EBARA Ego 2 slim Installation And Operating Manual page 41

Hide thumbs Also See for Ego 2 slim:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 25
Only available in C module, installed in variant Ego 2 (T) slim C.
There is a mode selection rotary switch in the terminal box. It can be rotated by gently inserting a screwdriver
into the arrow mark on top and rotating the switch to desired value.
Switch setting is used when the pump turns on!
Mode switch
Function
position
0
Web configuration
Mode 1
1
(2-10V control)
Mode 2
2
(0-10V control)
Mode 3
3
(PWM Solar)
Mode 4
4
(PWM Heating)
5
RESERVED
Show relay
6
configuration
Change relay
7
configuration
Twin reset to
8
factory
9
Reset to factory
Description
Terminal functions are configured over Web interface.
SET1 = RUN input
SET2 = MAX input
SET3 = FB (10.5 V) output, can be used to supply RUN and MAX inputs.
See section "4.4 Mode 1".
SET1 = RUN input
SET2 = SPEED input
SET3 = FB (10.5 V) output, can be used to supply RUN and SPEED
inputs.
See section "4.5 Mode 2".
SET1 = PWM-in (0 % = Pump OFF)
SET2 = PWM-out status
SET3 = FB (10.5 V) output, can be used to supply SET1 and SET2 bias.
SET1 = PWM-in (100 % = Pump OFF)
SET2 = PWM-out status
SET3 = FB (10.5 V) output, can be used to supply SET1 and SET2 bias.
Reserved for future or customer specific use.
LED1 and LED2 will show relay configuration.
See section "5. Relay output".
Relay configuration will be increased (0->1, 1->2, 2->0) when power is
turned on.
LED1 and LED2 will show current relay configuration.
See section "5. Relay output".
Same as Mode 9, with exception of:
module IP address is set to 192.168.0.246
This mode will set communication interface to default values. Main
purpose is to restore default settings. IP address is set to
192.168.0.245
40
40

Advertisement

Table of Contents
loading

Table of Contents