UPS MKD2000/3000 XL Manual Content Presentation Warranty conditions Limitation of liability Safety General safety instruction Transport and storage Placement Connection Operation Handling batteries Maintenance, servicing and faults Introduction System description Description of MKD series Handling elements on the front side 6.1.1 LCD display 6.1.2...
Page 3
UPS MKD2000/3000 XL Manual Software Maintenance and service 13.1 Measuring and autonomy time 13.2 Replacing the batteries 13.3 Service- log 13.4 Service - hotline: 13.5 Maintenance and service contracts Technical data 14.1 Specifications 14.2 Scope of delivery / optional accessory 14.3 List of wearing parts Requirements for the declaration of conformity...
All trademarks used are the property of their respective owners. ® EFFEKTA is a registered trademark of EFFEKTA Regeltechnik GmbH. We reserve the right to make technical and visual changes, and we are not liable for typographical errors (E&OE). Page 4 of 45...
UPS MKD2000/3000 XL Manual 2 Warranty conditions The delivery receipt is considered to be the initial proof of purchase and should be stored carefully. It is required for all warranty claims. If the product is transferred to another user, then the latter is entitled to claim under the warranty for the remainder of the warranty period.
UPS MKD2000/3000 XL Manual EFFEKTA GmbH does not give any express or implied warranties in relation to this equipment and its quality, performance, merchantability or suitability for a specific purpose. In some countries, the exclusion of implied warranties is not permitted by law.
UPS MKD2000/3000 XL Manual 3 Safety 3.1 General safety instruction Read and observe the user manual and safety instructions in this chapter before taking any further action (transportation, storage, connection, start-up etc.). Since the UPS equipment uses mains voltage and has a suitable energy accumulator (high-capacity batteries) installed either inside or outside the device, the instructions in this chapter are very important for all users and personnel.
UPS MKD2000/3000 XL Manual 3.4 Connection Only connect the UPS to an earthed shock-proof socket or, where a terminal clamp is used, be sure to connect the protective earth conductor. Under no circumstances should the equipment be operated without a protective earth conductor.
UPS MKD2000/3000 XL Manual To protect the UPS, avoid constant load of the output over 80% (especially during battery service). The display of the output load is just supposed to be a reference value. Separate measurements are necessary to ascertain the exact output load.
UPS MKD2000/3000 XL Manual 3.7 Maintenance, servicing and faults Warning – danger of electric shocks. The UPS remains connected to the battery circuit even after it has been disconnected from the mains power supply and has a dangerous voltage potential. Therefore always disconnect the battery circuit before carrying out servicing or maintenance work and make sure that the equipment is isolated from the supply Work on batteries may only be performed and monitored by personnel with...
UPS MKD2000/3000 XL Manual 4 Introduction This manual is intended to provide basic information about single-phase offline UPS equipment, namely the functional principle, use of the various functions and the procedure to follow in the event of faults. In addition, this manual contains information on transportation and storage as well as handling and installation of the UPS equipment.
UPS MKD2000/3000 XL Manual 5 System description The UPS is built following the principle of double conversion. The UPS supplies an uninterrupted, single-phase voltage to users with mission-critical applications. In addition to supplying consumer loads, the equipment also keeps its internal batteries in a fully charged state. In the event of a power failure or power fault (e.g.
UPS MKD2000/3000 XL Manual 6 Description of MKD series In this chapter you will be confronted with the corresponding machine elements, get instructions for the handling and get information concerning the connectings of the UPS. 6.1 Handling elements on the front side Fig..
UPS MKD2000/3000 XL Manual 6.1.1 LCD display Display Function 1) LCD display The LCD display indicates the service mode and several status figures. Following displays can be indicated by pushing the up and down button: Actual status INPUT VOLTAGE OUTPUT VOLTAGE INPUT FREQUENCY OUTPUT FREQUENCY BATTERY VOLTAGE...
UPS MKD2000/3000 XL Manual 6.1.2 Buttons Buttons Function The UPS will be started by pushing this button at the 2) Menu option same time as the menu-down button (3) for about 3sec. The UPS switches over to testing operation by pushing this button at the same time as the menu-up button (4) for about 3sec.
UPS MKD2000/3000 XL Manual 6.1.3 LED display Function 5) NORMAL flashing: mains existent, UPS is switched-off (battery load) duration: mains existent, UPS is switched-on 6) WARNING UPS is in overload, bypass or battery operation. 7) FAULT General fault: inverter fault, over temperature or no battery voltage.
