UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Legal Notice Legal Notice by EFFEKTA Regeltechnik GmbH EFFEKTA Regeltechnik GmbH, 78628 Rottweil, retains the copyright to this documentation. This documentation is solely intended for the operator and his staff. The con- tent of this documentation (texts, figures, drawings, graphics, plans, etc.) may...
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Table of Contents Table of Contents Introduction ......................5 Foreword ........................5 Validity ........................6 Storage ........................6 Symbols in this Manual ....................6 Information Obligation ....................10 Warranty Conditions ....................10 Transport and Storage ....................12...
Page 4
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Table of Contents Starting up the UPS System .................. 49 Eliminating Errors ....................50 Software ......................... 52 Maintenance and Service ..................53 11.1 Measurement of the Bridging Period (Support Period) ..........53 11.2 Replacing the Accumulators ..................
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Introduction Introduction Foreword Dear Operator, You are about to operate an uninterruptible power supply. This operating manual should provide you with support for working responsibly and give you basic information about the uninterruptible power supply, namely how it operates, its application and what you should do in the event of malfunc- tioning.
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Introduction Validity The descriptions in this operating manual relate solely to the uninterruptible power supply defined in the Technical Data as a whole or they refer to modules, components and individual parts that were developed and built by EFFEKTA Regeltechnik GmbH.
Page 7
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Introduction Text that is marked with WARNING! provides a warning about hazards. If accident prevention measures are not taken, these hazards may result in serious (irreversible) injuries or even death! Text that is marked with CAUTION! provides a warning about hazards.
Page 8
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Introduction 1.4.2 Warning information 1.4.2.1 Warning about danger spots General warning about danger spots! 1.4.2.2 Specific warning Warning about dangerous electrical voltage! Warning for handling accumulators! 1.4.3 Instruction symbols...
Page 9
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Introduction 1.4.4 General symbols ● This dot marks descriptions of activities that you should carry out. – This dash marks specifications. This arrow marks a cross reference. If a cross reference to another chapter is necessary in the text, this is short- ened for clarity.
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Introduction Information Obligation This operating manual must be read, understood and all its points regarded by all persons that are responsible for the – operation – cleaning and – disposal of the device.
Page 11
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Introduction – In the event of incompatibility or malfunctioning that was caused by product components we did not install. – In the event of developments that are related to the normal aging process of the product (wear parts).
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Introduction 1.6.1 Limitation of Liability Claims to damage compensation are excluded unless they involve intent or gross negligence by EFFEKTA Regeltechnik GmbH or its employees. This does not affect liability according to the Product Liability Act. Under no circum- stances are we liable for: –...
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Introduction Positioning Do not install in an area in which combustible vapours result e.g. from petrol tanks, engine compartments, etc. The UPS is designed for operation in ventilated rooms with a surrounding tem- perature of 0 °...
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Safety Instructions Safety Instructions Introduction The UPS is a device produced for uninterruptible power supply in accord- ance with the technology rules and requirements. The device and its related components, modules and parts meet individ- ually and in their entirety the currently valid safety standards as well as the standards of the EC Machinery Directive 2006/42/EC.
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Safety Instructions Avoiding Personal Injury / Property Damage Please read this operating manual carefully to familiarise yourself with the device. In particular, heed the information regarding the installation and commis- sioning of the device.
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Safety Instructions Connection Only connect the UPS to an earthed electric safety socket or be sure to connect it to the protective conductor in the event of a connecting termi- nal.
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Safety Instructions Operation Before the loads are connected on the output, the basic configuration must be set. The output voltage in relation to the loads is Very Important. The UPS system includes energy storage (accumulators). As a result, the out- put can carry power even if the UPS is not connected on the mains input side.
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Safety Instructions Defective accumulators must be disposed in an environmentally friendly way. Do not throw accumulators in household trash under any circumstances. Local disposal requirements are to be regarded.
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Device Description of UPS Device Description of UPS This manual is intended to provide basic information about single-phase offline UPS systems, namely how they function, the application of different functions and what you should do in the event of malfunctioning.
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Device Description of UPS Device Elements on the Front The front of the device contains all the operating and display elements required for normal operation. LED display "FAULT" LED display "WARNING"...
Page 22
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Device Description of UPS LCD display LED display "FAULT" LED display "WARNING" LED display "NORMAL" Key "LCD" Key "POWER ON/OFF" Fig. 3-1 - 2 Front view of MTD 700RM, 1000RM, 1500RM 1 LED display "FAULT"...
Page 23
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Device Description of UPS LED display "FAULT" LED display "WARNING" LCD display LED display "NORMAL" Key "Menu selection" Key "Menu decrease" Key "Menu increase" Fig. 3-1 - 4 Front view of MTD 3000RM...
Page 24
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Device Description of UPS 3.1.1 LCD display The LCD display is intended to display the type of operation and different sta- tus values. The following displays can be selected by pressing the up and down keys: –...
Page 25
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Device Description of UPS 3.1.3 Keys Menu selection The UPS is switched on by simultaneously pressing this key with the menu down key for approx. 3 seconds. The UPS is switched to test operation by simultaneously pressing this key with the menu up key for approx.
Page 31
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Device Description of UPS 3.2.1 Remote control An external display can be connected via the remote connection. 3.2.2 Communication interface After unscrewing the cover, various expansion cards can be used such as RS232 interface, network adapter, USB interface.
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Device Description of UPS Fig. 3-2 - 8 Network connection Fig. 3-2 - 9 USB interface 3.2.3 UPS output IEC sockets 10 A and 16 A for the connection of the loads.
Page 33
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Device Description of UPS 3.2.4 Mains input IEC inlet connector 10 A. IEC inlet connector 16 A with types 2000RM / 3000RM IEC. Mains connection via appended connection cable with safety plug.
