Additional Fittings; Valve Accessories - Samson EB 8015 EN Mounting And Operating Instructions

Table of Contents

Advertisement

Design and principle of operation

3.2 Additional fittings

Strainers
We recommend installing a SAMSON
strainer upstream of the valve. It prevents sol-
id particles in the process medium from
damaging the valve.
Bypass and shut-off valves
We recommend installing a shut-off valve
both upstream of the strainer and down-
stream of the valve and installing a bypass
line. The bypass ensures that the plant does
not need to be shut down for service and re-
pair work on the valve.
Insulation
Control valves can be insulated to reduce
heat energy transfer.
Refer to the instructions in the 'Installation'
chapter.
Test connection
Versions with bellows seal fitted with a test
connection (G 
) at the top flange allow the
1
/
8
sealing ability of the bellows to be moni-
tored.
Particularly for liquids and vapors, we rec-
ommend installing a suitable leakage indica-
tor (e.g. a contact pressure gauge, an outlet
to an open vessel or an inspection glass).
Safety guard
For operating conditions that require in-
creased safety (e.g. in cases where the valve
is freely accessible to untrained staff), a safe-
ty guard must be installed to rule out a crush
hazard arising from moving parts (actuator
3-4
and plug stem). Plant operators are responsi-
ble for deciding whether a guard is to be
used. The decision is based on the risk posed
by the plant and its operating conditions.
Noise emissions
Trims with flow dividers can be used to re-
duce noise emission (see u T 8081).

3.3 Valve accessories

Information Sheet u T 8350
EB 8015 EN