USV MTX Series 800 - 3000 VA
(Line-Interactive)
Operating Manual V 1.5
Versions / part number:
800 VA
1100 VA
1500 VA
2000 VA
3000 VA
/ ACX11MXS80000000
/ ACX11MXS1K100000
/ ACX11MXS1K500000
/ ACX11MXS2K000000
/ ACX11MXS3K000000
Translation of original operating manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the USV MTX Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Effekta USV MTX Series

  • Page 1 Uninterruptible Power Supply USV MTX Series 800 - 3000 VA (Line-Interactive) Operating Manual V 1.5 Versions / part number: 800 VA / ACX11MXS80000000 1100 VA / ACX11MXS1K100000 1500 VA / ACX11MXS1K500000 2000 VA / ACX11MXS2K000000 3000 VA / ACX11MXS3K000000 Translation of original operating manual...
  • Page 2 "VI"- USV 800-3000 VA Legal Notice Legal notice © by EFFEKTA Regeltechnik GmbH This operating manual is solely intended for the operator and his staff. The con- tent of this documentation (texts, figures, drawings, graphics, plans, etc.) may not be copied or distributed in part or in full without our written consent, nor can it be used without authorization for competitive purposes or given or made ac- cessible to third parties.
  • Page 3: Table Of Contents

    "VI"- USV 800-3000 VA Table of Contents Table of Contents Introduction ......................5 Preface ........................5 Validity ........................5 Storage of the manual ....................6 Abbreviations, terms and symbols ................6 Information obligation ....................8 Warranty conditions ....................9 Limitation of liability ....................10 Safety instructions ....................11 Introduction ......................11 Proper use........................11...
  • Page 4 "VI"- USV 800-3000 VA Table of Contents Warning and error messages of the device .............. 41 Troubleshooting ....................43 Service hotline ....................... 44 Monitor software ....................45 Maintenance and service..................46 12.1 Measuring the support time (autonomous time) ............46 12.2 Replacing components / accumulators ..............
  • Page 5: Introduction

    (UPS) defined in the technical data as a whole or as it refers to modules, components and individual parts that were developed and built by  EFFEKTA Regeltechnik GmbH (Chapter 13 Technical dataa). Read this documentation carefully and familiarize yourself with the product be-...
  • Page 6: Storage Of The Manual

    "VI"- USV 800-3000 VA Introduction Storage of the manual The operating manual for the device must be stored in the vicinity of the device at all times so it is immediately available if need be. Pass this manual on to any subsequent users of the product. Abbreviations, terms and symbols In this manual, the abbreviation UPS stands for: uninterruptible power supply.
  • Page 7 "VI"- USV 800-3000 VA Introduction Attention: Indicates a potentially harmful situation. If it is not avoided, the device or objects in its vicinity could be damaged. This symbol indicates text passages that contain notices / comments or com- prehensive tips. Warning symbols for the identification of danger areas: General warning about danger areas! Symbols of specific warnings:...
  • Page 8: Information Obligation

    This applies, in particular, to maintenance, operating and cleaning personnel, including persons responsible for transportation and/or disposal. EFFEKTA Regeltechnik GmbH is not liable for damage incurred or caused by staff who have not been trained or who have been insufficiently trained!
  • Page 9: Warranty Conditions

    "VI"- USV 800-3000 VA Introduction Warranty conditions The receipt of delivery is considered to be the record for the initial purchase and should be kept in a safe place. It will be necessary for making use of the warran- ty. If the product is passed on to another user, this user has the right to the war- ranty for the remainder of the warranty period.
  • Page 10: Limitation Of Liability

    EFFEKTA Regeltechnik GmbH was informed of the possibility of such damage in advance. This exemption also includes any liability that can re- sult from the claims of third parties against the initial purchaser.
  • Page 11: Safety Instructions

