SECTION 6 – ACCESSORIES DESCRIPTION
WARNING
IMPROPER INSTALLATION, OPERATION AND
MAINTENANCE
Ensure only qualified personnel install, operate, service
and maintain all electrical equipment.
Failure to comply with these instructions could
result in death or serious injury.

GENERAL INFORMATION

A wide range of optional accessories are interchangeable
across all EntelliGuard G power circuit breakers, regardless
of nominal rating or envelope/frame size. Each accessory
incorporates easy-fit design features for quick installation,
either at the factory or in the field (Fig. 6.1).
NOTE: Replacement accessories have an "R" at the end of
the catalog number as shown.
Table 6.1 Motor Operators
Envelope
Power
Consumption
DC – 300 W
1
AC – 350 VA
DC – 480 W
2 and 3
AC – 560 VA
 Spring charge contact is power rated only, as shown below.
AC Ratings
Voltage
Amps
AC21-15 A
110 V-130 V
AC23-10 A
AC21-10 A
220 V -240 V
AC23-5 A
©2012 General Electric All Rights Reserved
Courtesy of store.ips.us
Nominal Control
IEC Range (85% to 110%)
Voltage
24 Vdc/30 Vdc
20.4 V to 26.4 V
48 Vdc
40.8 V to 52.87 V
60 Vdc
51 V to 66 V
72 Vdc
61.2V to 79.2 V
110 Vdc/130 Vdc
106.25 V to 137.5 V
250 Vdc
212.5 V to 275 V
48 Vac
40.8 V to 52.87 V
120 Vac
102 V to 132 V
240 Vac
204 V to 264 V
277 Vac
235.5 V to 304.7 V
24 Vdc/30 Vdc
20.4 V to 26.4 V
48 Vdc
40.8 V to 52.87 V
60 Vdc
51 V to 66 V
72 Vdc
61.2 V to 79.2 V
110 Vdc/130 Vdc
106.25 V to 137.5 V
250 Vdc
212.5 V to 275 V
48 Vac
40.8 V to 52.87 V
120 Vac
102 V to 132 V
240 Vac
204 V to 264 V
27 Vac
235.5 V to 304.7 V
DC Ratings
Voltage
Amps
24 V
DC21-15 A
110 V-130 V
DC21-10 A
250 V
DC21-5 A
-
-
EntelliGuard® G Circuit Breaker
Section 6 – Accessories Description
Figure 6.1. Accessory Mounting

INDIVIDUAL ACCESSORIES

Motorized Spring Charging Unit

The unique motor/gearbox unit is specially designed to
operate with the full range of EntelliGuard G. It is easily
fitted with three heavy-duty bolts. After a breaker close
operation, the unit automatically recharges the spring and
makes it ready for immediate open and re-close should the
need arise. High speed recharging ensures that the springs
are fully charged within approximately three seconds
following a release. All electrically operated (EO) ANSI/UL
breakers are equipped with "Spring Charged" contacts
(GSCC1R) for status indication (Table 6.1).
ANSI Range
UL Range
(85% to 110%)
-
20.4 V to 26.4 V
38 V to 56 V
40.8 V to 52.87 V
-
51 V to 66 V
-
61.2 V to 79.2 V
100 V to 140 V
106.25 V to 137.5 V
200 V to 280 V
212.5 V to 275 V
-
40.8 V to 52.87 V
104 V to 127 V
102 V to 132 V
208 V to 254 V
204 V to 264 V
-
235.5 V to 304.7 V
-
20.4 V to 26.4 V
38 V to 56 V
40.8 V to 52.87 V
-
51 V to 66 V
-
61.2 V to 79.2 V
100 V to 140 V
106.25 V to 137.5 V
200 V to 280 V
212.5 V to 275 V
-
40.8 V to 52.87 V
104 V to 127V
102 V to 132 V
208 V to 254 V
204 V to 264 V
-
235.5 V to 304.7 V
 Spring charge time = 3 sec max.
 Recommended fuse amps: contact factory.
 Duty cycle = 2/min.
 Envelope 1 motors: running VA ~ 300 VA; inrush = 2 to 3 times.
 Envelope 2 and 3 motors: running VA ~ 450 VA; inrush = 2 to 3 times.
Cat No.
GM0124DR
GM01048DR
GM01060DR
GM01072DR
GM0113ODR
GM01250DR
GM01048AR
GM01120AR
GM01240AR
GM01277AR
GM0224DR
GM02048DR
GM02060DR
GM02072DR
GM0213ODR
GM02250DR
GM02048AR
GM02120AR
GM02240AR
GM02277AR
27