Battery Module Unit
Battery Model
Battery Cell Type
Operating Voltage Range
Nominal Voltage
Rated Energy
Rated Capacity
Rated Charge/Discharge Current
Maximum Charge/Discharge Current
Protective Class
Ingress Protection Code
CAUTION!
S/N:
Date:
3 Transportation and Storage
3.1 Transportation Requirements
DANGER
Load or unload batteries with caution. Otherwise, the batteries may be shortcircuited or
damaged (such as leakage and crack), catch fire, or explode.
WARNING
Do not move a battery by holding its terminals, bolts, or cables. Otherwise, the battery may
be damaged.
Keep batteries in the correct direction during transportation. They must not be placed upside
down or tilted, and must be protected against falling, mechanical impact, rains, snows, and
falling into water during transportation.
Before unpacking, storage, and transportation, ensure that the packing cases are intact, and
the batteries are correctly placed according to the labels on the packing cases. Do not place
a battery upside down or vertically, lay it on one side, or tilt it.
Stack the batteries according to the stacking requirements on the packing cases.
Ensure that the batteries do not fall or get damaged. Otherwise, they will need to be scrapped.
Do not dispose of batteries in a fire. The batteries may explode.
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes.
It may be toxic.
A Battery can present a risk of electric shock and burns by high short-circuit current.
Failed batteries can reach temperatures that exceed the burn thresholds for touchable surface.
HV48100 BMU
LFP Battery
47.5V~57.6V
51.2V
5.12kWh
100Ah
50A
50A
Class I
IP20
IFpP54/150/120[(8S)2S]E/-10+50/95
Shanghai PYTES Energy Co., Ltd.
18
MADE IN CHINA
Need help?
Do you have a question about the HV48100 and is the answer not in the manual?