York ZT SERIES Technical Manual

York ZT SERIES Technical Manual

3 - 12.5 ton packaged rooftop units
Hide thumbs Also See for ZT SERIES:
Table of Contents

Advertisement

TECHNICAL GUIDE
R-410A
ZT SERIES
3 - 12.5 TON
60 Hertz
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

Description

Ultra-High Efficiency

®
®
YORK
Predator
units are convertible single packages with a
common footprint cabinet and common roof curb for all 3
through 12.5 ton models. The units are designed for light
commercial applications and can be easily installed on a roof
curb, slab, or frame.
®
All Predator
units are self-contained and assembled on rigid
full perimeter base rails allowing for 3-way forklift access and
overhead rigging. Every unit is completely charged, wired,
piped, and tested at the factory to provide a quick and easy field
installation.
®
Predator
units in all tonnage sizes are convertible between
side airflow and down airflow, with corresponding economizer if
you require the economizer option.
®
Predator
units are available in the following configurations:
cooling only, cooling with electric heat, and cooling with gas
heat. Electric heaters are available as factory-installed options
or field-installed accessories.
All units meet ASHRAE 90.1 single-zone variable supply air
volume standard. Featuring a variable frequency drive on 3
through 12.5 ton ZT models.
Tested in accordance with:
5167821-YTG-K-1118

Advertisement

Table of Contents
loading

Summary of Contents for York ZT SERIES

  • Page 1 5167821-YTG-K-1118 TECHNICAL GUIDE R-410A Description ZT SERIES Ultra-High Efficiency ® ® YORK Predator units are convertible single packages with a 3 - 12.5 TON common footprint cabinet and common roof curb for all 3 60 Hertz through 12.5 ton models. The units are designed for light commercial applications and can be easily installed on a roof curb, slab, or frame.
  • Page 2: Table Of Contents

    5167821-YTG-K-1118 Table of contents Description ................... . 1 Product highlights .
  • Page 3: Nomenclature

    5167821-YTG-K-1118 Nomenclature ® 3-12.5 Ton York Model Number Nomenclature Z T 037 C A 2 A 1 Product Generation Product Category 1 = First Generation 2 = Second Generation Z = A/C, Single Pkg., R-410A Cabinet Options Product Identifier A = Std Cabinet...
  • Page 4: Component Location

    Slide-out motor and blower assembly for easy adjustment and service 1. Roof curbs in eight-and fourteen-inch heights. Roof curbs to transition from a York Sunline™ footprint to the ZT Series footprint are available as a field-installed accessory. Johnson Controls Ducted Systems...
  • Page 5 5167821-YTG-K-1118 Standard features This section describes the standard features for ultra-high efficiency 3 to 12.5 ton units. Ultra-high efficiency Ultra-high efficiency units reach as high as 17.5 SEER and 14.00 EER for 3 to 5 ton units, and up to 21.2 IEER and 13.1 EER for 6.5 to 12.5 ton units.
  • Page 6 5167821-YTG-K-1118 Toolless hinged panels • Service time is reduced through the use of hinged, toolless panels. The panels provide access to frequently inspected components and areas, including the control box, compressors, filters, indoor motor and blower, and the heating section. The panels are screwed in place at the factory to prevent access by children or other unauthorized persons.
  • Page 7 5167821-YTG-K-1118 Balanced heating ® The Predator two stage gas heating offers ultimate heating comfort with a balance between first and second stage gas ® heating. The first stage of a gas heat Predator unit provides 70% or 75% of the heating capacity for the 3 to 5 ton units. The 6.5 to 12.5 ton units reach 60% heating capacity on the first stage.
  • Page 8 5167821-YTG-K-1118 Low ambient control An integrated low-ambient control allows units to operate in the cooling mode down to 0°F outdoor ambient without additional components or intervention. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.
  • Page 9 5167821-YTG-K-1118 Options and accessories The following options and accessories are available as factory-installed and field-installed options. Options and accessories Factory option Field-installed Non-electrical  Burglar bars   Coil guard  Hail guard  Flue exhaust extension  2-inch only metal filter frame ...
  • Page 10 Factory and field-installed options ® ® line. YORK offers several factory and field-installed options for the Predator Down flow and end return economizers with barometric relief and fresh air hood Factory or field-installed option All units offer a variety of optional factory-installed or field-installed down flow economizers that are shipped, installed and wired with low leak dampers designed to meet ASHRAE 90.1, AMCA 511 Class 1A damper, and the International Energy...
  • Page 11 5167821-YTG-K-1118 Low NOx option Factory or field-installed option For units with gas furnaces in locations where codes require that the Oxides of Nitrogen emissions from the furnace be below 40 Nano grams per joule. The low NOx option is available for 3 to 5 ton units only. Stainless steel drain pan Factory option An optional rust-proof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments.
  • Page 12 5167821-YTG-K-1118 Hail guard Field-installed option This kit includes a sloped hood that is installed over the outside condenser coil and prevents damage to the coil fins from hail strikes. Dirty filter switch Factory or field-installed option This option/kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters.
  • Page 13 5167821-YTG-K-1118 Control options The following sections describe the control options. Smart Equipment™ control with communication option The communication option for the Smart Equipment™ control is a factory installed add-on card to expand the capabilities with a gateway to BACnet MS/TP (programmable to Modbus or N2 protocols). Novar®...
  • Page 14: Guide Specifications

