Fluidwell D Series User Manual

Multi-purpose indicator input loop powered, signal input: 4-20 ma sensor signal, options: intrinsically safe backlight
Hide thumbs Also See for D Series:
Table of Contents

Advertisement

Quick Links

User Manual
D490-A-PL
MULTI-PURPOSE INDICATOR
INPUT LOOP POWERED
Signal input:
4-20 mA sensor signal
Options:
intrinsically safe
backlight
D-Series - Panel mounted indicators
More info: www.fluidwell.com/dseries

Advertisement

Table of Contents
loading

Summary of Contents for Fluidwell D Series

  • Page 1 User Manual D490-A-PL MULTI-PURPOSE INDICATOR INPUT LOOP POWERED Signal input: 4-20 mA sensor signal Options: intrinsically safe backlight D-Series - Panel mounted indicators More info: www.fluidwell.com/dseries...
  • Page 2: Table Of Contents

    User Manual D490-A-PL TABLE OF CONTENTS ABOUT THIS MANUAL......................How to use this manual ....................Use of pictograms ......................Warranty and technical support ..................Model Reference ......................SAFETY ............................ Personal safety ....................... End-user responsibilities....................Potential equipment damage ..................Disposal of electronic waste ................... INTRODUCTION........................
  • Page 3 D490-A-PL User Manual Terminal connections hazardous area applications............26 Configuration example Intrinsically Safe applications............. 27 7.4.1 D490-A-PL-XI-ZB - Ex ia I/IIC/IIIC .................. 27 MAINTENANCE........................28 General directions......................28 Instructions for repair ...................... 28 Skip-this-node ......................... 000 APPENDIX A - TECHNICAL SPECIFICATION ................29 General ...........................
  • Page 4: About This Manual

    ● incorrect functioning of the unit or connected instruments. A note informs you of important information. WARRANTY AND TECHNICAL SUPPORT For warranty and technical support on your Fluidwell products, visit our internet site www.fluidwell.com or contact us at support@fluidwell.com. MODEL REFERENCE Hardware version: 03.04.xx...
  • Page 5: Safety

    D490-A-PL User Manual SAFETY PERSONAL SAFETY ● Risk of electric shock: Only open the unit if all leads are free of potential electrical energy. ● Immediately inform the person responsible for the installation if you disagree with the safety precautions or if you detect errors or danger. ●...
  • Page 6: Introduction

    User Manual D490-A-PL INTRODUCTION SYSTEM DESCRIPTION The multi-purpose indicator model D490-A-PL is a microprocessor-driven instrument designed to show the actual process value, such as level, temperature, flow, pressure etc. Fig. 1: The D490 This manual describes the daily use, configuration and installation of the D490-A-PL with analog 4-20 mA input from a sensor, and its available options.
  • Page 7: Installation Example

    D490-A-PL User Manual INSTALLATION EXAMPLE Following parts can be recognized in below installation example. Fig. 3: Installation example D490-A-PL 1. Front cover 3. Label 5. Keys 7. Clamp 2. Display 4. Back side cover 6. Mounting panel FW_D490-A-PL_M_v0501-01_EN Page 7...
  • Page 8: Operation

    User Manual D490-A-PL OPERATION This unit may only be operated by authorized and trained personnel who have read and understood this manual, particularly Section 2: Safety [»5] INTRODUCTION This chapter describes the daily use and operation of the D490-A-PL. For this, the D-Series is equipped with a control panel that provides the operator with various functions, information and operating modes.
  • Page 9: Backlight (Type Zb)

    D490-A-PL User Manual Fig. 4: Example of display information during process 4.2.2 BACKLIGHT (TYPE ZB) The D490-A-PL with Type ZB is equipped with a backlight to illuminate the display for improved readability. DISPLAYED INFORMATION 4.3.1 PROCESS VALUE The main display shows the actual process value, as configured in SETUP- mode ( SETUP 1: DISPLAY The configured unit is indicated on the bottom line of the display.
  • Page 10: Configuration

    User Manual D490-A-PL CONFIGURATION INTRODUCTION This chapter describes how technicians can use configuration settings to configure the D-Series for optimal functionality. Configuration of the D490-A-PL can be done in SETUP mode, using the front keys. CONFIGURING USING SETUP MODE For an overview of Operating modes, see Section 4.1.1: Operating modes [»8] Changing settings may influence current operation In SETUP mode the unit remains fully operational.
  • Page 11: Changing Configuration Settings

    D490-A-PL User Manual 5.2.3 CHANGING CONFIGURATION SETTINGS A menu item either contains a value (a number with optionally a decimal point and sign, e.g. -123.45) or a selection list (e.g. L – m - USGAL). After a menu item is selected in the SETUP menu, a new value can be programmed by performing the following steps.
  • Page 12: Setup Menu Overview

