Download Print this page

ActronAir MWC-B01CS Operation Manual page 50

Vrf basic wired controller

Advertisement

Parameter
Parameter Name
Code
N53
Stop delay when
unattended
N54
ETA function setting 00/01
N55
Energy rating of
cooling ETA
N56
Energy rating of
heating ETA
N57
On-site fanspeed
adjustment factor
N58
Initial static pressure
detection
N59
Filter ending - initial
static pressure
setting
N60
Ambient temperature
when preheating is
turned on
N61
Fresh air dry contact 1
Default
Parameter Range
Value
00/01/02/03/04/05
01
00
00/01/02
00
00/01/02
00
00/01/02/03/04/05/06
00
00/01
00
00/01/.../19
00
00/01/02
02
00
00/01
47
Remarks
00: 15 min
01: 30 min
02: 45 min
03: 60 min
04: 90 min
05: 120 min
00: Off
01: On
00: Level 1
01: Level 2
02: Level 3
00: Level 1
01: Level 2
02: Level 3
00: 1
01: 1.1
02: 1.05
03: 1.15
04: 0.95
05: 0.9
06: 0.85
00: Not reset
01: Reset
00-10Pa/01-20Pa/02-30Pa ~19-200Pa
00: 5°C
01: 0°C
02: (-5)°C
2nd generation Function 00: Disconnect; 01: Start

Advertisement

loading