    General ® YORK® Predator units are convertible single packages with a common footprint cabinet and common roof curb for all 3 through 12.5 ton models. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or ®...
  • Page 15 5167821-YTG-K-1118 Refrigerant Circuit and Refrigerant Safety Components shall include: a. Independent fixed-orifice or thermally operated expansion devices. b. Solid core filter drier/strainer to eliminate any moisture or foreign matter. c. Accessible service gage connections on both suction and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge.
  • Page 16 5167821-YTG-K-1118 • Dry bulb automatic economizer - Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall be designed to meet ASHRAE 90.1, AMCA 511 Class 1A damper, and the International Energy Conservation Code (IECC) certification requirements by achieving leakage rates of 3 CFM/sq.
  • Page 17 5167821-YTG-K-1118 Physical data ZT037-061 physical data Models Component ZT037 ZT049 ZT061 Nominal tonnage AHRI cooling performance Gross capacity @ AHRI A point (MBh) 38000 51200 61600 AHRI net capacity (MBh) 37000 50000 60000 13.05 14.0 13.00 SEER (208/230 & 460V) 17.0 17.5 16.3...
  • Page 18: Physical Data

    5167821-YTG-K-1118 ZT037-061 physical data (continued) Models Component ZT037 ZT049 ZT061 Nominal tonnage Condenser fan data Quantity of fans Fan diameter (inches) Type Prop Prop Prop Drive type Direct ECM Direct ECM Direct ECM Quantity of motors Motor HP each No. of speeds Var.
  • Page 19 5167821-YTG-K-1118 ZT078-150 physical data Models Component ZT078 ZT090 ZT102 ZT120 ZT150 Nominal tonnage 12.5 AHRI cooling performance Gross capacity @ AHRI A point (Mbh) 76000 91500 104000 121000 147500 AHRI net capacity (Mbh) 74000 89000 101000 117000 142000 12.4 /12.6 13.1 13.1 13.1...
  • Page 20 5167821-YTG-K-1118 ZT078-150 physical data (continued) Models Component ZT078 ZT090 ZT102 ZT120 ZT150 Nominal tonnage 12.5 Condenser fan data Quantity of fans Fan diameter (inches) Type Prop Prop Prop Prop Prop Drive type Direct Direct Direct Direct Direct Quantity of motors Motor HP each No.
  • Page 21 5167821-YTG-K-1118 ZT037-150 unit limitations Unit limitations Size Model Unit voltage Applied voltage Outdoor DB temp. (tons) Minimum Maximum Maximum (°F) 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 460-3-60 575-3-60 208/230-3-60 (6.5) 460-3-60 208/230-3-60 (7.5) 460-3-60 208/230-3-60 (8.5) 460-3-60 208/230-3-60 (10) 460-3-60 208/230-3-60 (12.5)
  • Page 22: Capacity Performance

