Effekta Compact RM 750 Operating Manual

Effekta Compact RM 750 Operating Manual

Uninterruptable power supply

Advertisement

Quick Links

UPS
Uninterruptable Power Supply
Compact RM 750 / 2200 / 3000
Operating Manual V 1.1
Part numbers:
ACX11COM75000000
ACX11COM2K200000
ACX11COM3K000000
Translation of the original operating manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Compact RM 750 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Effekta Compact RM 750

  • Page 1 Uninterruptable Power Supply Compact RM 750 / 2200 / 3000 Operating Manual V 1.1 Part numbers: ACX11COM75000000 ACX11COM2K200000 ACX11COM3K000000 Translation of the original operating manual...
  • Page 2 UPS: Compact RM 750 / 2200 / 3000 Legal Notice Legal Notice © by EFFEKTA Regeltechnik GmbH This documentation is solely intended for the operator and his staff. The content of this documentation (texts, figures, drawings, graphics, plans, etc.) may not be...
  • Page 3: Table Of Contents

    UPS: Compact RM 750 / 2200 / 3000 Table of Contents Table of Contents Introduction ......................5 Preface ........................5 Validity ........................6 Storage ........................6 Abbreviations, Terms and Symbols................6 Information obligation ....................9 Warranty conditions ....................10 Limitation of Liability ....................11 Safety Instructions ....................
  • Page 4 UPS: Compact RM 750 / 2200 / 3000 Table of Contents Service-Hotline....................... 37 Maintenance and service..................38 11.1 Measuring the support time (battery time) ..............38 11.2 Replacing components / accumulators ..............39 11.3 Maintenance and service contracts ................40 11.4 Service-Log ......................
  • Page 5: Introduction

    UPS: Compact RM 750 / 2200 / 3000 Introduction Introduction Preface Dear Operator, This manual is required for the operation of the uninterruptible power supply de- scribed herein. This operating manual should provide you with support for working responsibly and give basic information about the uninterruptible power supply, namely on how it works, its application and, in addition, what you should do in the event of malfunctioning.
  • Page 6: Validity

    UPS: Compact RM 750 / 2200 / 3000 Introduction Validity The descriptions in this operating manual relate solely to the uninterruptible power supply (UPS) defined in the technical data as a whole or as it refers to modules, components and individual parts that were developed and built by EFFEKTA Regeltechnik GmbH.
  • Page 7 UPS: Compact RM 750 / 2200 / 3000 Introduction Text that is marked with WARNING! provides a warning about hazards. If acci- dent prevention measures are not taken, these hazards may result in serious (irreversible) injuries or even death! Text that is marked with CAUTION! provides a warning about hazards. If acci- dent prevention measures are not taken, these dangerous situations can lead to slight or medium reversible injuries.
  • Page 8 UPS: Compact RM 750 / 2200 / 3000 Introduction Instruction Symbols: Take note of the provided documentation and/or instructions! Disconnect before working! Environmental Symbols: Identifies instructions for recycling. Identifies components that are subject to the Electronic Scrap Regulation. Identifies components or parts that must be disposed of properly. Do not throw these into the household waste.
  • Page 9: Information Obligation

    This applies, in particular, to maintenance, operating and cleaning personnel in- cluding persons responsible for transportation and/or disposal. EFFEKTA Regeltechnik GmbH is not liable for damage incurred or caused by staff who have not been trained or who have been insufficiently trained!
  • Page 10: Warranty Conditions

    UPS: Compact RM 750 / 2200 / 3000 Introduction Warranty conditions The receipt of delivery is considered as the record for the initial purchase and should be kept in a safe place. It will be necessary for making use of the war- ranty.
  • Page 11: Limitation Of Liability

    We are not liable for damage or consequential damage, whether directly, unin- tentionally or caused by negligence. EFFEKTA Regeltechnik GmbH does not provide either explicit or implicit war- ranties related to this device and its quality, performance, saleability, or suitabil- ity for a certain purpose.
  • Page 12: Safety Instructions

    UPS: Compact RM 750 / 2200 / 3000 Safety Instructions Safety Instructions Introduction The UPS is a device that has been produced according to the rules and regula- tions of technology for an uninterruptible power supply. The device is safe when used properly and under consideration of the safety re- quirements and instructions provided in this operating manual.
  • Page 13: Prevention Of Personal Injury / Property Damage

    Observe the required steps. Only use original re- placement parts from EFFEKTA Regeltechnik GmbH Environmental protection Send the product back to EFFEKTA Regeltechnik GmbH after the end of its service life. We will ensure its environmentally friendly disposal. Transport and Storage The UPS may only be transported to the intended location in the original pack- aging.
  • Page 14: Positioning

