Vrf basic wired controller

Advertisement

Parameter
Parameter Name
Code
C07
Wired controller
Follow Me
temperature
correction
C08
Lower limit of
cooling temperature
C09
Upper limit of
cooling temperature
C10
Lower limit of
heating temperature
C11
Upper limit of
heating temperature
C12
Set to display
0.5°C
C13
Wired controller
button light setting
C14
Send configuration
parameters stored in
the wired controller
to IDU by one click
C15
Buzzer of the wired
controller rings
C16
Backlight time
Parameter
Default Value
Range
-5.0 to 5.0°C
Celsius: -1.0
16°C to 30°C
IDU: 16°C
FAPU: 13°C
AHUKit: 10°C
16°C to 30°C
30°C
V8: °C: 16°C
V8: 16°C
-30°C((default16°C)
V6: 17°C
V6: °C: 17°C
FAPU: 13°C
-30°C((default17°C)
AHUKit: 10°C
16°C to 30°C
30°C
00/01
01
00/01
01
00/01/02/03/04
01
00/01
01
00/01/02
00
35
Remarks
Note: Accuracy is 0.5°C.
00: No
01: Yes
00: Off
01: On
The latest configuration parameters stored in
the wired controller will be changed after
power on for two hours or after configuration
parameters of wired controller are changed.
Note: 1: Applicable to one-to-one scenario
2: Only for 2nd generation IDU
00: No
01: Yes
00: 15s
01: 30s
02: 60s