GE GL 311 F3/4031 P/VE Operating Instructions Manual page 70

High voltage circuit breaker
Hide thumbs Also See for GL 311 F3/4031 P/VE:
Table of Contents

Advertisement

T
ROUBLESHOOTING
CAUTION
70 / 146
If the drum controller is positioned incorrectly, operation of the
mechanism will be negatively affected.
Therefore check the position of the drum controller.
- Motor limit switch: Contacts 15-16 are open in the "closing
spring discharged" position.
- Auxiliary switch: Contacts 15-16 are closed in breaker posi-
tion "O".
• Install the motor limit switch (or the auxiliary switch).
• Tighten the M5 screws.
• Mount the drive and connecting rods.
• Reinstall the locking clamps.
• Tighten the wire connections.
• Check to see whether there is play in the linkage.