UPS MKD2000/3000 XL Manual 6.2 Elements on the back side Fig. 3: back side view MKD2000 Fig. 4: back side view MKD3000 Page 17 of 45 MKD XL Series...
Page 18
UPS MKD2000/3000 XL Manual Danger! All connectings on the back side (except of RS232-interface) have got circuit potential when attached. Also when uncoupled dangerous voltage is possible on the connections, due to loaded capacities in the inside oft he unit. If all connections of the UPS are existent and the fuse is used, the battery is automatically in service.
Page 19
UPS MKD2000/3000 XL Manual d) Communication Via the serial interface (RS232), all of the relevant UPS (fuse D-Sub 9-jack) data are transmitted to an appropriate primary control unit (e.g. PC). In addition, a defined shutdown signal can be sent to the UPS. Suitable software packages are available for this (see Software chapter).
UPS MKD2000/3000 XL Manual 6.3 Acoustic alert signs of the UPS Support mode and high battery capacity: The acoustic alert sounds in the following sequence (A) [beep -> long pause (4 s) -> beep-> ..., repeating]. Support mode and low battery capacity Normal operation and low battery capacity (battery LOW) Overload 100% - 125%: The acoustic alert sounds in the following sequence (B)
UPS MKD2000/3000 XL Manual 7 Storage and unpacking 7.1 Storage of the UPS If the equipment is not installed immediately, the following should be observed: The equipment and accessories must always be left in the original packaging and stored. The recommended ambient storage temperatures are: +5°C...+30°C. Protect the equipment and its packaging from moisture.
UPS MKD2000/3000 XL Manual 8 Installation and connecting of the UPS All requirements in the technical data regarding environmental and operating conditions must be observed to ensure trouble-free functioning of the UPS. The following must be observed when setting up / installing the UPS equipment: Avoid extremes of temperature and atmospheric humidity.
UPS MKD2000/3000 XL Manual 8.1 Connecting the UPS The models of the MHD series are equipped with plug-type connections. The connection diagram (Fig. ) and the following information have to be observed: Fig. 5: connecting the UPS S: 16A mm² Warning! The UPS equipment contains components with high voltage and amperage.
UPS MKD2000/3000 XL Manual 8.2 Communicational interface of the UPS A convenient communications interface is available that facilitates data exchange with the UPS. The connection should only be made using the cables specified in the “Accessories” chapter. When using the SNMP adapter, the communicational interface is switched-off. Assignment: Fig.
UPS MKD2000/3000 XL Manual Fig. 7 Rear view MKD1000 with Battery pack 8.4 Connection sequence Connect the UPS to the mains making sure that the mains and UPS are safely switched-off beforehand. Before connecting the consumer with the output, the basic configuration (9.2.3) has to be made.
UPS MKD2000/3000 XL Manual 9 Operating and controlling the equipment 9.1 Operating of the UPS There are different operating modes and operating messages of this UPS. 9.1.1 Operating modes and signals The most important modes of the UPS can be described as follows: Charging If the mains power is available and the input fuse is switched on, the UPS is mode:...
Page 27
UPS MKD2000/3000 XL Manual On-line If mains power is available and the UPS has completed the start-up procedure, mode: on-line mode is automatically activated. -> If necessary, the battery pack is also charged in this operating mode. Display/alarm signal: Just the green LED (NORMAL) is flashing continuously, no acoustic signal.
Page 28
UPS MKD2000/3000 XL Manual Testing If the UPS is connected with the mains, testing service can be conducted by service: pushing at the same time for about 3sec button (2) “Menu option” and button (4) “Menu-up”. During this process, after a LED-text, the UPS switches for about 10sec over to battery service.
UPS MKD2000/3000 XL Manual Bypassing mode: 9.1.2 Measured value display Display: By pushing the buttons (3) „Menu-down“ and (4) „Menu-up“ you can switch over to the following displays: INPUT VOLTAGE OUTPUT VOLTAGE INPUT FREQUENCY OUTPUT FREQUENCY BATTERY VOLTAGE BATTERY CAPACITY OUTPUT POWER INSIDE TEMP NEW REC.
UPS MKD2000/3000 XL Manual Basic setting Type After about 2 min. it is automatically switching over to the status display. 9.2 Instruction manual of the UPS The user of the UPS always has to respect the instructions of this manual. The user is only allowed to do the following instructions very carefully: Using of the handling elements: switch-on, start and switch-off the UPS.
