Demand Group
I-1
Demand type
Set range: SLIDE
/
FIX
Default: SLIDE
I-2
Demand time
Calculating a moving
average time:
Set range 1~60 min
:
Default 15
J-1
Max/Min data Clear
Set range: YES
/
NO
Default: NO
J-2
Demand data Clear
:
Set range
YES
/
NO
Default:
NO
J-3
Max Demand data Clear
:
Set range
YES
/
NO
Default:
NO
:
12
K-1
DI1 Type
Digital intput Type"
di: only upload status
GATE: active energy
accumulated association
M.RST: Maximum Minimum
reset
D.RST Demand reset
:
MD.RST Maximum demand
:
reset
Default M.RST
:
K-2
DI2 Type
Digital input Type
di: only upload status
GATE: active energy
accumulated association
M.RST: Maximum Minimum
reset
D.RST : Demand reset
MD.RST:Maximum demand
reset
Default MD.RST
:
K-3
DO1 Type
Digital Output Type
Set range:
PLS.AE: ctive
A
Energy
output
AL-HI: High Alarm
AL-LO: Low alarm
DO: 485 Control Force Output
Default PLS.AE
:
K-4
DO1 Select
Alarm output DO1
corresponding parameter
Set range:
as Table A
K-5
DO1 SP
Alarm output points:
Set range:
-199999999~999999999
Default 0.00
pulse
:
Need help?
Do you have a question about the CPM-20 Series and is the answer not in the manual?