    5167821-YTG-K-1118 Capacity performance ZT037-150 cooling capacities ZT037 high speed compressor (3.0 ton) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW)
  • Page 23 5167821-YTG-K-1118 ZT037 high speed compressor (3.0 ton) (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 24 5167821-YTG-K-1118 ZT037 low speed compressor (3.0 ton) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 25 5167821-YTG-K-1118 ZT037 low speed compressor (3.0 ton) (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 26 5167821-YTG-K-1118 ZT049 high speed compressor (4.0 ton) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 27 5167821-YTG-K-1118 ZT049 high speed compressor (4.0 ton) (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 28 5167821-YTG-K-1118 ZT049 low speed compressor (4.0 ton) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 29 5167821-YTG-K-1118 ZT049 low speed compressor (4.0 ton) (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 30 5167821-YTG-K-1118 ZT061 high speed compressor (5.0 ton) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 31 5167821-YTG-K-1118 ZT061 high speed compressor (5.0 ton) (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 32 5167821-YTG-K-1118 ZT061 low speed compressor (5.0 ton) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 33 5167821-YTG-K-1118 ZT061 low speed compressor (5.0 ton) (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 34 5167821-YTG-K-1118 ZT078 (6.5 ton) 1st stage cooling Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 35 5167821-YTG-K-1118 ZT078 (6.5 ton) 1st stage cooling (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 36 5167821-YTG-K-1118 ZT078 (6.5 ton) 2nd stage cooling Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 37 5167821-YTG-K-1118 ZT078 (6.5 ton) 2nd stage cooling (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 38 5167821-YTG-K-1118 ZT078 (6.5 ton) 3rd stage cooling Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 39 5167821-YTG-K-1118 ZT078 (6.5 ton) 3rd stage cooling (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 40 5167821-YTG-K-1118 ZT090 (7.5 ton) 1st stage cooling Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 41 5167821-YTG-K-1118 ZT090 (7.5 ton) 1st stage cooling (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 42 5167821-YTG-K-1118 ZT090 (7.5 ton) 2nd stage cooling Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 43 5167821-YTG-K-1118 ZT090 (7.5 ton) 2nd stage cooling (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 44 5167821-YTG-K-1118 ZT090 (7.5 ton) 3rd stage cooling Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 45 5167821-YTG-K-1118 ZT090 (7.5 ton) 3rd stage cooling (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 46 5167821-YTG-K-1118 ZT102 (8.5 ton) 1st stage cooling Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 47 5167821-YTG-K-1118 ZT102 (8.5 ton) 1st stage cooling (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 48 5167821-YTG-K-1118 ZT102 (8.5 ton) 2nd stage cooling Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 49 5167821-YTG-K-1118 ZT102 (8.5 ton) 2nd stage cooling (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 50 5167821-YTG-K-1118 ZT102 (8.5 ton) 3rd stage cooling Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 51 5167821-YTG-K-1118 ZT102 (8.5 ton) 3rd stage cooling (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 52 5167821-YTG-K-1118 ZT120 (10 ton) 1st stage cooling Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 53 5167821-YTG-K-1118 ZT120 (10 ton) 1st stage cooling (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 54 5167821-YTG-K-1118 ZT120 (10 ton) 2nd stage cooling Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 55 5167821-YTG-K-1118 ZT120 (10 ton) 2nd stage cooling (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 56 5167821-YTG-K-1118 ZT120 (10 ton) 3rd stage cooling Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 57 5167821-YTG-K-1118 ZT120 (10 ton) 3rd stage cooling (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 58 5167821-YTG-K-1118 ZT150 (12.5 ton) 1st stage cooling Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 59 5167821-YTG-K-1118 ZT150 (12.5 ton) 1st stage cooling (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 60 5167821-YTG-K-1118 ZT150 (12.5 ton) 2nd stage cooling Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 61 5167821-YTG-K-1118 ZT150 (12.5 ton) 2nd stage cooling (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 62 5167821-YTG-K-1118 ZT150 (12.5 ton) 3rd stage cooling Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh)