    User Manual D490-A-PL SETUP MENU OVERVIEW DISPLAY DEFAULT UNIT mL - L - nL- M3 - nM3 - mg - g - kg - ton - gal - sgal - igal - lb - bbl - cf - scf - p - rev - °C - °F - K - % - m - mm - cm - mtr - inch - ft - psi - mbar - bar - barg - mmwk - mmwc - cmwk - cmwc - mwk - mwc - inwc - ftwc - Ph - mV - no unit TIME UNIT...
  • Page 13: Menu 2: Sensor

    D490-A-PL User Manual DISPLAY UNIT Determines the measurement unit for the displayed process value. The following can be selected: mL - L - nL- M3 - nM3 - mg - g - kg - ton - gal - sgal - igal - lb - bbl - cf - scf - p - rev - °C - °F - K - % - m - mm - cm - mtr - inch - ft - psi - mbar - bar - barg - mmwk - mmwc - cmwk - cmwc - mwk - mwc - inwc - ftwc - Ph - mV - no unit...
  • Page 14 User Manual D490-A-PL SENSOR FILTER The analog output signal of a sensor mirrors the actual process value. This signal is sampled several times per second by the D490-A-PL. Consequently, random and/or fast changes in sensor signal may lead to instable displayed process values. With the help of the filter setting a stable and accurate reading can be obtained.
  • Page 15: Menu 3: Others

    D490-A-PL User Manual 5.4.3 MENU 3: OTHERS OTHERS TYPE / MODEL Provides important information on your product. This information may be SOFTWARE VERSION required for maintenance or support. SERIAL NUMBER PASS CODE All SETUP values can be password protected. A four-digit password can be programmed, for example 1234. To disable password protection, enter four zeros (0000).
  • Page 16: Installation

    User Manual D490-A-PL INSTALLATION ● Mounting, electrical installation, start-up and maintenance of this instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ●...
  • Page 17: Handling The D490-A-Pl Enclosure

    D490-A-PL User Manual HANDLING THE D490-A-PL ENCLOSURE 6.2.1 IDENTIFICATION The D490-A-PL can be supplied as suitable for Safe Area or Hazardous Area. Suitability for Intrinsic Safety is indicated in the model Type XI. Refer to for identification and installation labels Section 7: Intrinsically safe applications [»23] for Intrinsically Safe applications.
  • Page 18: Mechanical Installation

    User Manual D490-A-PL MECHANICAL INSTALLATION 6.3.1 MECHANICAL DIMENSIONS 144 mm (5.67") 10.2 mm (0.4") 15.6 mm (0.61") 138 mm (5.43") 55.3 mm (2.18") Fig. 7: Mechanical dimensions 6.3.2 MOUNTING THE D-SERIES The D-Series unit is mounted by placing it in an opening in a panel or cabinet (see Section 6.3.1: ) and securing it.
  • Page 19: Electrical Installation

    D490-A-PL User Manual Fig. 8: Installation of the D490-A-PL in panel or cabinet ELECTRICAL INSTALLATION Hazardous area installations The following chapter gives general information regarding the electrical installation of the D490-A-PL. gives additional specific information Section 7: Intrinsically safe applications [»23] regarding intrinsically safe installation and has priority over the information given in this chapter.
  • Page 20: Field Wiring Connections

    User Manual D490-A-PL Fig. 9: Examples of ground connection to the front panel. 6.4.3 FIELD WIRING CONNECTIONS ● Do ground the aluminum / stainless steel enclosure as indicated in Section 6.4.2: Earth/ground . It is the responsibility of the installer to install, connect and test the ground connections [»19] connections in accordance with the local and (inter)national Rules and Regulations.
  • Page 21: Terminal 1: Ground

    D490-A-PL User Manual The following terminal connectors are available on the D490-A-PL when supplied with Type ZB. POWER SUPPLY SENSOR CURRENT SHIELDING GROUND BACKLIGHT LINK SIGNAL INPUT LOOP LINK 4-20 mA ZB 20-30 V DC Fig. 10: Overview of terminal connectors - Type ZB 6.5.1 TERMINAL 1: GROUND Terminal 1 can be used for grounding a metal front cover (see...
  • Page 22: Terminals 9-10: Backlight Power Supply - Type Zb

    User Manual D490-A-PL 6.5.3 TERMINALS 9-10: BACKLIGHT POWER SUPPLY - TYPE ZB To power the optional backlight, a voltage from 20 to 30 V must be connected to the display. The maximum current will be 30mA. Connect the “-“ to terminal 9 and the “+“ to terminal 10. 20 - 30 V DC Fig. 12: Terminals 9-10: Backlight power - Type ZB...
  • Page 23: Intrinsically Safe Applications

    D490-A-PL User Manual INTRINSICALLY SAFE APPLICATIONS IDENTIFICATION The D490-A-PL can be supplied as suitable for Safe Area or Hazardous Area. Suitability for Intrinsic Safety is indicated in the model Type XI. If Type XI is not indicated your unit is not suitable for Intrinsically Safe applications! Identification label To identify your D490-A-PL device, all enclosures have a weatherproof identification label placed at the backside of the product.
  • Page 24: Installations Based On Csa Certificate

