The CycleFlo has a built-in test program that allows for dynamic testing of all internal and external components.
Once activated, the self-test mode will do the following continuously until the test mode is de-activated:
• All display digits count from 0-9 in unison. This is used to determine any of the displays are faulty.
Replace the display board If segments of the display fail to activate during the self test.
• Each of the 5 front panel buttons activates a decimal point on the LED displays. Replace the
display board if a button fails to activate a decimal point.
• Closing the REMOTE RUN contact activates the AIR SUPPLY VALVE signal and cycles the
solenoid valves at the CPM rate set by SW1-1,2,3,4. Follow the trouble shooting guide on page
10 if either fails to operate.
Position SW1-7 to the ON position to activate the self-test mode. Position SW1-7 to the OFF position to de-
activate the self-test mode.
12
Self-Test Mode
During this test the solenoid valves
may be activated.This will activate a
connected pump. To prevent
inadvertent pumping, disconnect the
air supply to the solenoid valves or
remove the air lines to the pump.
309003