UPS MKD2000/3000 XL Manual 9.2.2 Switching-off and power down the UPS To switch the UPS off, the buttons (3) “Menu-down” and (4) “Menu-up” have to be pushed for about 3sec at the same time. At the same time the UPS will be in loading-service to keep the accumulators loaded and ready for service.
Page 32
UPS MKD2000/3000 XL Manual BYPASS LIMIT SET (input voltag) Scroll in switched-off condition, with the button (3) “Menu-down” to the display OUTPUT V&F. The cursor can be set to Vac (output voltage) or Hz (output frequency) by using the button (2) “Menu-option”. In switched-off condition, output voltage or output frequency can be changed by using the buttons (3) “Menu-down”...
UPS MKD2000/3000 XL Manual 9.2.4 Starting the testing mode Before activating the testing service, you should consider following information: Inform involved users about your action. As a precaution save all data of the connected machines. Let all connected machines switched-on, so that the loading conduct can remain.
UPS MKD2000/3000 XL Manual 10 Setting-up of the UPS To guarantee a perfect setting-up, please follow the instructions: 1. Connect the UPS with the mains, by using the enclosed cord. 2. Wait until the system test is finished. 3. Switch the UPS on by using the buttons as already described. 4.
UPS MKD2000/3000 XL Manual 11 Troubleshooting Just authorized persons are allowed to do troubleshooting at the UPS. If failures occur during UPS service, try to solve the problem by following the below mentioned schedule: Problem Possible reason solution No function, The UPS has got no power Assure that all connections are supply or is not switched-on.
Page 36
UPS MKD2000/3000 XL Manual Autonomy time is lower than The accumulators are not Load the accumulators longer nominal. completely loaded or than 8 hours and continue the particular accumulators are test. If the problem remains, the defective. accumulators have to be exchanged.
(chapter „Service“). There you get necessary information about adequate software packages with regard to your application and UPS. Also see our website: http://www.effekta.com/ The following basic functions are supported by all software packages: Capture and display of the mains condition of the UPS;...
UPS MKD2000/3000 XL Manual 13 Maintenance and service You can expect a long service life and trouble-free operation from your UPS equipment as long as you ensure that the necessary minimum level of maintenance is carried out. However, the reliability of the UPS is also significantly affected by environmental conditions.
UPS MKD2000/3000 XL Manual Work on the battery pack may only be carried out by technical personnel who have received specific training in the handling of batteries Note that high voltages remain in the equipment even when it is switched off. This includes the voltage in the battery pack and the charging voltages in mains capacitors, for example.
Internet address: http://www.effekta.com/html/kontakt.html 13.5 Maintenance and service contracts EFFEKTA Regeltechnik GmbH offers you tailored maintenance and customer services that ensure the highest possible reliability and availability of your UPS equipment. In addition, as part of a maintenance contract, our expert technical personnel...
UPS MKD2000/3000 XL Manual 14 Technical data 14.1 Specifications Model: MKD2000 XL MKD3000 XL Power: 2000 VA / 1400 W 3000 VA / 2100 W Mains inpu: Phases 1 external conductor + neutral conductor Voltage window 160 – 300 V AC Bypassing area 176 –...
14.2 Scope of delivery / optional accessory Below is a list of components that have been specifically tested and approved for this UPS by EFFEKTA Regeltechnik GmbH (Please examine the completeness of the scope of delivery after receipt of the product immediately):...
UPS MKD2000/3000 XL Manual USB slot Extension card for USB interface Z0P/USB Relays slot Extension card for relays outputs Z0P/AS400 Opto-coupler Extension card for opto-coupler output Z0P/DB9 SNMP-Mini-Slot Extension card for network interface GE/32CS121MINI X = scope of delivery / O = can be ordered separately as an option 14.3 List of wearing parts The following components are subject to normal wear and tear and are therefore not covered by the warranty for this UPS:...
EN 50091-2 EN 61000-3-2 EN 61000-3-2 EN 62040-1-1 An EU declaration of conformity for CE-labeled products can be requested from the following address: EFFEKTA Regeltechnik GmbH Rheinwaldstr. 34 78628 Rottweil GERMANY Tel.-no.: 0049 / (0) 741–17451-0 HB_EN_ABX11MKS2K03K000000_081111.doc Page 44 of 45...