  • Page 63 5167821-YTG-K-1118 ZT150 (12.5 ton) 3rd stage cooling (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh)
  • Page 64 5167821-YTG-K-1118 ZT078 (6.5 ton) reheat Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh) (°F) 35°F...
  • Page 65 5167821-YTG-K-1118 ZT078 (6.5 ton) reheat (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh) (°F)
  • Page 66 5167821-YTG-K-1118 ZT090 (7.5 ton) reheat Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh) (°F) 35°F...
  • Page 67 5167821-YTG-K-1118 ZT090 (7.5 ton) reheat (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh) (°F)
  • Page 68 5167821-YTG-K-1118 ZT102 (8.5 ton) reheat Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh) (°F) 35°F...
  • Page 69 5167821-YTG-K-1118 ZT102 (8.5 ton) reheat (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh) (°F)
  • Page 70 5167821-YTG-K-1118 ZT120 (10 ton) reheat Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh) (°F) 35°F...
  • Page 71 5167821-YTG-K-1118 ZT120 (10 ton) reheat (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh) (°F)
  • Page 72 5167821-YTG-K-1118 ZT150 (12.5 ton) reheat Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh) (°F) 35°F...
  • Page 73 5167821-YTG-K-1118 ZT150 (12.5 ton) reheat (continued) Temperature of air on condenser coil Air on evaporator coil Sensible capacity (MBh) Sensible capacity (MBh) Total Total Total input Total input capacity Return dry bulb (°F) capacity Return dry bulb (°F) (kW) (kW) (MBh) (MBh) (°F)
  • Page 74 5167821-YTG-K-1118 Drive selection Determine side or bottom supply duct application. Determine desired airflow. Calculate or measure the amount of external static pressure. With the operating point determined from steps 1, 2, and 3, locate this point on the appropriate supply air blower performance table.
  • Page 75 5167821-YTG-K-1118 Altitude and temperature correction for CFM, static pressure, and power Use the information below to assist in the application of the product at altitudes at or exceeding 1000 feet above sea level. The air flow rates listed in the standard blower performance tables are based on standard air at sea level. As the altitude or temperature increases, the density of air decreases.
  • Page 76 5167821-YTG-K-1118 Indoor blower specifications Motor Motor sheave Blower sheave Size Airflow Model Datum dia. Datum dia. Belt (tons) option Eff. Frame Bore (in.) Model Bore (in.) Model (in.) (in.) Std. 1-1/2 1725 0.86 1.15 2.4 - 3.4 1VL40 AK79 H. static 1-1/2 1725 0.86 1.15 2.4 - 3.4...
  • Page 77 5167821-YTG-K-1118 Additional static resistance - ZT037 through 061 Electric heat kW Size Model CFM Cooling only Economizer 4-in. pleated filter (tons) 0.05 -0.05 0.01 0.00 0.00 0.00 0.01 0.01 0.01 1000 0.05 -0.03 0.02 0.00 0.00 0.00 0.02 0.02 0.02 1100 0.04 -0.02...
  • Page 78 5167821-YTG-K-1118 Gas heat minimum supply air Supply air (CFM) Size (tons) Model Heat size Heating Minimum Maximum 2220 2370 1130 1800 2220 2370 1290 2250 2370 1380 2570 1580 2630 1950 3250 (6.5) 1950 3250 2250 3750 (7.5) 2250 3750 2550 4250 (8.5)
  • Page 79 5167821-YTG-K-1118 Airflow performance ZT037-150 side duct application ZT037 (3.0 ton) side duct Available external static pressure - IWG Air flow (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard 1.5 HP and drive High static 1.5 HP and drive 0.24...
  • Page 80 5167821-YTG-K-1118 ZT078 (6.5 ton) side duct Available external static pressure - IWG Air flow (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field supplied drive Standard 1.5 HP and drive High static 2 HP and drive 1800 0.27...
  • Page 81 5167821-YTG-K-1118 ZT102 (8.5 ton) side duct Available external static pressure - IWG Air flow (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field supplied drive Standard 2 HP and drive High static 3 HP and drive 2200 0.39...
  • Page 82 5167821-YTG-K-1118 ZT150 (12.5 ton) side duct Available external static pressure - IWG Air flow (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field supplied drive Standard 3 HP and drive 3200 0.44 0.79...