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Device Description of UPS Acoustic Warnings of the UPS – Support operation and high battery capacity: The acoustic warning sounds in the following sequence (A) [Beep -> long pause (4 sec.) -> Beep -> ..., repeating (5 times, subsequently no more messages)].
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Storage and Unpacking Storage and Unpacking Storage of the UPS If the device is not installed immediately, please consider the following: Always store the device and its accessories in the original packaging.
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 System Description System Description The UPS supplies uninterruptible, single-phase voltage for loads that are critical for operation. In addition to supplying the loads, the device also keeps the in- ternal accumulators charged.
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Installation and Connection of the Installation and Connection of the All the requirements stated in the technical data for the surrounding and opera- tional conditions are to be observed to ensure the perfect operation of the UPS.
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Installation and Connection of the Fig. 6-1 - 1 Connection of the UPS and loads MTD series MTD 3000 10 A 16 A 0.75 mm 1.5 mm Communication Connection of the UPS To exchange data with the UPS, a comfortable communication interface is available.
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Installation and Connection of the The UPS can also be forced to shut down immediately via the serial interface RS232 during support operation. This is triggered by a permanent + 12 V signal on the Rx receiving circuit ("shut down"...
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 The Device and its Operation The Device and its Operation Operating the UPS The operation of this system is characterised by various types of operations and messages. 7.1.1 Types of operation and messages...
Page 41
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 The Device and its Operation Start operation If the mains is present, the start process begins after pressing the two ON keys for 3 seconds. Afterwards, the UPS switches to bypass operation for approximately 10 seconds.
Page 42
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 The Device and its Operation Test operation No test operation is possible for the types 1000RM and 1500RM. If the UPS is in mains operation, you can switch to test operation by simul- taneously pressing, for approx.
Page 43
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 The Device and its Operation Faulty operation If there is a device error, the UPS immediately switches to the inverter mode. The error operation can be triggered by overload, short circuit on the UPS output, over-temperature, inverter error or DC/BUS error.
Page 44
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 The Device and its Operation OUTPUT POWER INSIDE TEMP (inside temperature) NEW AC FAIL (new AC failure) OLD AC FAIL (old AC failure) VOLT / FREQ SET INPUT /OUTPUT...
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 The Device and its Operation Operating Manual for the UPS The operator of this UPS system must always observe the instructions in this manual. The operator may only undertake the following listed...
Page 46
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 The Device and its Operation 7.2.2 Shutting and switching off the UPS With a running UPS, it is shut off by simultaneously pressing both the keys "Menu down" and "Menu up" (hold down for approx. 3 sec.). Press the "POW- ER ON/OFF"...
Page 47
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 The Device and its Operation Basic settings The changing of these parameters is not possible for types 1000RM / 1500RM. The following parameters can be changed via the basic settings: –...
Page 48
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 The Device and its Operation 7.2.4 Starting the test operation This function is not present for the types 1000RM / 1500RM. Before you start the test operation, you should consider the following points: Inform involved employees of your action.
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Starting up the UPS System Starting up the UPS System To ensure error-free start-up, the following points are to be observed: 1. Connect the UPS, with the provided connection cable, to the mains.
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Eliminating Errors Eliminating Errors Only authorised professional staff are to perform work for eliminating er- rors on the UPS system. Problem Possible cause Remedy No function, The mains is not pre-...
Page 51
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Eliminating Errors Problem Possible cause Remedy The UPS is in bypass The solar inverter does Shut down the UPS, operation, the "Fault" not work. remove the connected LED lights up, the loads and inform our display shows "Inverter...
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Software Software A suitable software package can determine and process the settings and the operating states of the UPS via the communication interface. The software packages are available from the manufacturer / dealer or under the provided service hotline.
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Maintenance and Service Maintenance and Service You can assume a long service life and uninterrupted operation with minimum maintenance for your UPS system. The reliability of the UPS will however be determined primarily by the surround- ing conditions.
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Maintenance and Service Remember that the accumulators of the system are discharged after the measurement, which means that the UPS system must work for a few hours (at least 5 hours) in the mains and charging operation before it is ready for use again at approx.
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Maintenance and Service 11.3 Service Report Always enter all the maintenance and service work that has been performed on the UPS system in the service report. Date Executed work...
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Maintenance and Service 11.4 Service Hotline Should problems with the UPS arise against expectations or if you need safety- relevant information, please contact our service hotline under the phone or fax number: Phone no.: 0049 / (0) 741 –...
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Technical Data Technical Data 12.1 Device Specifications for Tower Housing MTD model 1000 1500 2000 3000 Power Power in VA 1000 1500 2000 3000 Power in W 1250 1875...
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Technical Data 12.2 Device Specifications for Rack Mountable MTD model 700RM 1000RM 1500RM 2000RM 3000RM Power Power in VA 1000 1500 2000 3000 Power in W 1250 1875 Bridging...
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Technical Data 12.3 Scope of Delivery / (Optional) Accessories In the following, you will find a list of components that are specially approved and tested by EFFEKTA Regeltechnik GmbH for this UPS (please check the completeness of the delivery immediately after receiving the goods).
Page 62
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Technical Data 12.3.2 Scope of delivery for MTD 1000RM, 1500RM, 2000RM, 3000RM Units Description Function / View: Article no. Scope of de- livery UPS electronics MTD 700RM incl. internal...
UPS MTD 700 / 1000 / 1500 / 2000 / 3000 Requirements from the Declaration of Conformity Requirements from the Declaration of Conformity The CE-labelled UPS to the following EU directives and harmonised standards: EU directives: LVD 2006/95/EC EMC 2004/108/EC...