    "VI"- USV 800-3000 VA Safety Instructions Safety instructions Introduction The UPS is a device that has been produced according to the rules and regula- tions of technology for an uninterruptible power supply. The device is safe when used properly and in compliance with the safety re- quirements and instructions provided in this operating manual.
  • Page 12: Prevention Of Personal Injury / Property Damage

    Observe the prescribed instruction steps. Only use original replacement parts from EFFEKTA Regeltechnik GmbH. Environmental protection Send the product back to EFFEKTA Regeltechnik GmbH after the end of its service life. We will ensure its environmentally friendly disposal. Transport and storage The UPS can only be transported to the intended location in the original packag- ing.
  • Page 13: Positioning

    "VI"- USV 800-3000 VA Safety Instructions Positioning Only operate the UPS in well-ventilated rooms, ensuring the specified ambient temperature range (according to 13 Technical data). The UPS should not be placed in the vicinity of heat sources. Always take the operating conditions into account when positioning the device.
  • Page 14: Operation

    "VI"- USV 800-3000 VA Safety Instructions – Only use suitable power cables when connecting the UPS to the mains power supply and pay attention to the required current carry- ing capacity; – Only use suitable power cables when connecting loads to the UPS and pay attention to the required current carrying capacity;...
  • Page 15: Maintenance, Service And Malfunctions

    "VI"- USV 800-3000 VA Safety Instructions Accumulators should never be opened or destroyed. The electrolyte released presents a great danger to your health and the environment. It could result in chemical burns to skin and eyes; moreover, the electrolyte is very toxic. Defective accumulators must be disposed of in an environmentally friendly manner! Never dispose of accumulators with regular household waste!
  • Page 16: Ups Device Description

    "VI"- USV 800-3000 VA Device Description UPS device description Sensitive loads require comprehensive protection against power supply disrup- tions. These include: temporary power failure, mains voltage fluctuations, mains voltage peaks, changes in frequency, etc. The uninterruptible power supply is intended to protect mains-powered, electronic devices such as, computers, work stations, cash registers, telecommunication devices, process control systems, etc., against power supply disruptions.
  • Page 17: Format, Housing Sizes And Design

    "VI"- USV 800-3000 VA Device Description Format, housing sizes and design The MTX series is available in various capacity variants. All devices already have an internal energy storage unit (power bank). In addition, external battery banks with the same front format are delivered to enable an adaption to the au- tonomous time.
  • Page 18: Device Components Of The Ups

    "VI"- USV 800-3000 VA Device Description Device components of the UPS The complete MTX device series is integrated in a free-standing enclosure (TOWER). All device elements for the operation and display are accessible on the front of the device. The elements for the connection and extensions of the device are arranged on the back side.
  • Page 19 "VI"- USV 800-3000 VA Device Description mation or operating information and the available alarm codes in the case of failure are important. The total display contains various information areas and pictograms. Fig. 3-3 Example of view of total display. In the following, the meaning of the information shown is explained in detail. Ad- ditional and supplementary information for the display and notices can be seen ...
  • Page 20 "VI"- USV 800-3000 VA Device Description The upper circle bar graph shows the charging status of the battery bank in %. The gradations are: 2-24%, 25-49%, 50-74%, 75-100%. The UPS is in the charging mode. Indicator for the battery bank. Low battery bank status.
  • Page 21 "VI"- USV 800-3000 VA Device Description 3.3.3 Device elements of all device variants on the back of the UPS 800/1100 VA 1500 VA 2000 VA 3000 VA Fig. 3-4 Arrangement of the device elements on the back of the UPS.
  • Page 22 "VI"- USV 800-3000 VA Device Description  Programmable UPS outputs (C13 socket). The out- puts are generally intended for non-critical loads that can be dropped relatively quickly (programmable) during the support phase.  UPS outputs (C13, C19 socket). These outlets are generally intended for critical loads because they are energized during the entire support phase.
  • Page 23 "VI"- USV 800-3000 VA Device Description The following information is found on the label: – the model name; – the data on the connec- tion values; – the CE, ROHS labels and the serial number for the device; – the manufacturer’s ad- dress.
  • Page 24: Storage And Unpacking

