2.1

Quick Installation Guide

The AMAX-354 provides good EMI protection and a stable grounding base. There is
an easy-to-connect chassis grounding point.
Use the grounding cable (16 AWG) from the accessory bag to connect the chassis
ground with the earth ground.
2.2

Connecting Power

This product is intended to be supplied by an approved power adapter or DC power
source. This adapter is rated at 24 Vdc, 1.5 A and has a Tmax of 60°C (140°F). If you
need further assistance or information, please contact Advantech.
Follow the following instructions:
1.
Insert the positive and negative wires into the V+ and V- contacts on the termi-
nal block connector.
2.
Tighten the wire-clamps' screws to prevent the DC wires from coming loose.
Take the following guidelines into consideration before wiring the device:
1.
The terminal block is suitable for 16-26 AWG (10 A). Torque value 7 lb-in. Use
copper conductors only.
2.
The temperature rating of the input connection cable should be higher than
95°C (203°F).