    UPS: Compact RM 750 / 2200 / 3000 Safety Instructions Positioning Only operate the UPS in well-ventilated rooms, ensuring the specified ambient temperature range. The UPS should not be placed in the vicinity of heat sources. Always take the operating conditions into account when positioning the device.
  • Page 15: Operation

    UPS: Compact RM 750 / 2200 / 3000 Safety Instructions In addition, the following points must always be followed when connecting the UPS: – Install all connections appropriately and keep the cable length as short as possible; – Only use suitable power cables when connection the UPS to the mains power supply and pay attention to the required current carry- ing capacity;...
  • Page 16: Working With Accumulators

    UPS: Compact RM 750 / 2200 / 3000 Safety Instructions Working with accumulators When handling accumulators, there is always a risk of electric shock, burns and/or chemical burns. This is why unauthorized personnel should not have access to accumulators. Accumulators and their circuit points can cause electric shocks.
  • Page 17: Maintenance, Service And Malfunctions

    UPS: Compact RM 750 / 2200 / 3000 Safety Instructions 2.10 Maintenance, service and malfunctions Attention – Risk of electric shock. Even after switching off the supply with the power button or after disconnecting the accumulator feed, parts of the UPS can still carry high voltages.
  • Page 18: Ups Device Description

    UPS: Compact RM 750 / 2200 / 3000 Storage and unpacking UPS device description Sensitive loads require comprehensive protection against supply disruption. This includes: temporary mains failure, mains voltage fluctuations, mains volt- age peaks, frequency changes, etc. The uninterruptible power supply unit is in-...
  • Page 19: Ups Device Components

    UPS: Compact RM 750 / 2200 / 3000 UPS device description UPS device components The entire device series is integrated in a metal case. All components of the device for operation are located on the front panel of the device, and all components for the connection are distributed on the backside of the device (see the following fig- ures).
  • Page 20 UPS: Compact RM 750 / 2200 / 3000 Storage and unpacking Back View: Compact RM 750 VA Compact RM 2200 VA Compact RM 3000 VA Description: (1) Output: IEC C13 / 10A (2) Input fuse/breaker (3) AC-Input (4) Communication port (USB...
  • Page 21 UPS: Compact RM 750 / 2200 / 3000 UPS device description Meaning of the individual display symbols: (1) Display of the UPS input data (Mains voltage in volts). (2) Display of the UPS output data (Consumer voltage in volts). (3) AC mode indicator...
  • Page 22 UPS: Compact RM 750 / 2200 / 3000 Storage and unpacking  Communication port of the UPS, USB port for the exchange of device data and the signals for shutting down sensitive loads (PC, SHUT DOWN). If the USB- port is used, the serial port remains inactive.
  • Page 23 UPS: Compact RM 750 / 2200 / 3000 UPS device description 3.2.4 Name plate (Device identification) UPS device identification. The following information is on the name plate: – model name; – data for connected load values; – the CE-marking and the serial number for the device;...
  • Page 24: Storage And Unpacking

    UPS: Compact RM 750 / 2200 / 3000 Storage and unpacking Storage and unpacking Storage of the UPS If the UPS is to be put in storage after delivery, it is imperative to observe the following instructions: – Always leave the device and accessories in the original packaging;...
  • Page 25: Unpacking And Positioning Of The Device

    UPS: Compact RM 750 / 2200 / 3000 Storage and unpacking Unpacking and positioning of the device Remove the packaging at the installation site with the utmost care to avoid causing any possible damage to the device and the packaging material.
  • Page 26: Installation And Connection Of The Ups

    UPS: Compact RM 750 / 2200 / 3000 Installation and Connection Installation and Connection of the UPS All critical values listed in the technical specifications concerning ambient and operating conditions must be met to ensure proper operation of the UPS.
  • Page 27 UPS: Compact RM 750 / 2200 / 3000 Installation and Connection In addition, make sure that the ventilation channels of the UPS are not blocked and that there is sufficient clearance between the device and other equipment, furniture, and walls to allow the device to cool.
  • Page 28: Connection Of The Ups Device

    UPS: Compact RM 750 / 2200 / 3000 Installation and Connection Connection of the UPS device 5.2.1 Input and output connection for the The COMPACT RM series is usually con- nected to the supply network with the cold device cable provided on the input side.
  • Page 29 UPS: Compact RM 750 / 2200 / 3000 Installation and Connection UPS-Type [VA]: Fuse on the in- Com- put side: ment: 2200 3000 Circuit breaker 10 A 13 A 16 A Type „C“ (S): Cable cross max. 3x 0.75 mm²...
  • Page 30 UPS: Compact RM 750 / 2200 / 3000 Installation and Connection 5.2.4 Connection of the emergency shutdown, dropping of the loads The function of the emergency shutdown EPO or REPO (REMOTE EMER- GENCY POWER OFF) serves the immediate dropping of the connected loads An external emergency eject button must be connected to the EPO signal input for this purpose (potential-free contact).
  • Page 31: Operation Of Device And Service