    "VI"- USV 800-3000 VA Storage and Unpacking Storage and unpacking Storage of the UPS If the UPS is to be stored after delivery, the following points must be observed: – Always leave the UPS and accessories in the original packaging; –...
  • Page 25: Installation And Connection Of The Ups

    "VI"- USV 800-3000 VA Installation and Connection Installation and connection of the UPS All limit values listed in the technical data regarding the ambient and operation conditions are to be maintained in order to ensure the proper functioning of the UPS.
  • Page 26: Connecting The Ups Device

    "VI"- USV 800-3000 VA Installation and Connection Connecting the UPS device 5.1.1 Input and output connection for the The MTX series is usually connected to the supply network with the cold device cable provided on the input side. This can connect the UPS with the customary wall socket (Schuko).
  • Page 27 "VI"- USV 800-3000 VA Installation and Connection USV-Type [VA]: Fuse on the Com- input side: ment: 1100 1500 2000 3000 Circuit breaker Type „C“ 10 A 10 A 10 A 13 A 16 A (S): Cable cross 3x 0.75 3x 0.75 3x 0.75 3x 1.00 3x 1.50...
  • Page 28 "VI"- USV 800-3000 VA Installation and Connection 5.1.4 Connection of the emergency shutdown, dropping of the loads The function of the emergency shutdown EPO or REPO (REMOTE EMER- GENCY POWER OFF) serves the immediate dropping of the connected loads from a distance of known dimensions. For this, an external emergency release button must be connected to the signal input EPO (isolated contact).
  • Page 29 "VI"- USV 800-3000 VA Installation and Connection • Connect the battery bank cable with the plug-in connector intended for this to the UPS and the battery bank according to the following fig- ure. In doing so, please remove the covers of the connector plugs on the UPS and the battery bank.
  • Page 30: Operation Of Device And Service

    "VI"- USV 800-3000 VA Operation and Service Operation of device and service Due to the comprehensive protective functions which the device performs re- garding the load(s), the UPS operates nearly completely automatically. This re- duces the operation of the device to a few steps. The operating personnel should always inform affected employees (keyword: consumer network) about any scheduled tasks concerning the UPS.
  • Page 31 "VI"- USV 800-3000 VA Operation and Service 6.1.1 Standby mode (STANDBY) of the UPS ✓ The device is switched off and not yet connected to the supply net- work. If the UPS is coupled with the supply net- work (UPS input), the UPS initializes and switches directly to the standby mode.
  • Page 32 "VI"- USV 800-3000 VA Operation and Service It is always critical to keep the device in the charging more for several hours (min. 8 hrs.) to achieve the complete charging status of the accumulator before the device can assume its proper support function. 6.1.3 Autonomous mode of the UPS ✓...
  • Page 33 "VI"- USV 800-3000 VA Operation and Service Switching the UPS off occurs with the activa- tion of the OFF button. In doing so, the UPS is not completely switched off but rather switches to the STANDBY mode. The UPS output is, of course, switched off.
  • Page 34 "VI"- USV 800-3000 VA Operation and Service 6.1.6 Muting the UPS ✓ The device is in autonomous mode (6.1.3). The acoustic signaling can be switched off during the autonomous mode. To do so, the ON button must only be activated for rough- ly 3 seconds.
  • Page 35 "VI"- USV 800-3000 VA Operation and Service 6.1.8 AVR operation mode (AUTOMATIC VOLTAGE REGULATION) ✓ The device is in standard operating mode (6.1.2). If the supply voltage increases over a defined threshold, the UPS switches to buck mode (BUCK) so that the loads are protected against high voltage.
  • Page 36: Setting The Operation Parameters (Settings)