  • Page 83 5167821-YTG-K-1118 ZT037-150 bottom duct application ZT037 (3.0 ton) bottom duct Available external static pressure - IWG Air flow (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard 1.5 HP and drive High static 1.5 HP and drive 0.26 0.34...
  • Page 84 5167821-YTG-K-1118 ZT078 (6.5 ton) bottom duct Available external static pressure - IWG Air flow (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field supplied drive Standard 1.5 HP and drive High static 2 HP and drive 1800 0.29...
  • Page 85 5167821-YTG-K-1118 ZT120 (10 ton) bottom duct Available external static pressure - IWG Air flow (CFM) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field supplied Standard 2 HP and drive High static 3 HP and drive drive 2600...
  • Page 86 5167821-YTG-K-1118 Sound performance Indoor sound power levels (3 through 5 ton) Indoor sound power levels (horizontal ducted inlet, standard static belt drive) Unit description/model ZT037 / 3 ton / standard static belt drive Test configuration Horizontal (side return) ducted inlet Indoor blower speed (RPM) 612 - 3 turns open equivalent 709 - 1 turn open equivalent...
  • Page 87 5167821-YTG-K-1118 Unit description/model ZT061 / 5 ton / standard static belt drive Test configuration Horizontal (side return) ducted inlet Indoor blower speed (RPM) 814 - 3 turns open equivalent 918 - 1 turn open equivalent External static pressure (IWG) Airflow (CFM) 1700 1950 Blower motor BHP...
  • Page 88 5167821-YTG-K-1118 Unit description/model ZT049 / 4 ton / standard static belt drive Test configuration Horizontal (side supply) ducted discharge Indoor blower speed (RPM) 610 - 3 turns open equivalent 710 - 1 turn open equivalent External static pressure (IWG) Airflow (CFM) Blower motor BHP 0.37 0.42...
  • Page 89 5167821-YTG-K-1118 Indoor sound power levels (vertical ducted inlet, standard static belt drive) Unit description/model ZT037 / 3 ton / standard static belt drive Test configuration Vertical (bottom return) ducted inlet Indoor blower speed (RPM) 609 - 3 turns open equivalent 708 - 1 turn open equivalent External static pressure (IWG) Airflow (CFM)
  • Page 90 5167821-YTG-K-1118 Unit description/model ZT061 / 5 ton / standard static belt drive Test configuration Vertical (bottom return) ducted inlet Indoor blower speed (RPM) 812 - 3 turns open equivalent 915- 1 turn open equivalent External static pressure (IWG) Airflow (CFM) 1575 1800 Blower motor BHP...
  • Page 91 5167821-YTG-K-1118 Unit description/model ZT049 / 4 ton / standard static belt drive Test configuration Vertical (bottom supply) ducted discharge Indoor blower speed (RPM) 609 - 3 turns open equivalent 712 - 1 turn open equivalent External static pressure (IWG) Airflow (CFM) Blower motor BHP 0.32 0.42...
  • Page 92 5167821-YTG-K-1118 Indoor sound power levels (horizontal ducted inlet, high static belt drive) Unit description/model ZT037 / 3 ton / high static belt drive Test configuration Horizontal (side return) ducted inlet Indoor blower speed (RPM) 876 - 4 turns open equivalent 1,064 - 1/2 turn open equivalent 1,190 - 2.5 turns open equivalent External static pressure (IWG)
  • Page 93 5167821-YTG-K-1118 Unit description/model ZT061 / 5 ton / high static belt drive Test configuration Horizontal (side return) ducted inlet Indoor blower speed (RPM) 1,012- 5.5 turns open equivalent 1,134 - 3 turns open equivalent 1,174 - 2 turns open equivalent External static pressure (IWG) Nominal airflow (CFM) 2,000...
  • Page 94 5167821-YTG-K-1118 Unit description/model ZT049 / 4 ton / high static belt drive Test configuration Horizontal (side supply) ducted discharge Indoor blower speed (RPM) 922 - 6 turns open equivalent 1,069 - 4 turns open equivalent 1,165 - 2.5 turns open equivalent External static pressure (IWG) Nominal airflow (CFM) 1,600...
  • Page 95 5167821-YTG-K-1118 Indoor sound power levels (vertical ducted inlet, high static belt drive) Unit description/model ZT037 / 3 ton / high static belt drive Test configuration Vertical (bottom return) ducted inlet Indoor blower speed (RPM) 927 - 3 turns open equivalent 1,085 - 1/2 turn open equivalent 1,190 - 2.5 turns open equivalent External static pressure (IWG)
  • Page 96 5167821-YTG-K-1118 Unit description/model ZT061 / 5 ton / high static belt drive Test configuration Vertical (bottom return) ducted inlet Indoor blower speed (RPM) 1,039 - 5 turns open equivalent 1,143 - 3 turns open equivalent 1,201 - 2 turns open equivalent External static pressure (IWG) Nominal airflow (CFM) 2,000...
