Ordering Accessories And Replacement Parts; Inspection; Visual Inspection; Anti-Condensation Heater - GE GL 311 F3/4031 P/VE Operating Instructions Manual

High voltage circuit breaker
Hide thumbs Also See for GL 311 F3/4031 P/VE:
Table of Contents

Advertisement

9.1

Ordering Accessories and Replacement Parts

9.2

Inspection

DANGER
9.2.1

Visual Inspection

9.2.2

Anti-Condensation Heater

CAUTION
9.2.3

Checking Gas Pressure

REV7
/REV3
The following data are required for an order:
- Type designation
- Serial number
- Instruction manual number
- Figure number and position number in the figure
- Part description
- Quantity required
The circuit breaker may remain in operation during inspection.
Danger due to electric shock.
Therefore:
- Never reach into the high voltage insulation area of the
circuit breaker.
- Never touch the contacts of the circuit breaker control
system.
Follow all regional and operator-specified safety precautions.
• Check the circuit breaker carefully for damage or corrosion. In
particular, check the insulators from the ground for possible
damage.
• If corrosion is detected, take steps to prevent or control corrosion.
• Check the ventilation ports and vents in the mechanism cabinet to
make sure they are clear. Remove any blockages.
Check the heat dissipation from the anti-condensation heater. To
do so, place a contact thermometer on the anti-condensation hea-
ter and measure the temperature rise.
The anti-condensation heating unit gets hot during operation.
It can burn skin or clothing.
Therefore:
- Never touch the heating unit directly.
Check the density monitor indicator. If the indicator is not in the
green area, top up with gas until rated pressure is reached (see
"Filling the Breaker with Gas" on Page 56).
OI 250 (EN)
I
NSPECTION AND
on nameplate
on nameplate
on cover
M
AINTENANCE
77 / 146