    "VI"- USV 800-3000 VA Operation and Service Setting the operation parameters (SETTINGS) In general, the UPS must be in standby mode (STANDBY) in order to be able to switch to the setting mode from there. Generally, ensure that a battery bank, either internal or external, is connected to the UPS and ready for operation during the setting work.
  • Page 37 "VI"- USV 800-3000 VA Operation and Service The programmable UPS outputs listed  under can be activated or deactivated with these parameters. The options avail- able are: ENA (ENABLE): activated; DIS (DISABLE): deactivated; Menu page 3: Programmable outputs, support time If the programmable UPS outputs in menu page 2 are activated, the support period can be defined here.
  • Page 38 "VI"- USV 800-3000 VA Operation and Service Logic setting “EPO” (EMERGENCY POWER OFF) Menu page 7: It can be determined here how the EPO input will be fail safe handled. Either as “normally open contact” AC (ACTIVE CLOSED) or as “opener” AO (ACTIVE OPEN).
  • Page 39 "VI"- USV 800-3000 VA Operation and Service Step 1: Before switching to the setting mode, the UPS must be in STANDBY mode and the battery bank must be con- nected and charged in accord with the display pictured here. Step 2: Activate the SELECT button for more than 3 seconds;...
  • Page 40: Initial Operation Of The Ups

    "VI"- USV 800-3000 VA Initial Operation Initial operation of the UPS The initial operation generally requires that all previous chapters of this manual have already been successfully read or processed. Additionally, check that all connected loads are switched off. The initial operation of UPS devices is exclusively reserved for accredited per- sonnel.
  • Page 41: Messages And Error Codes

    "VI"- USV 800-3000 VA Error Codes Messages and error codes For a quick evaluation of the operating status or a message or a parameter of the UPS, the following table summarizes the significant abbreviations of the dis- play once again. Abbreviation: Representation: Meaning:...
  • Page 42 "VI"- USV 800-3000 VA Error Codes Error Warning / error Symbol (blinking) Acoustic signal number Low battery bank status Signal every 2 sec. (LOW BATTERY) Overload (OVERLOAD) Signal every sec. Overload (OVERLOAD) Constant signal Short circuit of UPS output Constant signal (SHORT) Battery bank not connected Signal every 2 sec.
  • Page 43: Troubleshooting

    "VI"- USV 800-3000 VA Error Codes Troubleshooting Over the course of time, failures or malfunctions of the UPS, accumulators or their surroundings can arise. In the event the UPS device is not working proper- ly, please first check the current operation information in the display. Then at- tempt to identify the problem by means of the following information: Problem/display: Possible cause:...
  • Page 44: Service Hotline

    0049 / (0) 741 – 17451-52 Telephone: 0049 / (0) 741 – 17451-29 Telefax: You can also reach us via email at: kundendienst@effekta.com In addition, you can contact the relevant department or branch office directly as listed on our website: http://www.effekta.com...
  • Page 45: Monitor Software

    "VI"- USV 800-3000 VA Software Monitor software The UPS management software runs as a client / server application for hetero- geneous networks or on a local computer. It works on all common platforms (Win, Linux, UNIX). Remote access to the UPS and its data is possible and recordable. The software shows all relevant UPS data, such as the battery status, tempera- ture, condition of the mains power supply, etc., in a clear graphic interface.
  • Page 46: Maintenance And Service

    "VI"- USV 800-3000 VA Maintenance and Service Maintenance and service You can expect a long service life and interference-free operation from this product. The service life and reliability of the UPS is greatly dependent on the conditions of its environment. The ambient temperature and humidity in the vi- cinity of the device must remain within the specified range.
  • Page 47: Replacing Components / Accumulators