  • Page 97 5167821-YTG-K-1118 Unit description/model ZT049 / 4 ton / high static belt drive Test configuration Vertical (bottom supply) ducted discharge Indoor blower speed (RPM) 962 - 5.5 turns open equivalent 1,092 - 3.5 turns open equivalent 1,190 - 2.0 turns open equivalent External static pressure (IWG) Nominal airflow (CFM) 1,600...
  • Page 98 5167821-YTG-K-1118 Indoor sound power levels (6.5 to 12.5 ton units) Indoor sound power levels (vertical ducted discharge) Unit description/model ZT078 Test configuration Vertical (bottom supply) ducted discharge External static pressure (IWG) Nominal airflow (CFM) 2600 2400 2200 2000 Octave band center frequency Full stage cooling operation Full stage cooling operation Full stage cooling operation...
  • Page 99 5167821-YTG-K-1118 Unit description/model ZT102 Test configuration Vertical (bottom supply) ducted discharge External static pressure (IWG) Nominal airflow (CFM) 3400 3200 3000 2800 Octave band center frequency Full stage cooling operation Full stage cooling operation Full stage cooling operation Full stage cooling operation (Hz) (dB) (dB)
  • Page 100 5167821-YTG-K-1118 Unit description/model ZT150 Test configuration Vertical (bottom supply) ducted discharge External static pressure (IWG) Nominal airflow (CFM) 4600 4400 4200 4000 Octave band center frequency Full stage cooling operation Full stage cooling operation Full stage cooling operation Full stage cooling operation (Hz) (dB) (dB)
  • Page 101 5167821-YTG-K-1118 Unit description/model ZT090 Test configuration Horizontal (side supply) ducted discharge External static pressure (IWG) Nominal airflow (CFM) 3000 2800 2600 2400 Octave band center frequency Full stage cooling operation Full stage cooling operation Full stage cooling operation Full stage cooling operation (Hz) (dB) (dB)
  • Page 102 5167821-YTG-K-1118 Unit description/model ZT120 Test configuration Horizontal (side supply) ducted discharge External static pressure (IWG) Nominal airflow (CFM) 4000 3800 3600 3400 Octave band center frequency Full stage cooling operation Full stage cooling operation Full stage cooling operation Full stage cooling operation (Hz) (dB) (dB)
  • Page 103 5167821-YTG-K-1118 Outdoor sound power levels ZT037-150 Octave band centerline frequency (Hz) Sound rating Size (tons) Model dB (A) 1000 2000 4000 8000 78.5 78.5 74.0 72.0 68.5 65.0 60.5 53.0 83.0 78.5 74.5 72.0 69.5 63.0 58.0 55.5 80.0 78.0 74.5 72.5 69.0...
  • Page 104 5167821-YTG-K-1118 Electrical data ZT037-150 standard indoor blower - without powered convenience outlet Compressors Max fuse OD fan Supply Max fuse (each) motors blower conv Electric heat option breaker Size with pwr breaker Volt (each) motor motor outlet size with (tons) (amps) size pwr exh...
  • Page 105 5167821-YTG-K-1118 ZT037-150 standard indoor blower - without powered convenience outlet (continued) Compressors OD fan Supply Max fuse Max fuse (each) motors blower conv Electric heat option breaker Size with pwr breaker Volt (each) motor motor outlet size with (tons) (amps) size pwr exh (amps)
  • Page 106 5167821-YTG-K-1118 ZT037-150 standard indoor blower - without powered convenience outlet (continued) Compressors Max fuse OD fan Supply Max fuse (each) breaker motors blower conv Electric heat option Size with pwr breaker Volt (each) motor motor outlet size with (tons) (amps) size pwr exh (amps)
  • Page 107 5167821-YTG-K-1118 ZT037-150 high static indoor blower - without powered convenience outlet Compressors OD fan Supply Max fuse Max fuse (each) motors blower conv Electric heat option breaker Size with pwr breaker (each) motor motor outlet Volt size with (tons) (amps) size pwr exh (amps)
  • Page 108 5167821-YTG-K-1118 ZT037-150 high static indoor blower - without powered convenience outlet (continued) Compressors OD fan Supply Max fuse Max fuse (each) motors blower conv Electric heat option breaker Size with pwr breaker (each) motor motor outlet Volt size with (tons) (amps) size pwr exh...
  • Page 109 5167821-YTG-K-1118 ZT037-150 high static indoor blower - without powered convenience outlet (continued) Compressors OD fan Supply Max fuse Max fuse (each) motors blower conv Electric heat option breaker Size with pwr breaker (each) motor motor outlet Volt size with (tons) (amps) size pwr exh...