    User Manual D490-A-PL ● Certificates and related documents are available on our website or from your distributor. ● Carefully study the configuration examples with wiring diagrams per classification in the following paragraphs. 7.2.1 INSTALLATIONS BASED ON CSA CERTIFICATE Installation instructions ●...
  • Page 25: Electrical Data - Control Drawing

    D490-A-PL User Manual 7.2.2 ELECTRICAL DATA - CONTROL DRAWING Control Drawing CD1104.11 SAFE AREA HAZARDOUS AREA TERMINAL CONNECTORS D400 / F400-series I.S. Certified Barrier POWER-SUPPLY Uo=28V to backlight Io=200mA Po=0.96W Optional hazardous location apparatus An appoved Optional hazardous associated location apparatus apparatus Optional hazardous location apparatus...
  • Page 26: Installations Based On Atex Or Iecex Certificate

    User Manual D490-A-PL 7.2.3 INSTALLATIONS BASED ON ATEX OR IECEX CERTIFICATE Installation instructions ● For installation under ATEX directive: this Intrinsically Safe device must be installed in accordance with ATEX directive 2014/34/EU and product certificate KEMA 03ATEX1075 X. ● For installation under IECEx scheme: this Intrinsically Safe device must be installed in accordance with product certificate IECEx KEM 08.0007X.
  • Page 27: Configuration Example Intrinsically Safe Applications

    D490-A-PL User Manual The following terminal connectors are available on the D490-A-PL-XI when supplied with Type ZB. POWER SUPPLY SENSOR CURRENT SHIELDING GROUND BACKLIGHT LINK SIGNAL INPUT LOOP LINK 4-20 mA ZB 20-30 V DC Fig. 14: Overview of terminal connectors - Type XI-ZB All electrical connections made to the terminals of the intrinsically safe product (Type XI) must follow the instructions and safety parameters as given in the product certificate.
  • Page 28: Maintenance

    User Manual D490-A-PL MAINTENANCE GENERAL DIRECTIONS ● Mounting, electrical installation, start-up and maintenance of this instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ●...
  • Page 29: Appendix A - Technical Specification

    D490-A-PL User Manual APPENDIX A - TECHNICAL SPECIFICATION GENERAL DISPLAY Type High intensity reflective numeric and alphanumeric LCD, UV-resistant Digits 5½ with height 26mm (1”) and 11 with height 8mm (0.31”). Various symbols and measuring units. Dimensions 90 x 40 mm (3.5” x 1.6”) Refresh rate 1/sec Piegraph...
  • Page 30: Input

    User Manual D490-A-PL HAZARDOUS AREA (TYPE XI) Intrinsically safe ATEX appr. KEMA 03ATEX1075 X IECEx appr. IECEx KEM 08.0007X Type XI II 1 G Ex ia IIC T4 Ga Ex ia IIC T4 Ga II 1 D Ex ia IIIC T 100ºC Da Ex ia IIIC T 100ºC Da...
  • Page 31: Appendix B - Troubleshooting

    D490-A-PL User Manual APPENDIX B - TROUBLESHOOTING Table 1 lists and describes how to troubleshoot problems that can occur when installing or operating the D490-A-PL. Table 2 lists internal alarm codes and conditions signaled by a blinking ALARM flag on the display ).
  • Page 32: Appendix C - Legal Information

    Fluidwell D4- and F4- Series indicators he , February 2022 We, Fluidwell BV, declare under our sole responsibility that the D4- and F4- Series indicators are designed and will operate conform the following applicable European Directives and Harmonised Standards, when installed and operated according to the related manuals:...
  • Page 33 D490-A-PL User Manual LIST OF CONFIGURATION SETTINGS SETTING DEFAULT DATE: DATE: DISPLAY UNIT TIME UNIT DECIMALS OFFSET SPAN 1600 DIRECTION normal CURRENT PERCENTAGE BARGRAPH SENSOR FORMULA interpolation FILTER 01 (off) CALIBRATE LOW factory CALIBRATE HIGH factory OTHERS TYPE / MODEL D490-A-PL SOFTWARE VERSION 03.xx.xx...
  • Page 34 User Manual D490-A-PL NOTES Page 34 FW_D490-A-PL_M_v0501-01_EN...
  • Page 35 D490-A-PL User Manual FW_D490-A-PL_M_v0501-01_EN Page 35...
  • Page 36 Fluidwell bv P.O. Box 6 Voltaweg 23 Website: www.fluidwell.com 5460 AA Veghel 5466 AZ Veghel Find your nearest representative: www.fluidwell.com/representatives the Netherlands the Netherlands © Copyright 2024 - FW_D490-A-PL_M_v0501-01_EN...