
Note
The absolute position will change if the present value of the high-speed
counter is changed or the high-speed counter is reset.
Item
Applicable inverters
Applicable motors
Number of position-
ing ports and
response frequency
Inverter command
output method
Present value coor-
dinate system
Present value range
Output modes
Acceleration/decel-
eration control
Pulse frequency
Error counter
present value
PLS2
instruction
Inverter that receives frequency commands from an analog
input or via Modbus-RTU communications. (Control method:
V/f control, vector control, etc.)
Depends on the inverter (e.g., squirrel-cage inductive motor)
Two ports at 100 kHz (J models: 20kHz) (within the speed
command range of the pulse output instructions)
Modbus-RTU communications commands or analog output
(from ladder program)
With origin: Absolute coordinate system
Without origin: Relative coordinate system
32 bits: 8000 000 to 7FFF FFFF hex (range of position com-
mand values and present values for pulse output instructions)
Continuous output (Number of pulses not specified.)
Independent mode (Number of pulses specified.)
Trapezoidal or S-curve acceleration/deceleration
Section 5-3
Motor shaft
turned manually.
Error counter
error occurs.
Specification