  • Page 110 5167821-YTG-K-1118 ZT037-150 standard indoor blower - with powered convenience outlet Compressors OD fan Supply Max fuse (each) motors blower conv Electric heat option fuse breaker Size with pwr (each) motor motor outlet Volt breaker size with (tons) (amps) size pwr exh (amps) Model Stages Amps...
  • Page 111 5167821-YTG-K-1118 ZT037-150 standard indoor blower - with powered convenience outlet (continued) Compressors OD fan Supply Max fuse (each) motors blower conv Electric heat option fuse breaker Size with pwr (each) motor motor outlet Volt breaker size with (tons) (amps) size pwr exh Model Stages Amps...
  • Page 112 5167821-YTG-K-1118 ZT037-150 standard indoor blower - with powered convenience outlet (continued) Compressors OD fan Supply Max fuse (each) motors blower conv Electric heat option fuse breaker Size with pwr (each) motor motor outlet Volt breaker size with (tons) (amps) size pwr exh (amps) Model...
  • Page 113 5167821-YTG-K-1118 ZT037-150 high static indoor blower - with powered convenience outlet Compressors OD fan Supply Max fuse Max fuse (each) motors blower conv Electric heat option breaker Size with pwr breaker (each) motor motor outlet Volt size with (tons) (amps) size pwr exh (amps)
  • Page 114 5167821-YTG-K-1118 ZT037-150 high static indoor blower - with powered convenience outlet (continued) Compressors OD fan Supply Max fuse Max fuse (each) motors blower conv Electric heat option breaker Size with pwr breaker (each) motor motor outlet Volt size with (tons) (amps) size pwr exh...
  • Page 115 5167821-YTG-K-1118 ZT037-150 high static indoor blower - with powered convenience outlet (continued) Compressors OD fan Supply Max fuse Max fuse (each) motors blower conv Electric heat option breaker Size with pwr breaker (each) motor motor outlet Volt size with (tons) (amps) size pwr exh...
  • Page 116 5167821-YTG-K-1118 Typical wiring diagrams ZT037-150 typical wiring diagrams Typical ZT037-061 cooling unit with gas heat 208/230 volt wiring diagram Johnson Controls Ducted Systems...
  • Page 117 5167821-YTG-K-1118 Typical ZT037-061 cooling unit with gas heat 208/230 volt unit (options) Johnson Controls Ducted Systems...
  • Page 118 5167821-YTG-K-1118 Typical ZT037-061 cooling unit with gas heat 460/575 volt wiring diagram Johnson Controls Ducted Systems...
  • Page 119 5167821-YTG-K-1118 Typical ZT037-061 cooling unit with gas heat 460/575 volt unit (options) Johnson Controls Ducted Systems...
  • Page 120 5167821-YTG-K-1118 Typical ZT037-061 cooling unit with/without electric heat 208/230 volt wiring diagram Johnson Controls Ducted Systems...
  • Page 121 5167821-YTG-K-1118 Typical ZT037-061 cooling unit with/without electric heat 208/230 volt unit Johnson Controls Ducted Systems...
  • Page 122 5167821-YTG-K-1118 Typical ZT037-061 cooling unit with/without electric heat 460/575 volt wiring diagram Johnson Controls Ducted Systems...
  • Page 123 5167821-YTG-K-1118 Typical ZT037-061 cooling unit with/without electric heat 460/575 volt unit (options) Johnson Controls Ducted Systems...
  • Page 124 5167821-YTG-K-1118 Typical ZT078-150 cooling unit with gas heat 208/230 volt wiring diagram Johnson Controls Ducted Systems...
  • Page 125 5167821-YTG-K-1118 Typical ZT078-150 cooling unit with gas heat 208/230 volt unit (options) Johnson Controls Ducted Systems...
  • Page 126 5167821-YTG-K-1118 Typical ZT078-150 cooling unit with gas heat 460 volt wiring diagram Johnson Controls Ducted Systems...
  • Page 127 5167821-YTG-K-1118 Typical ZT078-150 cooling unit with gas heat 460 volt unit (options) Johnson Controls Ducted Systems...
  • Page 128 5167821-YTG-K-1118 Typical ZT078-150 cooling unit with/without electric heat wiring diagram Johnson Controls Ducted Systems...
  • Page 129 5167821-YTG-K-1118 Typical ZT078-150 cooling unit with/without electric heat unit (options) Johnson Controls Ducted Systems...
  • Page 130 5167821-YTG-K-1118 BAS controls typical wiring diagrams Typical SURVEYOR BAS control wiring diagram Johnson Controls Ducted Systems...
  • Page 131 5167821-YTG-K-1118 Typical CPC BAS control wiring diagram Johnson Controls Ducted Systems...
  • Page 132 5167821-YTG-K-1118 Typical HONEYWELL BAS control wiring diagram Johnson Controls Ducted Systems...
  • Page 133 5167821-YTG-K-1118 Typical NOVAR BAS control wiring diagram Johnson Controls Ducted Systems...