    Replacing components / accumulators The replacement of accumulators and possibly other UPS components must on- ly be performed by personnel from EFFEKTA Regeltechnik GmbH or an accred- ited service center. During the replacement of the accumulators and other UPS components, the loads are directly connected to the mains power supply via an external bypass whereby other support functions of the UPS cannot occur at this time.
  • Page 48 "VI"- USV 800-3000 VA Maintenance and Service Please follow the instructions below to replace the internal battery bank. The fol- lowing applies for the MTX series with 800-2000 VA: Step 1: Remove the safety plate on Step 2: Pull the battery bank slightly the device base of the UPS.
  • Page 49 "VI"- USV 800-3000 VA Maintenance and Service The following applies for the MTX series with 3000 VA: Step 1: Remove the front cover of the Step 2: Open the electrical connection UPS. and remove the battery bank cover. Step 3: Pull the battery bank com- Step 4: The battery bank trays must pletely out of the UPS.
  • Page 50: Maintenance And Service Contracts

    12.3 Maintenance and service contracts EFFEKTA Regeltechnik GmbH offers corresponding maintenance and service contracts to guarantee the best possible reliability and availability of the UPS. Under a maintenance contract, our service personnel can also support and as- sist you in the following areas: Regular inspection of the UPS, in particular, the accumula- tors and their timely replacement.
  • Page 51: Service Log

    "VI"- USV 800-3000 VA Maintenance and Service 12.4 Service log Please always enter all maintenance and service work performed on the UPS device into the service log. Date Tasks performed Performed by...
  • Page 52: Technical Data

    "VI"- USV 800-3000 VA Technical Data Technical data MTX: 1100 800 VA / 720 W 1100 VA / 990 W Mains power supply 1 phase, neutral conductor and PE conductor Nominal voltage 230 VAC Voltage ranges 150-234/156-243/162-268/170-280/177-290 VAC 50/60 Hz  5 Hz (automatic detection) Frequency range Mains power supply 1 phase, neutral conductor and PE conductor...
  • Page 53 "VI"- USV 800-3000 VA Technical Data MTX: 1500 2000 3000 1500 VA / 1350 W 2000 VA / 1800 W 3000 VA / 2700 W Mains power supply 1 phase, neutral conductor and PE conductor Nominal voltage 230 VAC Voltage ranges 150-234/156-243/162-268/170-280/177-290 VAC 50/60 Hz ...
  • Page 54: Scope Of Delivery / Accessories

    "VI"- USV 800-3000 VA Accessories Scope of delivery / Accessories The following is a list of the scope of delivery; please compare this with the re- ceived goods. Please inform us immediately if any items or components are missing. Article (No.) Function / view: Description: MTX series,...
  • Page 55: Optional Accessories

    Optional Accessories Optional accessories The components, devices and/or equipment listed below are accessories that are suitable for the MTX series and have been tested and approved by EFFEKTA Regeltechnik GmbH. 15.1 Signal adapter: Relay card (AS400) ZBBVTBRELMTXWK00 The relay card also belongs to the intelligent extension card and is used for the direct and potential-free contact with external controls and/or machines.
  • Page 56: Communication Adapter: Snmp

    "VI"- USV 800-3000 VA Optional Accessories 15.2 Communication adapter: SNMP The SNMP adapter integrates the UPS into a network and communicates via TCP/IP, Telnet or FTP. After assigning an individual IP-address, the UPS can be accessed from any location, which is of particular interest for remote admin- istration and maintenance of the equipment.
  • Page 57: External Battery Bank

    "VI"- USV 800-3000 VA Optional Accessories 15.4 External battery bank Each UPS system needs an energy storage to supply the stored power to the loads during a power failure. The ex- ternal battery bank units can either be used as the sole energy storage or in addition to the internal battery bank of the UPS to extend the autonomous pe- riod and/or adjust the necessary load...
  • Page 58: Wear Parts

    All units labeled with a CE sign fulfill the EU harmonized standards and regula- tions. The EU declaration of conformity for this product is available upon request. Please contact our  10 Service hotline. You can also find the declaration of conformity for this product on our website: http://www.effekta.com.
  • Page 59 Notes...