    UPS: Compact RM 750 / 2200 / 3000 Operation of device and service Operation of device and service Due to the comprehensive protective functions which the device performs re- garding the loads, the UPS runs completely automatically. This reduces the op- eration of the device to a few steps.
  • Page 32 UPS: Compact RM 750 / 2200 / 3000 Operation of device and service 6.1.1 Switching on the UPS, Charging mode If the UPS is connected to the mains, the de- vice starts automatically and starts with the ini- tialization. The device then automatically and automati-...
  • Page 33 UPS: Compact RM 750 / 2200 / 3000 Operation of device and service The UPS output remains switched on, the consumers continue to be supplied for the duration of the autonomy period. The discharge of the battery can be observed. The display icon shows the re- maining battery capacity ("approx.
  • Page 34 UPS: Compact RM 750 / 2200 / 3000 Operation of device and service 6.1.6 UPS overload operation If the UPS is overloaded on the output side, the loads continue to be supplied for a short time depending on the overload.
  • Page 35: Initial Operation Of The Ups

    UPS: Compact RM 750 / 2200 / 3000 Initial operation Initial operation of the UPS The initial operation generally requires that all previous chapters of this manual have already been successfully read or processed. Additionally, check that all connected loads are switched off.
  • Page 36: Error Messages And Support

    UPS: Compact RM 750 / 2200 / 3000 Error Messages Error messages and support In the event the UPS device is not working properly, please first check the oper- ation information on the operation unit. Please try to localize the problem with the aid of the following table:...
  • Page 37: Troubleshooting

    UPS: Compact RM 750 / 2200 / 3000 Troubleshooting Troubleshooting Over the course of time, failures or malfunctions of the UPS, the accumulator or their surroundings can arise. In this event, please contact our customer service (service hotline) as soon as possible.
  • Page 38: Maintenance And Service

    UPS: Compact RM 750 / 2200 / 3000 Maintenance and Service Maintenance and service You can expect a long service life and trouble-free operation for this product. However, the service life and reliability of the UPS is largely determined by the ambient conditions.
  • Page 39: Replacing Components / Accumulators

    (key word: dust). 11.2 Replacing components / accumulators Only EFFEKTA Regeltechnik service personnel or personnel of other accredited service points is allowed to replace accumulators or other UPS components. During the replacement of accumulators and other components, the loads are directly connected to the mains power supply via an external by-pass.
  • Page 40: Maintenance And Service Contracts

    UPS: Compact RM 750 / 2200 / 3000 Maintenance and Service 11.3 Maintenance and service contracts EFFEKTA Regeltechnik GmbH offers corresponding maintenance and service contracts to guarantee the best possible reliability and availability of your UPS equipment. Under a maintenance contract, our service personnel can, in addi-...
  • Page 41: Service-Log

    UPS: Compact RM 750 / 2200 / 3000 Maintenance and Service 11.4 Service-Log Please always enter all maintenance and service work performed on the UPS into the service log. Date Performed tasks Performed by Compact RM Series...
  • Page 42: Specifications

    UPS: Compact RM 750 / 2200 / 3000 Specifications Specifications COMPACT RM: 2200 3000 750 VA, 450 W 2200 VA, 1320 W 3000 VA, 1800 W Input 1 Phase, neutral conductor and PE conductor Nominal Voltage 220, 230, 240VAC Voltage Range...
  • Page 43: Scope Of Delivery

    UPS: Compact RM 750 / 2200 / 3000 Scope of Delivery Scope of delivery The following is the list of the scope of delivery; please compare the list with the delivered goods. Should any items or components be missing in your delivery, please let us know immediately.
  • Page 44: Optional Accessories

    UPS: Compact RM 750 / 2200 / 3000 Optional accessories Optional accessories The components, devices and/or equipment listed below are accessories that fit the OFFICE series and that have been tested and approved by EFFEKTA Re- geltechnik GmbH. 14.1 Communication adapter SNMP The SNMP adapter integrates the UPS into a network and communicates via TCP/IP, Telnet or FTP.
  • Page 45: External Bypass

    UPS: Compact RM 750 / 2200 / 3000 Optional accessories 14.3 External Bypass An external by-pass system allows the operation of the loads on two different paths. In the UPS operation mode (Fig. 14-4) the UPS system is integrated into the current path and the loads are protected in the usual manner.
  • Page 46: Declaration Of Conformity

    UPS: Compact RM 750 / 2200 / 3000 Declaration of conformity Declaration of conformity All units labeled with a CE sign fulfill the EU harmonized standards and regula- tions. The EU declaration of conformity for this product is available upon request.
  • Page 47 Notes Compact RM Series...