Transport at the Installation Site

CAUTION
DANGER
16 / 146
H
EXAFLUORIDE
All pressure specifications are given in terms of relative pressure
(p
).
e
Pole columns are shipped at a gas gauge pressure of approxima-
tely 0.03 MPa (p
) (0.3 bar).
e
The bursting of pressurized parts such as insulators or bushings
may result in property damage or personal injury.
Therefore:
- Do not move pole columns if the gas gauge pressure is
higher than the shipping pressure.
OI 250 (EN)