5. Fire Circuit activated.
Check devices are normally closed.
Check cable runs for broken circuits.
If no Fire devices on system
Link out FR circuit.
6. Tamper Alarm activated.
Check Tamper circuits:
1. B- shorted to BT (Bell Tamper)
2. T T (Global Tamper circuit)
8. Control Panel Lid Tamper.
4. Remote Keypad Lid Tamper.
Locate open Tamper circuit.
Close circuit.
Try resetting control panel.
If still unable to locate fault:
1. Remove cables from (B- BT) (T T)
2. Replace with links i.e Closed circuits.
3. Replace Panel lid and reset system.
4. Reconnect the tamper circuits, one at a time,
until the fault is identified.
7. Engineer Mode.
To enter Engineer mode:
Enter (€)(0) (@)(9)(9)(9) (Factory set 9999)
To exit Engineer mode:
Enter @@a)
(9)(Q) (9) (9) (Factory set 9999)
8. Fault light stays on (Not flashing).
1. Check 1 Amp aux fuse.
2. Check Sounder fuse
3. Check N.V.M Jumper link is disconnected.
(Fuses located on main processor board -Top Left Hand Side)
9. Mains Failure.
1. Check 2Amp fuse in fuse spur.
RDOC 279B issue 1