Controller requirements and specifications
Neutral
5- 2
NOTE: All power outlets must be dedicated to this equipment.
When determining the electrical connections for printing system,
make sure that:
-Each power cord has a separate circuit.
-The printer power cord configurations match your receptacle.
-Your electrical outlets are within the required specifications.
50 Hz systems: Ensure that power connections are per local
codes/regulations.
The following figure shows American, Canadian, and European
wall outlets in which to plug the controller.
NOTE: The optional 9 track and 18/36 track tape drives each
require an outlet identical to the one that is shown for the
controller.
USA/Canada
AC Neutral
(ACN)
United Kingdom
Figure 5-1 Multinational wall outlet configurations
The required wall outlet voltages for USA / Canada, United
Kingdom, and the rest of Europe are as follows:
USA / Canada: The voltage at the wall outlet is 100 to 120
VAC between AC hot and neutral, and between AC hot and
GND. The voltage is less than three VAC between GND and
neutral.
United Kingdom: The voltage at the wall receptacle is 200 to
240 VAC between live and neutral, and between live and
earth. The voltage is less than three VAC between earth and
neutral.
Europe: The voltage at the wall receptacle is 200 to 240 VAC
between supply pins. The voltage between one supply pin and
AC Hot (ACH)
Earth Ground (GND)
Europe
Earth
Live
Supply
Installation Planning Guide
Earth