Interlock Relay Feature; Figure 19. Digital I/O Module Connections - Omega DP6000 User Manual

Dual-line process meter
Table of Contents

Advertisement

DP6000 Process Meter
Instruction Manual
1
2
3
4
5
6
7
8
9
10
+5
O1
O2
O3
O4
G
I1
I2
I3
I4
DI 1-4
DO 1-4
5 VDC
GND

Figure 19. Digital I/O Module Connections

Interlock Relay Feature

As the name implies, the interlock relay feature reassigns one, or more,
alarm/control relays for use as interlock relay(s). Interlock contact(s) are
wired to digital input(s) and trigger the interlock relay. This feature is
enabled by configuring the relay, and relative digital input(s) (see page
65). In one example, dry interlock contacts are connected in series to
one digital input which will be used to force on (energize) the assigned
interlock power relay when all interlock contacts are closed (safe). The
interlock relay front panel LED flashes when locked out. The interlock
relay would be wired in-series with the load (N/O contact). See below.
27