ActronAir MWC-B01CS Operation Manual page 48

Vrf basic wired controller

Advertisement

Parameter
Parameter Name
Code
Q4/Q4min air outlet
N35
4 setting
Cooling only for IDU 00/01
N36
One-to-more of wired
N37
controller enabled
Long-distance on/off
N38
function setting
Delay time setting
N39
(Using long-distance
on/off port to turn off
the IDU)
Long-distance alarm
N40
function setting
Faster cooling mode
N41
setting
Sterilization function 00/01
N42
Sterilization setting
N43
Silent mode setting
N44
ECO
N45
Parameter Range Default
Value
00/01
00
00
00/01
00
00/01
00
00/01/.../06
00
00/01
00
00/01
00
00
00/01/02
00
00/01
00
00/01
00
45
Remarks
00 - Free control
01 - Off
00: Cooling and heating
01: Cooling only
00: No
01: Yes
00: Turn off the IDU when closed
01: Turn off the IDU when open
Note: When turn off the IDU by long-distance
on/off port, the wired controller for IDU will display
d6
00 - No delay
01 - 1min delay
02 - 2min
03 - 3min
04 - 4min
05 - 5min
06 - 10min
00: Alarm when closed
01: Alarm when open
00: Off
01: On
00: No sterilization function (default)
01: Plasma disinfection
00: Auto on
01: Forced on
02: Forced off
00: Off
01: On
00: Off
01: On