7. Configuration
4.Interface config
The configuration function of S3 logger, you can add inverters, EPM (Solis EPM Device),
meteorological meters, meters and other devices through the Add Device. Com1 and Com2
support inverters and EPM devices, Com3 supports meteorological meters, and com4 supports
meters (two-way electric meters can be used to meet the zero injection function).
5.Add EPM and inverter to Com1 and com2.
(1) Click Add Device to select a device type. You can select EPM or inverter
(2) The default device address of the EPM is 1, and the default device address of the inverter is
1-15. If the default value is used, you do not need to consider the second row. The third line
is the rated power of the inverter, which must be filled in.
(3) If the inverter address is not in the default setting, click the number from 1 to 15 based on
the number of connected devices, and manually enter the inverter address in the second row.
Note: The device address entered manually cannot be the same as the default address.
(4) If an error occurs, the configuration content will be confused. You can delete all the
configurations (YES or NO) and restart the datalogger to restore the data.