Mounting The Guide Shaft - GE GL 311 F3/4031 P/VE Operating Instructions Manual

High voltage circuit breaker
Hide thumbs Also See for GL 311 F3/4031 P/VE:
Table of Contents

Advertisement

R
ECONDITIONING
10.1.9

Mounting the Guide Shaft

90 / 146
• Insert the interrupter unit (5) and the movable contact system (6)
into the fixed contact (7) so that the shaft holes in the guide levers
(8) and fixed contact (7) are lined up.
• Place the spacer sleeve (21) between the levers.
• Connect the guide lever and fixed contact to the guide shaft (28).
• Coat a new screw (22) with locking adhesive per S1.
• Fasten the shaft with the locking plate (23) and the new screw
(22). Tighten to a torque of 17Nm.
5
Interrupter unit
6
Movable contact system
7
Fixed contact
8
Guide lever
17
Socket head cap screw, M8x12 A2-70
21
Spacer sleeve
23
Locking plate
28
Guide shaft
OI 250 (EN)
6
5
23 22
8
28
21
7
1x
1x
1x
2x
1x
1x
1x
1x
REV7
/REV7