  • Page 134 5167821-YTG-K-1118 Weights and dimensions ZT037-150 unit weights Unit 4 point load weight Unit 6 point load weight FRONT FRONT LEFT LEFT FRONT LEFT ZT037-150 standard unit weights Size Weight (lbs.) Center of gravity 4 point load location (lbs.) 6 point load location (lbs.) Model (tons) Shipping Operating...
  • Page 135 5167821-YTG-K-1118 ZT078-150 with MagnaDry option unit weights Weight (lbs.) Center of gravity 4 point load location (lbs.) 6 point load location (lbs.) Size Model (tons) Shipping Operating 1293 1288 47.25 24.00 (6.5) 1298 1293 48.25 25.34 (7.5) 1309 1304 47.25 24.75 (8.5) 1486...
  • Page 136 5167821-YTG-K-1118 ZT037-150 unit dimensions ZT037 - 061 29.69 15.25 15.38 59.00 15.38 2X Ø 24.38 SEE DETAIL A FOR GAS INLET 11.38 SEE DETAIL B 59.00 4.19 FOR DRAIN LOCATION LEFT 27.31 21.19 89.00 FRONT ZT037-061 unit physical dimensions Dimension (in.) Unit model number ZT037, 049, 061 22 1/8...
  • Page 137 5167821-YTG-K-1118 ZT078 - ZT102 45.64 14.92 4X Ø 24.38 14.92 58.09 14.92 29.95 30.11 SEE DETAIL A FOR GAS INLET 11.38 SEE DETAIL B 59.00 4.19 FOR DRAIN LOCATION 27.31 LEFT 21.19 89.00 FRONT ZT078-102 unit physical dimensions Dimension (in.) Unit model number 078, 090 and 102 22 1/8...
  • Page 138 5167821-YTG-K-1118 ZT120 - ZT150 28.86 29.66 44.09 15.23 14.85 29.03 29.03 14.85 Ø 24.58 TYP. 4 PL. 15.23 See detail A for gas inlet 11 3/8 See detail B for drain location 21 3/16 LEFT 4 3/16 FRONT 27 5/16 ZT120-150 unit physical dimensions Dimension (in.) Unit model number...
  • Page 139 5167821-YTG-K-1118 Detail A 3.184 3.184 Gas Pipe Inlet Gas Pipe Inlet Ø 2.000 Ø 2.000 Gas Exhaust Vent Gas Exhaust Vent Ø 3.126 Ø 3.126 17.541 14.594 7.715 7.705 4.737 4.727 42” CABINET 50 3/4” CABINET Detail B 5-3/8 1” FPT ZT037-150 unit clearances Direction Distance (in.)
  • Page 140 5167821-YTG-K-1118 ZT037-150 unit bottom duct openings Top view 32 11/16 6 13/16 6 13/16 SUPPLY RETURN 27 1/2 LEFT RIGHT 20 1/8 19 1/8 17 1/8 12 5/16 Bottom condensate drain 14 1/2 25 9/16 Bottom gas supply entry 16 3/8 18 1/16 FRONT Bottom power, control...
  • Page 141 5167821-YTG-K-1118 ZT037-150 unit electrical entry Disconnect Swith Cover Power Entry Ø 2-1/2 Control Entry Ø 7/8 Power Entry Ø 2-1/2 Convenience Outlet Cover Convenience Outlet Power Entry Ø 7/8 FRONT ZT037-061 unit side duct openings 1 8 - 1 /4 D o t P l u g s Return Supply Air...
  • Page 142 5167821-YTG-K-1118 ZT078-102 unit side duct openings Dot Plugs 18-1/4 5-5/32 2-7/8 31-5/8 ZT078-102 side duct dimensions Dimension (in.) Unit model number ZT078, 090, 102 28 1/4 18 1/16 28 1/4 18 1/4 ZT120-150 unit side duct openings Dot Plugs 18-1/4 5-5/32 2-7/8 31-5/8...
  • Page 143 5167821-YTG-K-1118 ZT037-061 unit left/end duct opening 4-5/16 ZT037-150 left/end duct dimensions Dimension (in.) Unit model number ZT037, 049, 061 30.357 13.365 22.516 ZT078, 090, 102 30.358 22.580 22.330 ZT120, 150 30.358 22.580 22.330 Johnson Controls Ducted Systems...
  • Page 144 5167821-YTG-K-1118 ZT037-150 unit accessory dimensions ZT037-150 roof curb RIGHT 80-5/8 INSULATED DECK UNDER CONDENSER SECTION SUPPLY RETURN 2 TYP. INSULATED DECK UNDER 50-1/2 COMPRESSOR SECTION FRONT 8 or 14 ZT037-061 transition roof curb 2 TYP 23 4 30-1/2 50-1/2 80-5/8 RETURN SUPPLY 76-5/8...
  • Page 145 5167821-YTG-K-1118 ZT037-150 roof curb cutaway 2“ 3/4” X 1-1/4” WIDE GASKETING FOR CURB FRAME AND ALL DUCT SUPPORT SURFACES UNIT BASE 3.75” WOOD NAILER 3.56” UNIT BASE RAILS 14” 8“ MIN. ABOVE FINISHED ROOF COUNTERFLASHING CURB FRAME CAN’T STRIP INSULATION AND ROOFING MATERIAL INSULATION ROOF DECK AND SUPPORT STRUCTURE Johnson Controls Ducted Systems...
  • Page 146: Economizer Options

    5167821-YTG-K-1118 Economizer options Economizer usage Application Cabinet height Description Model Side return Horizontal economizer without barometric relief 2EE04706924 42 in. Economizer, 42 inch tall cabinet 2EE04717424 Downflow, end return Horizontal or ERV 50 in. Economizer, 50 inch tall cabinet 2EE04717624 1.
  • Page 147: Ytg-K

    Power Exhaust Barometric Barometric Fresh Air Hood Relief Damper Relief Hood Subject to change without notice. Printed in U.S.A. 5167821-YTG-K-1118 Copyright © 2018 by Johnson Controls, Inc. All rights reserved. Supersedes: 5167821-YTG-J-0518 York International Corporation 5005 York Drive Norman, OK 73069...